Summary
Vaillant's F-code scheme is the most consistent of the major UK brands: an F.28 on a 2006 ecoTEC plus 831 means the same thing as an F.28 on a 2024 ecoTEC plus 835, and Vaillant publishes the full table in every installation and servicing manual. That consistency makes the codes genuinely useful for phone triage — a customer reading "F.22" off the display is almost certainly describing low pressure and can be talked through repressurising; a customer reading "F.75" has a fault that needs a visit; a customer reading "F.61" or "F.62" should be told to leave the boiler off until an engineer arrives.
The scheme does have traps. F.75 is the Vaillant code engineers argue about most: the control expects to see system pressure rise slightly when the pump starts, and F.75 means it did not. That can be a failed pump, a stuck or scaled pressure sensor, air in the pump, or a system so full of sludge the pump cannot shift it — and on the 2005–2015 ecoTEC plus the sensor was a known weak point, so a sensor is often changed first and the pump condemned second when the fault returns. F.28 versus F.29 is the other: F.28 is failure to light, F.29 is a flame that lit and went out, and they point at different parts of the gas path. And the status codes (S.xx — S.04 burner on, S.53 water shortage/pressure wait, S.76 low pressure blocking) shown during normal operation are not faults, though customers frequently report them as such.
This guide tabulates the F-codes seen on domestic Vaillant boilers in the UK, gives the diagnostic path for the six that dominate callouts, flags the gas-safety codes that must never be cleared and left, and gives decision trees for F.28 and F.75. Codes marked **** should be checked against the model's own manual before a part is ordered.
Key Facts
- F-codes = faults (boiler locked out or blocking); S-codes = status (normal operation — S.00 no demand, S.04 burner on heating, S.14 burner on DHW, S.53 waiting due to water shortage, S.76 pressure too low); P-codes = test programmes; d-codes = diagnostic parameters
- F.22 — dry fire / low water pressure (sensor reads below ~0.5 bar, or no water detected). Repressurise to 1–1.5 bar cold; the boiler restarts automatically on most models when pressure is restored
- F.28 — ignition failure: no flame established during start-up attempts. Gas supply, frozen condensate, electrode, gas valve, flue, PCB/ignitor
- F.29 — flame loss during operation. Gas pressure under load, flue recirculation, electrode/ionisation signal, gas valve
- F.54 — gas pressure fault (insufficient inlet pressure or gas valve closed); appears in combination with F.28/F.29
- F.75 — no pressure change detected on pump start (pump, pressure sensor, air in pump, severely sludged system). The most-misdiagnosed Vaillant code
- F.61 — gas valve control fault (short to earth in the valve wiring, defective valve, defective electronics); F.62 — gas valve switch-off delay (valve slow to close or leaking) — both gas safety related
- F.20 — safety cut-out: flow temperature above ~97 °C (overheat); circulation fault — pump, blockage, air, closed valves. Do not reset repeatedly
- F.27 — false flame: flame signal with gas valve closed — gas safety related
- F.00 / F.01 — flow / return NTC open circuit; F.10 / F.11 — flow / return NTC short circuit; F.13 — hot water (DHW) NTC fault
- F.23 — flow/return temperature difference too large (low circulation); F.24 — temperature rise too fast (no or low flow); both circulation
- F.25 — flue gas temperature too high (flue gas safety cut-out); F.26 — gas valve stepper motor / fuel valve fault
- F.32 — fan fault (speed outside tolerance, tacho); F.33 — fan fault / flue (some models)
- F.49 — eBUS short circuit / low voltage (controls wiring); F.63 — EEPROM / PCB; F.64 — electronics / NTC fault; F.65 — electronics overheat; F.67 — flame signal implausible; F.70 — invalid device code (wrong or unprogrammed PCB / display); F.71–F.74 — pressure sensor / NTC plausibility faults
- F.76 — overheat protection on primary heat exchanger (fuse/limiter on the exchanger — often means the exchanger has overheated and cracked); F.77 — condensate pump / flue damper fault (where fitted)
- F.83 / F.84 / F.85 — flow/return temperature plausibility and sensor swap faults on ecoTEC plus 8xx/9xx
- Reset — press the reset button (flame-with-cross symbol) once; if the code returns immediately the fault is active. Repeated F.28/F.29 resets are limited by the control
- Frozen condensate is the leading winter cause of F.28 on ecoTEC combis; Vaillant condensate trap and siphon blockages also cause F.28 in summer
- Gas Safety (Installation and Use) Regulations 1998 — all behind-the-case work is for a Gas Safe registered engineer; Benchmark record should be checked first
- Parts pricing (indicative, excluding labour): pressure sensor £30–£70; NTC £15–£35; electrode £30–£60; fan £150–£300; gas valve £140–£260; PCB £220–£400; pump £130–£250; diverter valve £120–£220; plate heat exchanger £150–£300 ****
Quick Reference Table
Diagnosed the problem? Create a repair quote in minutes with squote.
