Summary

Vaillant's F-code scheme is the most consistent of the major UK brands: an F.28 on a 2006 ecoTEC plus 831 means the same thing as an F.28 on a 2024 ecoTEC plus 835, and Vaillant publishes the full table in every installation and servicing manual. That consistency makes the codes genuinely useful for phone triage — a customer reading "F.22" off the display is almost certainly describing low pressure and can be talked through repressurising; a customer reading "F.75" has a fault that needs a visit; a customer reading "F.61" or "F.62" should be told to leave the boiler off until an engineer arrives.

The scheme does have traps. F.75 is the Vaillant code engineers argue about most: the control expects to see system pressure rise slightly when the pump starts, and F.75 means it did not. That can be a failed pump, a stuck or scaled pressure sensor, air in the pump, or a system so full of sludge the pump cannot shift it — and on the 2005–2015 ecoTEC plus the sensor was a known weak point, so a sensor is often changed first and the pump condemned second when the fault returns. F.28 versus F.29 is the other: F.28 is failure to light, F.29 is a flame that lit and went out, and they point at different parts of the gas path. And the status codes (S.xx — S.04 burner on, S.53 water shortage/pressure wait, S.76 low pressure blocking) shown during normal operation are not faults, though customers frequently report them as such.

This guide tabulates the F-codes seen on domestic Vaillant boilers in the UK, gives the diagnostic path for the six that dominate callouts, flags the gas-safety codes that must never be cleared and left, and gives decision trees for F.28 and F.75. Codes marked **** should be checked against the model's own manual before a part is ordered.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Code Meaning Type Most likely causes Urgency
F.00 / F.01 Flow / return NTC open circuit Lockout Thermistor, plug, wiring Medium
F.10 / F.11 Flow / return NTC short circuit Lockout Thermistor, damp plug, wiring Medium
F.13 DHW NTC fault Lockout Thermistor, wiring Medium
F.20 Safety cut-out — overheat Lockout Pump, blockage, air, closed valves, limiter High — do not keep resetting
F.22 Dry fire / low water pressure Blocking (auto-restart on refill) Leak, PRV, bleed, expansion vessel, sensor Medium
F.23 Flow–return ΔT too large Lockout Low circulation, pump, sensor pockets swapped Medium–High
F.24 Temperature rise too fast Lockout No/low flow, pump, air, closed valves Medium–High
F.25 Flue gas over-temperature Lockout Combustion, flue restriction, heat exchanger High
F.26 Gas valve stepper / fuel valve fault Lockout Gas valve, wiring, PCB High
F.27 False flame Lockout Electrode tracking, gas valve passing, PCB High — gas safety
F.28 Ignition failure at start-up Lockout No gas, frozen condensate, electrode, gas valve, flue, ignitor/PCB High
F.29 Flame loss during operation Lockout Gas pressure under load, flue recirculation, electrode, gas valve High
F.32 Fan fault Lockout Fan, tacho wiring, blocked flue, PCB High
F.49 eBUS fault Lockout Controls wiring short, eBUS device Medium
F.54 Gas pressure fault (with F.28/F.29) Lockout Inlet pressure, meter, gas valve closed High
F.61 Gas valve control fault Lockout Valve wiring short, valve, electronics High — gas safety
F.62 Gas valve switch-off delay Lockout Valve slow/leaking, electronics High — gas safety
F.63 EEPROM / PCB Lockout PCB Medium–High
F.64 Electronics / NTC fault Lockout NTC short, PCB Medium
F.65 Electronics temperature too high Lockout PCB overheating, location, ventilation Medium
F.67 Flame signal implausible Lockout Electrode, PCB High
F.70 Invalid device code Lockout Unprogrammed/wrong PCB or display after replacement Medium
F.71–F.74 Pressure sensor / NTC plausibility Lockout Sensor stuck, wiring Medium
F.75 No pressure change on pump start Lockout Pump, pressure sensor, air in pump, sludge Medium–High
F.76 Primary heat exchanger overheat protection Lockout Exchanger overheated/cracked, fuse High
F.77 Condensate pump / flue damper fault Lockout Condensate pump, damper, wiring Medium
F.83–F.85 Temperature plausibility / sensor swap (ecoTEC plus 8xx) Lockout NTCs swapped or loose, low water Medium
S.53 Status: waiting, water shortage / ΔT Status, not fault Low flow, pressure —
S.76 Status: pressure too low, blocking Status, not fault Low pressure —
Any code not listed Unconfirmed for this model — **** —

Detailed Guidance

What does F.22 mean on a Vaillant boiler?

