Summary

Glow-worm has been a Vaillant Group brand since 2001, positioned as the value range beneath Vaillant's own ecoTEC. From the Ultracom and Flexicom generations onwards the boilers share Vaillant's control electronics, which is why an F.28 on a Glow-worm Energy means the same as an F.28 on a Vaillant ecoTEC — and why an engineer who knows one brand's codes is most of the way to knowing the other's. Glow-worm publishes fault-finding code tables for each range on its trade website, and those are the authority for the range in front of you.

The traps are generational. The CI Plus, HXi, SXi and CXi boilers of the mid-2000s used a shorter code set with F.1, F.4 and F.9 that do not map onto Vaillant's scheme (F.1 and F.4 are both ignition-related, F.9 is the water pressure sensor), and some of those models show codes without the decimal point. The Betacom and Flexicom ranges sit in between. A code quoted over the phone therefore needs the model name attached before you can act on it. And as with Vaillant, status codes (S.xx) shown during normal operation are not faults, though customers report them as such.

This guide tabulates the F-codes on current and recent Glow-worm boilers, flags where the older CI Plus/HXi generation differs, gives the diagnostic path for the six codes that dominate callouts, identifies the gas-safety codes that must never be cleared and left, and gives decision trees for F.28 and F.22. Codes marked **** should be checked against the range's own fault-finding table before a part is ordered.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Code Range Meaning Type Most likely causes Urgency
F.00 / F.01 Energy/Ultimate/Betacom/Flexicom Flow / return NTC open circuit Lockout Thermistor, plug, wiring Medium
F.10 / F.11 Same Flow / return NTC short circuit Lockout Thermistor, damp plug, wiring Medium
F.13 Combi models DHW NTC fault Lockout Thermistor, wiring Medium
F.20 All current Safety cut-out — overheat Lockout Pump, blockage, air, closed valves High — do not keep resetting
F.22 All current Dry fire / low water pressure Blocking (auto-restart) Leak, PRV, bleed, sensor, sensor/pump cable Medium
F.23 / F.24 All current ΔT too large / rise too fast Lockout Low or no circulation Medium–High
F.27 All current False flame Lockout Electrode tracking, gas valve passing, PCB High — gas safety
F.28 All current Ignition failure at start-up Lockout Low gas / no credit, blocked condensate, electrode, PCB High
F.29 All current Flame loss during operation Lockout Gas pressure under load, flue, electrode High
F.32 All current Fan fault Lockout Fan, tacho, blocked flue, PCB High
F.49 eBUS-controlled eBUS fault Lockout Controls wiring, eBUS device Medium
F.54 All current Gas pressure fault (with F.28/F.29) Lockout Inlet pressure, valve closed High
F.61 / F.62 All current Gas valve control / switch-off delay Lockout Valve wiring, valve, electronics High — gas safety
F.63 / F.64 / F.65 All current PCB / electronics faults Lockout PCB, NTC short, PCB overheating Medium–High
F.70 All current Invalid device code Lockout PCB/display not programmed after replacement Medium
F.71–F.74 Newer Pressure sensor / NTC plausibility Lockout Sensor stuck, wiring Medium
F.75 All current No pressure change on pump start Lockout Pump, pressure sensor, air, sludge Medium–High
F.76 Some Primary exchanger overheat protection Lockout Exchanger overheated, fuse High
F.77 Where fitted Condensate pump / flue damper Lockout Pump, damper, wiring Medium
F.83–F.85 Newer Temperature plausibility / sensor swap Lockout NTCs swapped/loose, low water Medium
F1 / F4 CI Plus / HXi / SXi / CXi Ignition fault Lockout Gas, electrode, PCB High
F9 CI Plus / HXi / SXi / CXi Water pressure sensor fault Lockout Sensor, low pressure, wiring Medium
S.53 / S.76 Current Status: water shortage wait / pressure too low Status Low flow / pressure —
Any code not listed — Unconfirmed for this range — **** —

Detailed Guidance

Identify the range before you read the code

The data badge is inside the drop-down panel or on the underside of the case. Broadly:

What does F.22 mean on a Glow-worm boiler?

