Summary
The four EICR codes are the single most argued-over part of domestic electrical inspection. A landlord sees a C2 and thinks the house is about to burn down; a tenant sees a C3 and refuses to move in; an agent sees FI and does not know whether the report has passed or failed. Electricians disagree too, which is why two inspectors can look at the same 1980s consumer unit and one writes C2 while the other writes C3. The codes themselves are short and clear. The difficulty is applying them consistently, and explaining to a customer what each one obliges them to do.
This article is for the electrician writing the report and for the tradesperson who has to price the remedial work that follows. It sets out the definition of each code, the common domestic observations that attract each one with the industry consensus on which code applies, how the codes drive the overall satisfactory or unsatisfactory assessment under the current Appendix 6 form, and what the codes mean legally for landlords under the 2020 Regulations. It does not cover how to carry out the inspection itself; see electrical installation condition report for extent, sampling and testing, and eicr pricing guide for what to charge.
One point worth stating up front: an EICR is a judgement against the current edition of BS 7671, but a departure from the current edition is not automatically a defect. An installation wired to the 15th or 16th Edition that remains in good condition and is not dangerous is coded C3 at most. The question an inspector asks of every observation is not "does this comply with the 18th Edition?" but "is this dangerous, potentially dangerous, or merely not what we would do today?"
Key Facts
- Four codes only — C1, C2, C3 and FI. There is no C4, no "pass with advisories" and no "minor". Anything else on a report is a contractor's own invention
- C1 — Danger present — risk of injury exists now; the inspector should make safe immediately (with the client's permission) and the client must act straight away
- C2 — Potentially dangerous — not an immediate danger but likely to become one through a single further fault or foreseeable event; urgent remedial action required
- C3 — Improvement recommended — a departure from the current edition of BS 7671 that does not give rise to danger; not a reason to fail the report
- FI — Further investigation required without delay — the inspector could not establish, within the agreed extent and limitations, whether a danger exists. FI is not a "don't know" filler; it must be followed up
- Overall assessment — unsatisfactory if any C1, C2 or FI is recorded; satisfactory if the only observations are C3 (or none)
- Amendment 4 form — the Appendix 6 EICR model form in BS 7671:2018+A4:2026 puts C1/C2 observations and C3/FI observations in two separate tables in Section K, so the overall assessment is visibly driven by C1 and C2 (see bs 7671 amendment 4 2026 changes explained)
- Private rented sector (England) — the 2020 Regulations require an EICR at least every 5 years; C1, C2 and FI must be remedied within 28 days (or sooner if the report says so) with written confirmation; penalties up to £30,000 per breach
- Industry guidance — Electrical Safety First Best Practice Guide 4 (BPG4) is the reference most electricians use to code consistently; NICEIC, NAPIT and the IET's Guidance Note 3 give the same classifications with minor differences in examples
- Limitations are not codes — "LIM" (agreed limitation) and "N/V" (not verified) record what was not inspected; they are not observations and do not change the outcome, but a report with excessive limitations is a poor report
- Age is not a code — "installation is old" or "wiring colours are pre-2004" is not an observation in its own right. Old colours without a warning label at the consumer unit is a C3
- Make safe and leave — where a C1 exists and the client refuses immediate rectification, the inspector should isolate the circuit if possible, record the refusal and issue a Danger Notification (Electrical Safety First has a model form)
- One observation, one code — each defect gets its own line and its own code; do not bundle a C2 and a C3 into one observation, because the remedial contractor and the landlord need to see which items are mandatory
Quick Reference Table
Quoting an electrical job? Describe the work and squote handles the pricing.
Try squote free →| Code | Wording on the form | Meaning in practice | Effect on overall assessment | Landlord duty (England PRS) |
|---|---|---|---|---|
| C1 | Danger present. Risk of injury. Immediate remedial action required | Someone could be injured now | Unsatisfactory | Remedy within 28 days (in reality: immediately) |
| C2 | Potentially dangerous. Urgent remedial action required | One further fault or event away from danger | Unsatisfactory | Remedy within 28 days |
| C3 | Improvement recommended | Not to current standard, but not dangerous | Satisfactory | None (good practice only) |
| FI | Further investigation required without delay | Inspector could not determine whether danger exists | Unsatisfactory | Investigate and remedy within 28 days |
Detailed Guidance
C1 — danger present
C1 is reserved for observations where a person or livestock could be injured, or a fire started, without anything else going wrong first. Typical domestic examples:
- Accessible live parts: a broken socket front or light switch with the terminals reachable, a missing blank in a consumer unit, a cable with conductor exposed in a loft
- Incorrect polarity where it results in a live part being exposed or a protective conductor being live
- Conductive parts that have become live because of a fault (for example, an exposed metal fitting reading 230 V to earth)
- A protective device that has been bypassed or bridged (a nail across a fuse carrier, a linked-out MCB)
- Evidence of thermal damage or arcing that is ongoing
A C1 obliges the inspector to act on the day. The accepted sequence is: tell the client, obtain permission to make safe, isolate or repair as far as the agreed scope allows, and if the client refuses, record the refusal and issue a written Danger Notification. Walking away from a C1 with nothing more than a line on a report is not acceptable practice and would not survive scrutiny if someone were later hurt.
