Summary

Baxi is the third of the UK's big three boiler brands and, through BDR Thermea, also owns Main and Potterton, which is why a Potterton Promax or a Main Eco Compact shows the same E-codes as a Baxi Duo-tec or Baxi 800. The E-code scheme has been stable since the mid-2000s Duo-tec, which makes it a good scheme for phone triage, and Baxi publishes the common codes on its trade and homeowner websites with the engineer-level fix actions behind the Baxi Works installer login.

Three things trip engineers up. First, E118 and E119 are both low-pressure codes and the one you see depends on the model — Baxi's own list gives E118 for pressure below 0.5 bar, while many Duo-tec and Platinum units display E119 for the same condition; either way the remedy is the same. Second, E133 is a catch-all: Baxi describes it simply as a gas supply fault, but on site it covers everything from a pre-payment meter out of credit to a frozen condensate pipe to a failed electrode, and the sequence you observe on reset tells you which. Third, E168 is a "general internal fault" that is genuinely often the PCB — but on the earlier Duo-tecs a damaged wiring loom, a damp plug or a low mains voltage produce the same code, and a PCB has been fitted to a great many boilers that only needed a connector pushed home.

This guide tabulates the E-codes seen on domestic Baxi, Main and Potterton boilers in the UK, gives the diagnostic path for the five fault groups that dominate callouts, and gives decision trees for E133 and E119. Codes marked **** are documented on third-party sources but should be checked against the model's own manual before a part is ordered.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Code Meaning Reset type Most likely causes Urgency
E10 Outdoor sensor fault Auto Sensor, wiring (only if fitted) Low
E20 Flow NTC fault Manual Thermistor, plug, wiring Medium
E28 Flue NTC open/short circuit Manual Flue thermistor, wiring; sometimes blocked flue/condensate Medium–High
E40 Return NTC fault Manual Thermistor, plug, wiring Medium
E50 DHW NTC fault Manual Thermistor, wiring Medium
E78 Pressure sensor fault Manual Sensor, wiring Medium
E109 Air in primary / circulation (Duo-tec) Manual Air, pump, low flow Medium
E110 Safety thermostat / overheat Manual (hold 5 s) Pump jammed, air, blockage, closed valves High — do not keep resetting
E117 Pressure too high Auto when corrected Filling loop open, expansion vessel Medium
E118 Pressure below ~0.5 bar Auto on refill Leak, PRV, bleed, expansion vessel Medium
E119 Low pressure (model-dependent display) Auto on refill As E118 Medium
E125 Water circulation fault Manual Pump, air, blockage, closed valves High
E128 Flame loss during operation Manual Gas pressure under load, flue, electrode High
E129 Flame loss / low gas pressure Manual Inlet pressure, gas valve High
E130 Flue NTC over-temperature Manual Combustion, flue restriction, exchanger High
E133 Gas supply / ignition failure Manual No gas, frozen condensate, electrode, gas valve, flue High
E160 / E161 / E162 Fan fault / wiring / speed Manual Fan, tacho, blocked flue, PCB High
E168 General internal fault Manual PCB, wiring loom, damp plug, low mains voltage Medium–High
E193 Circulation / air (600/800) Manual Air, pump Medium
E270 Dry fire — no water in exchanger Manual No water, air, pump High
E321 DHW NTC (some models) Manual Thermistor Medium
E384 False flame Manual Electrode tracking, gas valve passing, PCB High — gas safety
Any code not listed Unconfirmed for this model — **** —

Detailed Guidance

Identify the model and generation

Read the data badge (inside the drop-down flap or on the underside). Current Baxi ranges: Baxi 400, 600, 800 (2017 on), Platinum / Platinum+, Duo-tec / Duo-tec 2, EcoBlue, Assure; Potterton Promax, Gold, Titanium, Assure; Main Eco Compact, Eco Elite. All use E-codes. Older ranges — Baxi Combi 80e/105e/Instant, Solo HE, Bermuda back boilers, Barcelona, Potterton Suprima/Performa/Kingfisher — use LED flash patterns or a different two-character scheme and are old enough (15–25 years) that repair-versus-replace should be the first conversation.