F.22 — Dry fire / low water pressure. The pressure sensor reads below the minimum (around 0.5 bar on most models), or the control has detected no water in the primary. The boiler blocks and, on most ecoTEC models, restarts itself once pressure is restored above the threshold — so the customer often reports "it comes back on when I top it up".

Causes: system leak (radiator valve, tail, joint, automatic air vent), PRV discharging (wet discharge pipe outside — expansion vessel is the usual root), radiators bled without topping up, expansion vessel lost charge or failed, pressure sensor fault (reads low while the gauge reads normal — the two are separate on many Vaillants, which makes this easy to check).

Path: compare gauge and displayed pressure (d.-parameter or live pressure display) → repressurise to 1–1.5 bar cold via the filling loop → monitor a heating cycle (0.3–0.5 bar rise normal; more = expansion vessel) → recurring loss: PRV and systematic leak check; see boiler loses pressure repeatedly and boiler pressure relief valve discharging. If the gauge is normal and the display reads low, the sensor or its wiring is at fault.

What does F.28 mean on a Vaillant boiler?

F.28 — Ignition failure. The boiler ran its start-up sequence (fan, ignition, gas valve) without establishing a flame within the permitted attempts and locked out. The commonest Vaillant winter callout. F.54 alongside it means the control specifically suspects gas pressure.

Causes, in rough order of frequency:

  1. No gas — pre-payment credit, meter valve, appliance isolation valve; check another appliance.
  2. Frozen or blocked condensate — ecoTEC combis back up through the siphon trap; a frozen external run, or a trap full of debris in summer, stops ignition. Thaw with warm water and fix the route; see condensate pipe frozen boiler lockout and condensate pipe installation.
  3. Ignition electrode — the ecoTEC's combined ignition/ionisation electrode is a service item: erosion, cracks, carbon, gap, lead.
  4. Low inlet pressure / gas valve — working pressure at the test point below ~17 mbar natural gas under load; no click from the valve.
  5. Flue — blocked terminal, displaced or failed seals, recirculation.
  6. Ignitor / PCB — no spark with electrode and lead proven.

Path: gas at other appliances → condensate → reset once and observe the sequence → no spark: electrode, lead, ignitor, PCB → spark but no flame: gas pressure, gas valve, flue.

What does F.29 mean on a Vaillant boiler?

F.29 — Flame loss during operation. The burner lit and ran, then the ionisation signal was lost. Different from F.28: the ignition chain works. Look at gas supply under load (pressure drop when other appliances run — pipe sizing, meter regulator; see gas pipe sizing), flue recirculation in wind (terminal position, seals), electrode signal quality (worn electrode gives a marginal ionisation current that drops out), gas valve modulation, and condensate partially backing up during a long run. A combustion check with a flue gas analyser (see flue gas analysis) is the right confirmation.

What does F.75 mean on a Vaillant boiler?

F.75 — No pressure change detected on pump start. Vaillant's control expects system pressure to rise by a small amount (roughly 0.1–0.2 bar) when the pump starts; if it does not, F.75. The logic is that if the pump is running and the sensor sees no change, either the pump is not moving water or the sensor cannot see it.

Causes: pressure sensor stuck or scaled (very common on 2005–2015 ecoTEC plus — the sensor sits in a pocket that silts up), pump failed or air-locked, pump running on too low a speed setting, system heavily sludged so the pump cannot create the pressure rise, air in the system, sensor wiring.

Path: check the sensor first — clean or replace (it is cheap), and clear the pocket → bleed the pump and check it spins → check pump speed setting (ecoTEC plus pumps have a speed selector; too low a setting on a large system gives F.75) → check for sludge (magnetic filter contents, ΔT, radiator cold spots) → pump. If a sensor has already been changed and F.75 returns, it is the pump or the system water quality — clean to BS 7593:2019 (see powerflush).

F.61 / F.62 / F.27 — gas valve and false flame

These are the codes to treat as gas safety matters:

Do not reset and leave. Prove there is no gas passing at the valve outlet with the valve de-energised, check the harness, then replace the valve or PCB as the evidence directs.