C2 — potentially dangerous
C2 is the code that generates most remedial work and most disagreement. The test is whether the defect is likely to result in danger through a single further fault or a reasonably foreseeable event. BPG4 gives the clearest domestic examples, and the following are generally agreed:
- Absence of main protective bonding to incoming metallic gas or water pipework where it is extraneous-conductive (see earthing and bonding)
- No RCD protection for socket-outlets that are likely to supply mobile equipment outdoors, or for circuits in a bathroom or shower room
- No circuit protective conductor on a lighting circuit where Class I (metal) fittings or metal switches are installed; if every accessory on the circuit is Class II (all-insulated), the same missing CPC is usually C3 with a recommendation not to fit metal accessories
- Undersized or damaged earthing conductor, or a main earthing terminal that is loose or corroded
- Cables buried in walls at less than 50 mm outside the prescribed zones with no earthed metallic covering and no 30 mA RCD protection (see cable safe zones in walls)
- Socket-outlets or switches in bathroom zones where they are not permitted
- Rewirable fuses with incorrect fuse wire, or MCBs of the wrong rating for the cable they protect
- Signs of overheating at terminals, a melted accessory or discoloured consumer unit busbar connections where the cause is not ongoing (ongoing damage is C1)
- Inadequate IP rating of accessories exposed to water
- Immersion heater circuit without local isolation in combination with other defects is a judgement call; on its own this is usually C3
The consistent theme is that a C2 defect is dormant until something else happens: a flex gets cut on a lawnmower, a lighting fitting develops an earth fault, a nail goes through a cable. Remove the thing that would turn the fault into an injury, and you have remedied the C2.
C3 — improvement recommended
C3 records departures from the current BS 7671 that do not give rise to danger. The installation would not be designed this way today, but nobody is at risk. Common domestic C3 observations:
- No RCD protection for socket-outlets that are not reasonably expected to supply equipment outdoors (a 1990s ring final in a first-floor bedroom, for example)
- No RCD protection for lighting circuits (required for new work since the 18th Edition; a C3 on an existing installation)
- Plastic consumer unit, including one under a timber staircase. BPG4 codes a non-metallic consumer unit as C3 unless there is evidence of thermal damage or poor connections, in which case it is C2
- Old cable colours (pre-2004 red/black) without the warning notice at the consumer unit
- Missing or incomplete labelling at the consumer unit, no periodic inspection label, no RCD test notice
- Absence of surge protection (SPD) where a risk assessment would now call for one (see spd surge protection)
- Absence of AFDDs where the 18th Edition now recommends them
- Cables not adequately supported in a loft (clipped to joists but sagging), provided they are not damaged
- Supplementary bonding absent in a bathroom where it is not required because RCD protection and main bonding are in place
A report with only C3 items is satisfactory. Under the 2020 Regulations the landlord has no legal duty to act on C3 items, though a well-written report explains why acting on them is still worthwhile. Many of the C3 items above, particularly RCD protection, cost little to fix at the same time as C2 work and remove most of the residual risk in an older installation.
FI — further investigation required
FI is the code for the inspector's own uncertainty: a defect might exist but could not be confirmed within the agreed extent and limitations. Legitimate uses:
- An unidentified circuit or cable leaving the consumer unit that could not be traced to a load
- A protective conductor continuity reading that is inconsistent and could not be explained on the day
- A borderline insulation resistance result (above the 1 MΩ minimum but well below what the circuit's age and condition would suggest) where the cause could not be established
- An earth fault loop impedance reading that varies between tests
- Evidence of a previous fault (a scorch mark) whose cause could not be found
FI is not a way of avoiding a decision. If the inspector can see the defect and knows what it is, it gets a C1, C2 or C3. FI makes the report unsatisfactory and, in the private rented sector, starts the 28-day clock, so it has real consequences. The inspector should say in the observation exactly what investigation is needed, so the follow-up electrician does not have to re-inspect the whole installation to find it.
How the overall assessment is decided
The logic has always been simple: any C1, C2 or FI gives an unsatisfactory assessment; C3 observations alone give a satisfactory assessment. What changed in Amendment 4 is the layout of the form. On the old single-table Section K, a C3 sat in the same list as C1 and C2 and was routinely misread as a failure item by landlords and letting agents. The A4 form separates the observations into a C1/C2 table and a C3/FI table so the outcome is visually tied to the first table. FI remains an unsatisfactory outcome and must be followed up; placing it alongside C3 on the form reflects that it is not a confirmed defect, not that it can be ignored.
When writing up, state the overall assessment on the report, in the covering email and in the quote for remedial work. Then list the C1/C2/FI items as mandatory, and the C3 items as recommended, with separate prices. This is what the landlord's letting agent needs to see to demonstrate compliance, and it avoids the common dispute where a customer is asked to pay for a C3 item they believed was legally required.