What does E133 mean on a Baxi boiler?

E133 — Gas supply fault / ignition failure. Baxi's own description is "gas supply fault"; in practice it is the boiler failing to establish or detect a flame within the ignition window, for any reason. The commonest Baxi/Potterton callout, overwhelmingly in winter.

Causes, in rough order of frequency:

  1. No gas — pre-payment credit, meter valve, appliance isolation valve. Check another appliance first.
  2. Frozen or blocked condensate — Baxi combis stop ignition when the siphon trap backs up. Thaw a frozen external run with warm water; clear a blocked trap; fix the route (32 mm, insulated, falls, short external run — see condensate pipe installation and condensate pipe frozen boiler lockout).
  3. Ignition electrode / detection electrode — Baxi uses separate ignition and detection electrodes on many models; a worn detection electrode gives E133 even though the burner visibly lights.
  4. Low inlet pressure / gas valve — working pressure at the test point below ~17 mbar natural gas under load; no click from the valve.
  5. Flue — blocked terminal, failed seals, recirculation.
  6. Spark generator / PCB — no spark with electrode and lead proven.

Path: gas at other appliances → condensate → reset and watch the sequence through the sight glass → no spark: ignition electrode, lead, spark generator, PCB → spark and flame visible but E133: detection electrode and lead → spark, no flame: gas pressure, gas valve, flue.

What does E118 / E119 mean on a Baxi boiler?

E118 / E119 — Low system water pressure. The pressure sensor reads below the minimum (around 0.5 bar). Which code is displayed depends on the model; the remedy is identical. The boiler restarts itself once pressure is restored.

Causes: system leak (radiator valve, tail, joint, automatic air vent), PRV discharging (wet discharge pipe — expansion vessel is the usual root), radiators bled without topping up, expansion vessel lost charge or failed, pressure sensor fault.

Path: gauge reading → repressurise to 1–1.5 bar cold via the filling loop → monitor one heating cycle (0.3–0.5 bar rise normal; more = expansion vessel) → recurring loss: check PRV discharge, then systematic leak check; see boiler loses pressure repeatedly and boiler pressure relief valve discharging. If the gauge is normal and the code persists, suspect the pressure sensor (E78 may accompany it).

What does E110 mean on a Baxi boiler?

E110 — Safety thermostat / overheat. Baxi lists two triggers: the maximum temperature was exceeded for the gradient (temperature rising faster than circulation can explain — probable pump jammed or air in the circuit), or the safety thermostat sensor tripped. Either way it is a circulation fault and the code most often damaged by repeated resets.

Causes: pump jammed, seized or not running (very common after a summer idle on older Duo-tecs); air in the primary; heat exchanger or system blocked with sludge/scale; motorised valves closed with no bypass; diverter stuck midway; faulty safety thermostat or NTC (less common).

Path: allow to cool → confirm the pump runs on demand (check the pump plug and that the rotor turns) → confirm flow through the system (radiators warming, ΔT across the boiler reasonable) → check bypass and TRVs → check exchanger for restriction → resistance-check the safety stat/NTC. Clean to BS 7593:2019 where sludge is found (see powerflush and system cleansing inhibitors).

What does E125 mean on a Baxi boiler?

E125 — Water circulation fault. The control saw no or insufficient primary circulation (typically a flow–return temperature relationship that implies the water is not moving). Causes overlap with E110 but E125 usually fires before the overheat does: pump not running or air-locked, air in the system, blockage, closed valves, very low pressure. Bleed the system (and the pump), prove the pump, check valves and bypass, then look for sludge. See also E109 and E193 which are the air/circulation variants on specific models.

What does E28 mean on a Baxi boiler?

E28 — Flue NTC open or short circuit. The flue gas thermistor circuit is faulty. Baxi's own definition is the sensor fault; on site it is also seen when a blocked flue or frozen condensate has driven flue conditions outside the sensor's plausible range. Check the sensor and its wiring first, then the flue and condensate route. E130 (flue over-temperature) is the related code that points at combustion or a restricted flue and needs a flue gas analysis (see flue gas analysis).

