Summary

Worcester Bosch is the UK's biggest-selling boiler brand and has been for most of two decades, so its Greenstar codes are the ones every heating engineer meets most often. The brand uses the Bosch Group "Heatronic" control platform, which has evolved through several generations: Heatronic 3 on the 2nd-generation Greenstar i, Si and CDi (the familiar "EA", "E9", "A1" two-character display with a 3-digit sub-code visible in service mode), the text-display Greenstar CDi Classic and Highflow, and the Bosch "Bosch Control" platform on the Greenstar 2000, 4000 and 8000 Life/Style ranges from 2019, which show the same two-character family on the main display with the 3-digit cause code alongside. The two-character code tells you the category; the three-digit code tells you the specific trigger, and it is the three-digit code that should drive the diagnosis.

Two things catch engineers out. First, some two-character codes are blocking (the boiler waits and retries automatically — e.g. A1 or H7 for low pressure, C1 for fan speed during operation) while others are locking (manual reset required — EA, E9, F7). A customer who reports "it just comes back on by itself" is describing a blocking code, which narrows the field. Second, the same two characters can carry different cause codes on different generations — for example low pressure is reported as A1 281 on some 2nd-gen models but D5 or H7 on later ones — so a code quoted over the phone from a 2009 CDi does not necessarily mean what it would on a 2022 Greenstar 4000.

This guide tabulates the common display and cause codes, states which generation each applies to, gives the diagnostic path for the five fault groups that dominate callouts, and gives decision trees for EA (no flame) and E9 (overheat). Codes marked **** are documented on third-party sources but should be checked against the model's installation and servicing manual.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Display Cause code Generation Meaning Type Most likely causes Urgency
EA 227 All No flame after ignition attempts Locking No gas, frozen condensate, electrode, gas valve, flue High
EA 229 2nd-gen Flame lost during operation Locking Gas pressure under load, flue recirculation, electrode High
E9 219 All Safety temperature limiter tripped Locking Pump, blockage, air, closed valves High — do not keep resetting
E9 224 All Heat exchanger limiter / thermostat Locking As 219; heat exchanger scaled High
E5 218 2nd-gen Flow temperature too high Blocking Circulation, pump speed Medium–High
E2 222 2nd-gen Flow NTC fault Locking Thermistor, wiring Medium
EF 220 2nd-gen Heat exchanger temperature too low Blocking NTC, control Medium
A1 281 2nd-gen i/Si/CDi Pump running dry / no pressure rise Blocking Low pressure, pump, air Medium
D5 — Later models Low system pressure Blocking Leak, PRV, bleed Medium
H7 — 2000/4000/8000 System pressure below ~0.5 bar Blocking Leak, PRV, bleed Medium
CE 207 Some models Low water pressure (sensor) Blocking Low pressure, sensor Medium
C6 215 / 216 All Fan speed too high / too low Locking Blocked flue, fan, tacho wiring High
C1 264 2nd-gen Fan speed dropped during run Blocking Fan, wiring Medium–High
C7 214 2nd-gen Fan not running Locking Fan, supply, PCB High
D1 240 / 241 2nd-gen Return NTC fault Locking Thermistor, wiring Medium
D4 341 2nd-gen Temperature rise too fast Blocking Flow restriction, pump Medium–High
F7 328 All Flame detected with gas valve closed Locking Electrode tracking, gas valve leak, PCB High — gas safety
FA 306 2nd-gen Flame after gas valve shut off Locking Gas valve, PCB High — gas safety
B7 257 2nd-gen Internal / PCB fault Locking PCB Medium–High
9U 233 2nd-gen Code plug / PCB Locking Code plug, PCB Medium
Any code not listed — — Unconfirmed for this model — **** —

Detailed Guidance

Identify the generation before you read the code

Open the fascia and read the data badge (on the inside of the front panel or on the underside of the case). Broadly:

What does EA mean on a Worcester Bosch boiler?