Try squote free →| Code | Meaning | Type | Most likely causes | Urgency |
|---|---|---|---|---|
| F.00 / F.01 | Flow / return NTC open circuit | Lockout | Thermistor, plug, wiring | Medium |
| F.10 / F.11 | Flow / return NTC short circuit | Lockout | Thermistor, damp plug, wiring | Medium |
| F.13 | DHW NTC fault | Lockout | Thermistor, wiring | Medium |
| F.20 | Safety cut-out — overheat | Lockout | Pump, blockage, air, closed valves, limiter | High — do not keep resetting |
| F.22 | Dry fire / low water pressure | Blocking (auto-restart on refill) | Leak, PRV, bleed, expansion vessel, sensor | Medium |
| F.23 | Flow–return ΔT too large | Lockout | Low circulation, pump, sensor pockets swapped | Medium–High |
| F.24 | Temperature rise too fast | Lockout | No/low flow, pump, air, closed valves | Medium–High |
| F.25 | Flue gas over-temperature | Lockout | Combustion, flue restriction, heat exchanger | High |
| F.26 | Gas valve stepper / fuel valve fault | Lockout | Gas valve, wiring, PCB | High |
| F.27 | False flame | Lockout | Electrode tracking, gas valve passing, PCB | High — gas safety |
| F.28 | Ignition failure at start-up | Lockout | No gas, frozen condensate, electrode, gas valve, flue, ignitor/PCB | High |
| F.29 | Flame loss during operation | Lockout | Gas pressure under load, flue recirculation, electrode, gas valve | High |
| F.32 | Fan fault | Lockout | Fan, tacho wiring, blocked flue, PCB | High |
| F.49 | eBUS fault | Lockout | Controls wiring short, eBUS device | Medium |
| F.54 | Gas pressure fault (with F.28/F.29) | Lockout | Inlet pressure, meter, gas valve closed | High |
| F.61 | Gas valve control fault | Lockout | Valve wiring short, valve, electronics | High — gas safety |
| F.62 | Gas valve switch-off delay | Lockout | Valve slow/leaking, electronics | High — gas safety |
| F.63 | EEPROM / PCB | Lockout | PCB | Medium–High |
| F.64 | Electronics / NTC fault | Lockout | NTC short, PCB | Medium |
| F.65 | Electronics temperature too high | Lockout | PCB overheating, location, ventilation | Medium |
| F.67 | Flame signal implausible | Lockout | Electrode, PCB | High |
| F.70 | Invalid device code | Lockout | Unprogrammed/wrong PCB or display after replacement | Medium |
| F.71–F.74 | Pressure sensor / NTC plausibility | Lockout | Sensor stuck, wiring | Medium |
| F.75 | No pressure change on pump start | Lockout | Pump, pressure sensor, air in pump, sludge | Medium–High |
| F.76 | Primary heat exchanger overheat protection | Lockout | Exchanger overheated/cracked, fuse | High |
| F.77 | Condensate pump / flue damper fault | Lockout | Condensate pump, damper, wiring | Medium |
| F.83–F.85 | Temperature plausibility / sensor swap (ecoTEC plus 8xx) | Lockout | NTCs swapped or loose, low water | Medium |
| S.53 | Status: waiting, water shortage / ΔT | Status, not fault | Low flow, pressure | — |
| S.76 | Status: pressure too low, blocking | Status, not fault | Low pressure | — |
| Any code not listed | Unconfirmed for this model | — | **** | — |
Detailed Guidance
What does F.22 mean on a Vaillant boiler?
F.22 — Dry fire / low water pressure. The pressure sensor reads below the minimum (around 0.5 bar on most models), or the control has detected no water in the primary. The boiler blocks and, on most ecoTEC models, restarts itself once pressure is restored above the threshold — so the customer often reports "it comes back on when I top it up".
Causes: system leak (radiator valve, tail, joint, automatic air vent), PRV discharging (wet discharge pipe outside — expansion vessel is the usual root), radiators bled without topping up, expansion vessel lost charge or failed, pressure sensor fault (reads low while the gauge reads normal — the two are separate on many Vaillants, which makes this easy to check).
Path: compare gauge and displayed pressure (d.-parameter or live pressure display) → repressurise to 1–1.5 bar cold via the filling loop → monitor a heating cycle (0.3–0.5 bar rise normal; more = expansion vessel) → recurring loss: PRV and systematic leak check; see boiler loses pressure repeatedly and boiler pressure relief valve discharging. If the gauge is normal and the display reads low, the sensor or its wiring is at fault.
What does F.28 mean on a Vaillant boiler?