F.22 — Dry fire / low water pressure. Glow-worm's Energy range table lists three causes: no or insufficient water in the product; a defective water pressure sensor; or a loose, unconnected or defective cable to the pump or the pressure sensor. In practice the first is the overwhelming majority — the system has lost pressure.

Causes: leak (radiator valve, tail, joint, automatic air vent), PRV discharging (wet discharge pipe — expansion vessel usually the root), radiators bled without topping up, expansion vessel lost charge or failed, pressure sensor fault or cable.

Path: compare gauge and displayed pressure → repressurise to 1–1.5 bar cold via the filling loop → monitor one heating cycle (0.3–0.5 bar rise normal) → recurring loss: PRV then systematic leak check (see boiler loses pressure repeatedly and boiler pressure relief valve discharging) → gauge normal but F.22 persists: sensor and its cable, then the pump cable Glow-worm specifically mentions.

What does F.28 mean on a Glow-worm boiler?

F.28 — Ignition failure. Glow-worm's own guidance lists: not enough gas reaching the boiler (low gas pressure or insufficient credit on a pre-payment meter); a blocked condensate pipe that has backed condensate into the combustion chamber; a faulty ignition electrode; a faulty PCB. That list is in the right order of frequency for winter.

Path:

  1. Gas — check another appliance; check meter credit; check isolation valves.
  2. Condensate — frozen external run or blocked siphon trap. Thaw with warm water, clear the trap, fix the route (32 mm, insulated, falls — see condensate pipe installation and condensate pipe frozen boiler lockout).
  3. Reset once and watch the sequence — fan runs, spark, gas valve click?
  4. No spark — electrode (erosion, cracks, carbon, gap), lead, ignitor/PCB.
  5. Spark, no flame — working pressure at the test point under load (~17 mbar minimum natural gas), gas valve click, flue terminal and seals.
  6. F.54 alongside — the control specifically suspects gas pressure: start at the meter.

What does F.29 mean on a Glow-worm boiler?

F.29 — Flame loss during operation. The burner lit and then the ionisation signal was lost. The ignition chain works, so look at gas supply under load (pressure drop when other appliances run — pipe sizing, meter regulator; see gas pipe sizing), flue recirculation in wind, electrode signal quality (a worn electrode gives a marginal signal), gas valve modulation and condensate partially backing up during a long run. Confirm with a flue gas analysis (see flue gas analysis).

What does F.75 mean on a Glow-worm boiler?

F.75 — No pressure change on pump start. The control expects a small rise in system pressure when the pump starts; none was seen. Causes: pressure sensor stuck or scaled (clean the pocket and replace the sensor first — it is cheap and the commonest cause), pump air-locked or on too low a speed, pump failing, severely sludged system. If a sensor has been changed and F.75 returns, bleed and speed-check the pump, look for sludge (filter contents, ΔT, radiator cold spots), clean to BS 7593:2019 (see powerflush) and then replace the pump.

F.20, F.23, F.24, F.76 — overheat and circulation

F.20 is the safety cut-out at around 97 °C; F.24 is a temperature rise rate that implies no flow; F.23 is a flow–return ΔT larger than permitted (low circulation, or NTCs in the wrong pockets after a repair); F.76 on some models is the exchanger's own thermal limiter, which often means damage has already occurred. All point at pump, air, blockage, closed zones or sludge. Cool, prove the pump, prove flow, check bypass and TRVs, check the exchanger, then sensors. See boiler kettling and system cleansing inhibitors.

F.27, F.61, F.62 — gas safety codes

Flame with the valve closed (F.27), the valve not driving correctly (F.61), or the valve slow to close (F.62). Do not reset and leave. With the valve de-energised, prove there is no gas passing at the outlet; check the harness for shorts; replace the valve or PCB as the evidence directs.

F.32 — fan

Fan speed outside tolerance. Flue first (blocked terminal, crushed flexible section, frost), then fan plug and tacho lead, bearing noise (see boiler fan noise diagnosis), supply voltage, then fan or PCB. Combustion check after any flue or fan work.