EA 227 — No flame detected. The boiler ran its ignition sequence (fan pre-purge, spark, gas valve open) up to four times without the ionisation electrode sensing a flame, waited ~30 seconds between attempts, and locked out. The most common Worcester callout, overwhelmingly in winter.

Causes, in rough order of frequency:

  1. No gas — pre-payment credit, meter valve, isolation valve; check another gas appliance.
  2. Frozen or blocked condensate — Greenstar combis have an internal siphon trap; a frozen external run or a blocked trap stops the boiler firing. Thaw with warm water; re-route, insulate or fit a condensate pump; see condensate pipe frozen boiler lockout.
  3. Ignition / ionisation electrode — the combined electrode is a service item; look for erosion, cracked porcelain, carbon, wrong gap, and a damaged lead.
  4. Gas valve — no click, or opens but no gas: check inlet working pressure (~20 mbar natural gas at the meter, not below ~17 mbar at the appliance under load).
  5. Flue — blocked or displaced terminal, recirculation, failed seals; a Greenstar flue with a damaged seal causes intermittent EA that is maddening to trace.
  6. Spark generator / Heatronic PCB — no spark with electrode and lead proven.

EA 229 (flame lost during operation) points more at gas pressure under load, flue recirculation in wind, or electrode signal quality than at the ignition chain. Check working pressure with other appliances running and do a combustion check (see flue gas analysis).

What does E9 mean on a Worcester Bosch boiler?

E9 219 / 224 — Overheat / safety temperature limiter. The safety thermostat on the heat exchanger (or the flow NTC acting as limiter) has seen a temperature above its limit and locked the boiler out. It is a circulation fault until proven otherwise, and the single most damaging Worcester code to keep resetting.

Causes: pump failed, seized or on the wrong speed; heat exchanger blocked with sludge or scale (very common on 2nd-gen aluminium heat exchangers in hard-water or poorly inhibited systems); air in the primary; motorised zone valves closed with no bypass; diverter stuck midway; faulty limiter or NTC giving a false reading (less common).

Path: allow to cool → confirm the pump runs on demand and is not seized → check flow through the system (radiators warming, ΔT across the boiler not excessive) → check automatic bypass → check heat exchanger for restriction (flow and return temperatures, pressure drop) → resistance-check the limiter/NTC. Where sludge is confirmed, clean to BS 7593:2019 (see powerflush and system cleansing inhibitors). A 2nd-gen Greenstar that has had repeated E9s often has a heat exchanger that is now weeping — check the condensate for primary water.

What does A1 / D5 / H7 mean on a Worcester Bosch boiler?

A1 281 (2nd-gen) — Pump running dry / no pressure rise. The control saw the pump run without the expected pressure change — nearly always low system pressure, sometimes air in the pump or a pump that is not actually turning. D5 and H7 on later models are the sensor-based low-pressure codes (pressure below ~0.5 bar). These are blocking codes: repressurise to 1–1.5 bar cold and the boiler restarts itself.

Path: gauge reading → repressurise via the filling loop → monitor one heating cycle (0.3–0.5 bar rise normal; large rise = expansion vessel) → recurring loss = PRV discharging (look outside) or system leak; see boiler loses pressure repeatedly and boiler pressure relief valve discharging. If pressure is correct and A1 persists, suspect the pump (check it spins and is not air-locked) or the pressure sensor.

What does C6 mean on a Worcester Bosch boiler?

C6 215 (fan speed too high) / 216 (fan speed too low). The Heatronic board compares fan tacho speed to target. Too high usually means the fan is spinning freely against no resistance — blocked flue or disconnected air pressure path — or the tacho is reading wrongly; too low means a failing fan, a wiring/connector fault or a flue so blocked the fan cannot reach speed. C1 264 is the fan speed falling away during a run; C7 214 is the fan not running at all.