F.28 — Ignition failure. The boiler ran its start-up sequence (fan, ignition, gas valve) without establishing a flame within the permitted attempts and locked out. The commonest Vaillant winter callout. F.54 alongside it means the control specifically suspects gas pressure.
Causes, in rough order of frequency:
- No gas — pre-payment credit, meter valve, appliance isolation valve; check another appliance.
- Frozen or blocked condensate — ecoTEC combis back up through the siphon trap; a frozen external run, or a trap full of debris in summer, stops ignition. Thaw with warm water and fix the route; see condensate pipe frozen boiler lockout and condensate pipe installation.
- Ignition electrode — the ecoTEC's combined ignition/ionisation electrode is a service item: erosion, cracks, carbon, gap, lead.
- Low inlet pressure / gas valve — working pressure at the test point below ~17 mbar natural gas under load; no click from the valve.
- Flue — blocked terminal, displaced or failed seals, recirculation.
- Ignitor / PCB — no spark with electrode and lead proven.
Path: gas at other appliances → condensate → reset once and observe the sequence → no spark: electrode, lead, ignitor, PCB → spark but no flame: gas pressure, gas valve, flue.
What does F.29 mean on a Vaillant boiler?
F.29 — Flame loss during operation. The burner lit and ran, then the ionisation signal was lost. Different from F.28: the ignition chain works. Look at gas supply under load (pressure drop when other appliances run — pipe sizing, meter regulator; see gas pipe sizing), flue recirculation in wind (terminal position, seals), electrode signal quality (worn electrode gives a marginal ionisation current that drops out), gas valve modulation, and condensate partially backing up during a long run. A combustion check with a flue gas analyser (see flue gas analysis) is the right confirmation.
What does F.75 mean on a Vaillant boiler?
F.75 — No pressure change detected on pump start. Vaillant's control expects system pressure to rise by a small amount (roughly 0.1–0.2 bar) when the pump starts; if it does not, F.75. The logic is that if the pump is running and the sensor sees no change, either the pump is not moving water or the sensor cannot see it.
Causes: pressure sensor stuck or scaled (very common on 2005–2015 ecoTEC plus — the sensor sits in a pocket that silts up), pump failed or air-locked, pump running on too low a speed setting, system heavily sludged so the pump cannot create the pressure rise, air in the system, sensor wiring.
Path: check the sensor first — clean or replace (it is cheap), and clear the pocket → bleed the pump and check it spins → check pump speed setting (ecoTEC plus pumps have a speed selector; too low a setting on a large system gives F.75) → check for sludge (magnetic filter contents, ΔT, radiator cold spots) → pump. If a sensor has already been changed and F.75 returns, it is the pump or the system water quality — clean to BS 7593:2019 (see powerflush).
F.61 / F.62 / F.27 — gas valve and false flame
These are the codes to treat as gas safety matters:
- F.61 — the control cannot drive the gas valve correctly (short to earth in the valve harness, valve coil fault, PCB output fault).
- F.62 — the gas valve did not close within the expected time after the burner shut off — a slow or leaking valve, or electronics.
- F.27 — flame detected with the valve closed: electrode tracking, a valve passing gas, or PCB.
Do not reset and leave. Prove there is no gas passing at the valve outlet with the valve de-energised, check the harness, then replace the valve or PCB as the evidence directs.
F.20, F.23, F.24, F.76 — circulation and overheat
F.20 is the safety cut-out at around 97 °C flow; F.24 is a rate of temperature rise that implies no flow; F.23 is a flow–return ΔT larger than the control permits (low circulation, or flow and return NTCs in the wrong pockets after a repair); F.76 on some models is the heat exchanger's own thermal fuse/limiter tripping, which often means the aluminium exchanger has already been damaged. All point to pump, air, blockage, closed zones or sludge. Let the boiler cool, prove the pump, prove flow through the system, check bypass and TRVs, check the exchanger for restriction, and only then suspect sensors. See boiler kettling and system cleansing inhibitors.
F.32 — fan
Fan speed outside tolerance. Check the flue (blocked terminal, crushed flexible section, frost), fan plug and tacho lead, bearing noise (see boiler fan noise diagnosis), supply voltage to the fan, then fan or PCB. Combustion check after any flue or fan work.
Decision tree — F.28 ignition failure
F.28 (± F.54) displayed
|
Gas at other appliances?
|
+----+---------+
| |
No Yes
| |
Restore, Condensate frozen / siphon blocked?
reset |
+----+------+
| |
Yes No
| |
Thaw, reset, Reset once; watch sequence
fix route |
+-----+------------------+
| |
Fan runs, no spark Spark, no flame
| |
Electrode, lead, Working pressure at
ignitor, PCB test point under load;
gas valve click;
flue terminal/seals
Decision tree — F.75
F.75 displayed
|
Gauge vs displayed pressure agree?
|
+---+----------------+
| |
No Yes
| |
Pressure sensor: Pump spins when energised?
clean pocket, |
replace sensor +----+--------+
| |
No Yes
| |
Pump, supply, Pump speed setting;
PCB output air in pump; sludge
(filter, dT, cold spots)
-> clean to BS 7593,
then pump if persists
Frequently Asked Questions
How do I reset a Vaillant boiler?