What does E168 mean on a Baxi boiler?

E168 — General internal fault. Genuinely often the PCB — but check the cheap things first: every plug on the board pushed fully home, the wiring loom for chafing or damage (older Duo-tecs suffer where the loom passes the fan), moisture on the board from a leak above, and the mains voltage at the boiler under load (a low or spiky supply, or a boiler sharing a circuit with heavy loads, produces E168). Only after those are proven, quote the board. On the 600/800 ranges a firmware or configuration issue after a board swap also shows E168.

E160–E162 — fan

Fan not running, wrong speed or wiring fault. Check flue (blocked terminal, crushed flexible section, frost), fan plug and tacho lead, bearing noise (see boiler fan noise diagnosis), supply to the fan, then fan or PCB. Combustion check after any flue or fan work.

E384 — false flame

Flame signal present with the gas valve closed. Electrode tracking from moisture or carbon, a gas valve passing (dangerous), or a PCB fault. Treat as a gas safety matter: prove no gas passing at the valve outlet with the valve de-energised. Never clear it with a reset and leave.

Decision tree — E133

E133 displayed
      |
Gas at other appliances?
      |
  +---+----------+
  |              |
 No             Yes
  |              |
Restore,      Condensate frozen / siphon trap blocked?
reset              |
              +----+------+
              |           |
             Yes          No
              |           |
         Thaw, clear,   Reset once; watch through sight glass
         fix route         |
                 +---------+-----------+----------------+
                 |                     |                |
           No spark            Spark + flame      Spark, no flame
                 |             seen, still E133         |
           Ignition               |              Working pressure
           electrode, lead,   Detection          under load; gas
           spark gen, PCB     electrode, lead    valve; flue

Decision tree — E118 / E119

E118 / E119 displayed
      |
Gauge reading?
      |
  +---+---------------------+
  |                         |
Below 0.5 bar          Normal (1-1.5 bar)
  |                         |
Repressurise to        Pressure sensor /
1-1.5 bar cold;        wiring (E78?)
code clears
  |
Monitor one heating cycle
  |
  +---+-----------------+
  |                     |
Holds              Drops again
  |                     |
Done              PRV discharging? -> expansion vessel
                  Not discharging -> systematic leak
                  check: valves, tails, AAV, plate
                  exchanger, under floors

Frequently Asked Questions

How do I reset a Baxi boiler?

On most current models press and hold the reset button (or turn the selector to the reset position and hold) for about five seconds until the display clears, then release. Low-pressure codes (E118/E119) clear themselves once the system is topped up and do not need a reset. If the code returns straight away the fault is active. Do not keep resetting E110 (overheat) or E384 (false flame).

Is E118 the same as E119?

Yes in effect — both mean primary water pressure has dropped below the minimum (around 0.5 bar). Which one your boiler displays depends on the model and software generation. Repressurise to 1–1.5 bar cold; if it recurs, water is leaving the system and the leak or PRV/expansion vessel needs finding.

My Potterton shows the same codes as this Baxi list — is that right?

Yes. Potterton and Main are Baxi Heating (BDR Thermea) brands and current models share the control platform and the E-code scheme. The model-specific table in the installation manual is still the authority, because the exact list differs between, say, a Promax and a Baxi 800.

Why does E133 only appear on frosty mornings?

Frozen condensate. The external condensate run freezes overnight, the siphon trap backs up and the boiler will not ignite; by mid-morning it thaws and the boiler runs normally. Insulate, shorten and upsize (32 mm) the external run, correct the fall, or terminate internally; see condensate pipe installation.

How much does a typical Baxi repair cost?

Indicative, excluding labour: pressure sensor/switch £25–£60; NTC £15–£35; electrode £25–£50; fan £120–£250; gas valve £120–£220; PCB £180–£350; pump £120–£220; diverter valve £90–£180; plate heat exchanger £120–£250. Labour typically £80–£150 for diagnosis plus repair time. **** Baxi guarantees run 5–10 years on many current models when installed by a Baxi Works installer and registered — check before quoting.

Regulations & Standards