F.70 after a repair

A replacement PCB or display that has not been programmed with the correct device code for the model shows F.70. It is a configuration step in the diagnostic menu, not a faulty part.

Older CI Plus / HXi / SXi / CXi codes

Glow-worm's table for this generation lists F1 and F4 as ignition faults and F9 as a water pressure sensor fault, and refers the engineer to its technical department for detail. Treat F1/F4 as you would F.28 (gas, condensate, electrode, PCB) and F9 as F.22 with a sensor bias. These boilers are now 15–20 years old; sludge, heat exchanger and PCB failures dominate, and parts availability should be checked before quoting a repair against replacement.

Decision tree — F.28

F.28 (± F.54) displayed
        |
Gas at other appliances? Meter credit?
        |
   +----+---------+
   |              |
  No             Yes
   |              |
Restore,      Condensate pipe frozen / trap blocked?
reset         (Glow-worm lists this explicitly)
                   |
              +----+------+
              |           |
             Yes          No
              |           |
         Thaw, clear,   Reset once; watch sequence
         fix route         |
                     +-----+------------------+
                     |                        |
               Fan runs, no spark       Spark, no flame
                     |                        |
               Electrode, lead,         Working pressure
               ignitor/PCB              under load; gas
                                        valve; flue

Decision tree — F.22

F.22 displayed
      |
Gauge vs displayed pressure?
      |
  +---+--------------------+
  |                        |
Both low              Gauge normal, display low
  |                        |
Repressurise to       Pressure sensor, sensor
1-1.5 bar cold;       cable, pump cable
auto-restart          (per Glow-worm table)
  |
Monitor one heating cycle
  |
  +---+---------------+
  |                   |
Holds            Drops again
  |                   |
Done             PRV discharging? -> expansion vessel
                 Not discharging -> systematic leak
                 check: valves, tails, AAV, plate
                 exchanger, under floors

Frequently Asked Questions

Are Glow-worm fault codes the same as Vaillant's?

Mostly, on current ranges. Glow-worm is a Vaillant Group brand and the Energy, Ultimate3, Easicom3, Compact, Betacom4, Flexicom and Ultracom ranges use Vaillant-derived controls, so F.22, F.28, F.29, F.75, F.20, F.27, F.61/F.62 and the NTC codes carry the same meanings. The older CI Plus/HXi/SXi/CXi generation used a different, shorter set (F1, F4, F9). Always use Glow-worm's own table for the range in front of you.

How do I reset a Glow-worm boiler?

Press the reset button — the flame-with-a-cross symbol — once. F.22 clears itself when pressure is restored on most models. If the code returns immediately the fault is active, and the control limits repeated F.28/F.29 resets. Never keep resetting F.20 (overheat), F.27, F.61 or F.62 (gas valve/false flame).

Why does my Glow-worm show F.28 only in cold weather?

Frozen condensate — Glow-worm lists a blocked condensate pipe as an explicit F.28 cause. The external run freezes overnight, condensate backs up into the combustion chamber or trap, and the boiler will not ignite until it thaws. Insulate, shorten and upsize (32 mm) the external run, correct the fall, or terminate internally.

The display shows S.53 or S.76 — is the boiler broken?

No. S-codes are status indications. S.53 means the boiler is pausing because of a water-shortage or temperature-difference condition; S.76 means pressure is too low and it is waiting to be topped up. A boiler that sits on S.53 for long periods has a circulation or pressure issue worth investigating, and it may progress to F.22, F.23 or F.75.

How much does a typical Glow-worm repair cost?

Indicative, excluding labour: pressure sensor £30–£60; NTC £15–£30; electrode £25–£50; fan £130–£260; gas valve £130–£240; PCB £180–£350; pump £120–£230; diverter valve £100–£200; plate heat exchanger £130–£260. Labour typically £80–£150 for diagnosis plus repair time. **** Glow-worm guarantees run up to 7–10 years on some Energy and Ultimate3 models when installed by a Club Energy installer and registered — check before quoting.