Press the reset button — the flame-with-a-cross symbol on the fascia — once. The display clears and the boiler attempts a restart. F.22 clears itself when pressure is restored and does not need a reset on most models. If a code returns immediately the fault is active; the control also limits how many F.28/F.29 resets it will accept in a period. Never keep resetting F.20 (overheat), F.27, F.61 or F.62 (gas valve/false flame).
Is S.53 or S.76 a fault code?
No. S-codes are status codes shown during normal operation. S.53 means the boiler is waiting because of a water-shortage or ΔT condition (often low flow — it may precede F.22, F.23 or F.75); S.76 means pressure is too low and the boiler is blocking until it is topped up. They tell you what the boiler is doing, not that it has failed — but a boiler sitting on S.53 for long periods has a circulation or pressure problem worth looking at.
What is the difference between F.28 and F.29?
F.28 is failure to light: the boiler never established a flame during start-up. F.29 is flame loss: it lit, ran, and the flame went out. F.28 with no spark is the ignition chain (electrode, lead, ignitor, PCB); F.28 with a spark is gas supply or valve; F.29 is gas pressure under load, flue recirculation, a marginal electrode or a valve modulating badly. The distinction halves the diagnosis time.
Why does F.75 keep coming back after the pressure sensor was replaced?
Because the sensor was only ever half the story. F.75 means the control saw no pressure rise when the pump started. If a new sensor sees none either, the pump is not creating one — it is air-locked, on too low a speed, failing, or fighting a sludged system. Check pump speed and bleed it, look at the magnetic filter and radiator cold spots for sludge, clean the system to BS 7593:2019 if needed, and replace the pump if it still fails.
How much does a typical Vaillant repair cost?
Indicative, excluding labour: pressure sensor £30–£70; NTC £15–£35; electrode £30–£60; fan £150–£300; gas valve £140–£260; PCB £220–£400; pump £130–£250; diverter valve £120–£220; plate heat exchanger £150–£300; main heat exchanger £400–£800. Labour typically £80–£150 for diagnosis plus repair time. **** Vaillant guarantees run 5–10+ years on many ecoTEC models when installed by a Vaillant Advance installer and registered — check before quoting.
Regulations & Standards
Gas Safety (Installation and Use) Regulations 1998 — all work on gas appliances, including fault diagnosis behind the case, must be carried out by a Gas Safe registered engineer
Building Regulations Approved Document J (England) — combustion appliances; flue and condensate requirements
Building Regulations Approved Document L (England) and Boiler Plus (2018) — controls and efficiency on replacement
BS 6798:2014 — installation and maintenance of gas-fired boilers up to 70 kW net input
BS 5440-1:2008 and BS 5440-2:2023 — flueing and ventilation of gas appliances
BS 7593:2019 — treatment of water in domestic hot water central heating systems (sludge-related F.75/F.20/F.24 faults)
BS 7671:2018+A4:2026 — electrical work associated with the boiler supply and PCB replacement
BS 7967:2015 — carbon monoxide in dwellings and combustion performance of gas appliances; flue gas analysis after F.29 or any gas-side repair
Benchmark Commissioning Checklist — should be completed and reviewed on any callout; required to maintain the Vaillant guarantee
Vaillant UK — fault codes and troubleshooting — manufacturer homeowner guidance and links to model manuals
Vaillant UK — installer technical documents — installation and servicing manuals with full F-code tables
Gas Safe Register — statutory register for gas engineers in Great Britain
HSE — Gas Safety — statutory guidance on gas appliance safety
HomeServe — Vaillant boiler fault codes — independent code summary
Heatable — Vaillant boiler error codes — independent code list
boiler error codes glow worm — Glow-worm (Vaillant Group) codes using the same F-numbering
boiler error codes ideal — Ideal L/F codes
boiler error codes worcester bosch — Worcester Bosch display and cause codes
boiler error codes baxi — Baxi E-codes
heat pump error codes vaillant arotherm — Vaillant aroTHERM heat pump codes
condensate pipe frozen boiler lockout — the winter F.28 cause
boiler loses pressure repeatedly — recurring F.22
boiler pressure relief valve discharging — PRV and expansion vessel
boiler fan noise diagnosis — fan faults before F.32
boiler kettling — heat exchanger scale and overheat codes
flue gas analysis — combustion checks after repair