F.20, F.23, F.24, F.76 — circulation and overheat

F.20 is the safety cut-out at around 97 °C flow; F.24 is a rate of temperature rise that implies no flow; F.23 is a flow–return ΔT larger than the control permits (low circulation, or flow and return NTCs in the wrong pockets after a repair); F.76 on some models is the heat exchanger's own thermal fuse/limiter tripping, which often means the aluminium exchanger has already been damaged. All point to pump, air, blockage, closed zones or sludge. Let the boiler cool, prove the pump, prove flow through the system, check bypass and TRVs, check the exchanger for restriction, and only then suspect sensors. See boiler kettling and system cleansing inhibitors.

F.32 — fan

Fan speed outside tolerance. Check the flue (blocked terminal, crushed flexible section, frost), fan plug and tacho lead, bearing noise (see boiler fan noise diagnosis), supply voltage to the fan, then fan or PCB. Combustion check after any flue or fan work.

Decision tree — F.28 ignition failure

F.28 (± F.54) displayed
        |
Gas at other appliances?
        |
   +----+---------+
   |              |
  No             Yes
   |              |
Restore,      Condensate frozen / siphon blocked?
reset              |
              +----+------+
              |           |
             Yes          No
              |           |
         Thaw, reset,   Reset once; watch sequence
         fix route         |
                     +-----+------------------+
                     |                        |
               Fan runs, no spark       Spark, no flame
                     |                        |
               Electrode, lead,         Working pressure at
               ignitor, PCB             test point under load;
                                        gas valve click;
                                        flue terminal/seals

Decision tree — F.75

F.75 displayed
      |
Gauge vs displayed pressure agree?
      |
  +---+----------------+
  |                    |
 No                   Yes
  |                    |
Pressure sensor:   Pump spins when energised?
clean pocket,          |
replace sensor    +----+--------+
                  |             |
                 No            Yes
                  |             |
            Pump, supply,   Pump speed setting;
            PCB output      air in pump; sludge
                            (filter, dT, cold spots)
                            -> clean to BS 7593,
                            then pump if persists

Frequently Asked Questions

How do I reset a Vaillant boiler?

Press the reset button — the flame-with-a-cross symbol on the fascia — once. The display clears and the boiler attempts a restart. F.22 clears itself when pressure is restored and does not need a reset on most models. If a code returns immediately the fault is active; the control also limits how many F.28/F.29 resets it will accept in a period. Never keep resetting F.20 (overheat), F.27, F.61 or F.62 (gas valve/false flame).

Is S.53 or S.76 a fault code?

No. S-codes are status codes shown during normal operation. S.53 means the boiler is waiting because of a water-shortage or ΔT condition (often low flow — it may precede F.22, F.23 or F.75); S.76 means pressure is too low and the boiler is blocking until it is topped up. They tell you what the boiler is doing, not that it has failed — but a boiler sitting on S.53 for long periods has a circulation or pressure problem worth looking at.

What is the difference between F.28 and F.29?

F.28 is failure to light: the boiler never established a flame during start-up. F.29 is flame loss: it lit, ran, and the flame went out. F.28 with no spark is the ignition chain (electrode, lead, ignitor, PCB); F.28 with a spark is gas supply or valve; F.29 is gas pressure under load, flue recirculation, a marginal electrode or a valve modulating badly. The distinction halves the diagnosis time.

Why does F.75 keep coming back after the pressure sensor was replaced?

Because the sensor was only ever half the story. F.75 means the control saw no pressure rise when the pump started. If a new sensor sees none either, the pump is not creating one — it is air-locked, on too low a speed, failing, or fighting a sludged system. Check pump speed and bleed it, look at the magnetic filter and radiator cold spots for sludge, clean the system to BS 7593:2019 if needed, and replace the pump if it still fails.

How much does a typical Vaillant repair cost?

Indicative, excluding labour: pressure sensor £30–£70; NTC £15–£35; electrode £30–£60; fan £150–£300; gas valve £140–£260; PCB £220–£400; pump £130–£250; diverter valve £120–£220; plate heat exchanger £150–£300; main heat exchanger £400–£800. Labour typically £80–£150 for diagnosis plus repair time. **** Vaillant guarantees run 5–10+ years on many ecoTEC models when installed by a Vaillant Advance installer and registered — check before quoting.