Path: check flue terminal and route (bird guard, debris, crushed flexible section, frost on the terminal) → check fan plug and tacho lead → listen for bearing noise (see boiler fan noise diagnosis) → check fan supply voltage → fan or PCB. Always do a combustion check after a flue or fan repair (see flue clearances and part j).

F7 / FA — false flame

Flame signal present when the gas valve should be closed. Causes: electrode or lead tracking to earth from moisture or carbon, a gas valve passing (dangerous), or a PCB fault. This is a gas safety matter: with the valve de-energised, prove there is no gas passing before anything else. Never clear it with a reset and leave.

Sensor and PCB codes — E2, D1, EF, B7, 9U

Decision tree — EA no flame

EA 227 displayed
      |
Gas at other appliances?
      |
  +---+----------+
  |              |
 No             Yes
  |              |
Restore,      Condensate frozen / siphon trap blocked?
reset              |
              +----+------+
              |           |
             Yes          No
              |           |
         Thaw, reset,   Reset once; watch sequence
         fix the run       |
                     +-----+-------------------+
                     |                         |
               Fan runs, no spark        Spark, no flame
                     |                         |
               Electrode, lead,          Working gas pressure
               spark generator/PCB       under load; gas valve
                                         click; flue terminal
                                         and seals

Decision tree — E9 overheat

E9 219 / 224 displayed -- allow boiler to cool
      |
Pump runs on demand?
      |
  +---+-----------+
  |               |
 No              Yes
  |               |
Pump, supply,   Flow through system?
PCB             (radiators warm, dT normal)
                  |
             +----+--------+
             |             |
            No            Yes
             |             |
      Air lock, closed   Limiter / NTC
      zone valves,       false reading
      blocked heat       -- resistance
      exchanger,         check, replace
      stuck diverter;
      clean to BS 7593

Frequently Asked Questions

How do I reset a Worcester Bosch Greenstar?

Hold the reset button (or turn the control knob to the reset position on 2nd-gen i/Si models) for three to five seconds until the display changes and the boiler attempts to restart. Blocking codes (A1, H7, C1) clear themselves once the cause is removed and do not need a reset. If a locking code returns immediately there is an active fault; do not keep resetting E9 (overheat) or F7/FA (false flame).

What is the difference between the two-character code and the three-digit code?

The two-character display code (EA, E9, C6) is the fault category shown on the main display. The three-digit cause code (227, 219, 215) is the specific trigger and is what the manual's fault table is written around. On 2nd-gen Greenstar i/Si/CDi you read it from the service menu; on Greenstar 2000/4000/8000 it is shown alongside the letter code. Diagnose from the cause code, not the category.

Why does my Worcester show EA only on cold mornings?

Almost always a condensate problem — the external run freezes overnight, backs up into the siphon trap and stops ignition; as the day warms it thaws and the boiler fires. Insulate and shorten the external run, increase it to 32 mm, fall it correctly, or terminate internally; see condensate pipe installation. Less often, a flue terminal that frosts up in still cold air causes the same pattern.

My Worcester Bosch keeps showing E9 and I keep resetting it — is that safe?

No. E9 means the heat exchanger has overheated, which means water is not circulating properly. Every reset repeats the thermal shock. On a 2nd-gen aluminium heat exchanger that leads to cracking and a leak; on any boiler it points to a blockage or pump fault that will not fix itself. Have a Gas Safe engineer diagnose the circulation fault before the boiler goes back into normal use.

How much does a typical Worcester Bosch repair cost?

Indicative, excluding labour: pressure sensor/switch £30–£70; NTC thermistor £15–£35; electrode £25–£50; fan £150–£280; gas valve £130–£250; Heatronic PCB £200–£380 (plus code plug if lost); diverter valve £120–£220; plate heat exchanger £150–£300; main heat exchanger £400–£700. Labour typically £80–£150 for diagnosis plus repair time. **** Worcester's extended guarantees (up to 10–12 years on many Greenstar models when installed and registered by an accredited installer) are worth checking before quoting — the repair may be free.

Regulations & Standards