Coding consistency — using BPG4
Electrical Safety First's Best Practice Guide 4 is a free document, written with the IET, NICEIC, NAPIT, ECA and others, that lists dozens of common domestic observations and the code each should attract. It is not a British Standard, but it is the closest thing the trade has to an agreed interpretation, and competent person scheme assessors use it when auditing reports. Two rules of thumb drawn from it:
Is there a risk of injury NOW?
├── Yes ────────────────────────────────→ C1 (make safe today)
└── No
│
Would ONE further fault or foreseeable event make it dangerous?
├── Yes ──────────────────────────→ C2 (urgent remedial action)
└── No
│
Can you confirm whether a danger exists?
├── No, not within the agreed extent ──→ FI (investigate without delay)
└── Yes, and it is simply not to current standard → C3 (improvement recommended)
If a report is challenged, the question an assessor asks is whether the code can be justified against this logic and against BPG4. "I always code plastic consumer units C2" is not a justification. "There is thermal damage at the main switch terminals of a non-metallic consumer unit, photograph attached" is.
Pricing the remedial work
For the tradesperson quoting after an unsatisfactory report, the usual pattern is a small number of C2 items and a longer list of C3. Typical remedial prices in England and Wales (labour and materials, excluding VAT) are shown below; adjust for region and access.
| Remedial item | Typical code | Typical price |
|---|---|---|
| Main protective bonding to gas and water (10 mm² green/yellow, two clamps) | C2 | £120–£250 |
| Replace damaged socket or switch front | C1 or C2 | £40–£80 each |
| Add 30 mA RCD protection by replacing MCBs with RCBOs (per circuit) | C2 or C3 | £70–£120 per way |
| Consumer unit replacement (metal, RCBOs, SPD, 8–12 ways) | C3 (C2 if damaged) | £550–£1,100 |
| Add CPC to a lighting circuit (re-run cable, one floor) | C2 | £250–£600 |
| Re-terminate overheated connection and replace accessory | C2 | £60–£150 |
| Install warning labels, RCD test notice, circuit chart | C3 | £20–£50 |
| Trace and identify unknown circuit (FI follow-up, per hour) | FI | £45–£75/hour |
Prices in this table are indicative 2026 figures and should be checked against local rates. A follow-up visit to confirm remedial work and issue written confirmation is itself chargeable and should be in the quote; landlords need that confirmation in writing within the 28-day window.
Frequently Asked Questions
Does a C2 mean the property cannot be let?
Not in itself. The 2020 Regulations do not prohibit letting; they require the landlord to obtain a satisfactory report and, where the report is unsatisfactory, to complete the remedial work within 28 days and obtain written confirmation. A property can be occupied during that window. A C1, however, means danger is present now, and the electrician should have made it safe on the day. A landlord who leaves a known C1 in an occupied property is exposed well beyond the Regulations, including under the Landlord and Tenant Act 1985 repairing obligations and the Homes (Fitness for Human Habitation) Act 2018.
Why did one electrician code my plastic consumer unit C2 and another C3?
Because the first was wrong, unless there was evidence of damage. BPG4 and the main scheme providers agree that a non-metallic consumer unit, including one under a wooden staircase or on the sole escape route, is a C3 on an existing installation. It becomes C2 where there is thermal damage, poor connections or missing blanks that would let a fault escape the enclosure. Inconsistent coding of consumer units is the most common EICR complaint scheme providers receive.
Is FI a pass or a fail?
A fail, in the sense that the overall assessment is unsatisfactory and, in the private rented sector, the 28-day duty applies. The investigation may conclude there is no defect, in which case the follow-up electrician issues written confirmation and the installation is then treated as satisfactory. Do not use FI as a soft option to avoid committing to a C2; it has the same legal effect and costs the landlord a second visit.
Does every departure from the 18th Edition need a code?
No. The report records observations that are dangerous, potentially dangerous or that the inspector recommends improving. An installation wired to an earlier edition is not required to comply with the current one. Items such as the absence of AFDDs or SPDs on an older installation are C3 at most, and some inspectors legitimately choose not to list every such item, instead noting in the general comments that the installation pre-dates the current edition. What must never be omitted is a C1, C2 or FI.
Can a tenant or agent demand that C3 items are fixed?
They can ask, but there is no legal duty on the landlord under the 2020 Regulations to act on C3 observations. A satisfactory report with C3 items is a satisfactory report. Agents who insist "everything on the report must be done" are misreading the form, which is exactly the confusion the two-table layout in Amendment 4 was introduced to reduce.
Regulations & Standards
BS 7671:2018+A4:2026 (IET Wiring Regulations, 18th Edition, Amendment 4) — Chapter 65 (periodic inspection and testing) and Appendix 6 (model forms, including the EICR and the classification codes); A4 published 15 April 2026 with the A2:2022/A3:2024 text withdrawn 15 October 2026
IET Guidance Note 3: Inspection & Testing — the IET's detailed guidance on periodic inspection, sampling and classification
Electrical Safety First Best Practice Guide 4 — "Electrical installation condition reporting: classification codes for domestic and similar electrical installations"; the trade's consensus document on coding
Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 (SI 2020/312) — five-yearly EICR, 28-day remedial duty for C1/C2/FI, copies to tenants and local authority, penalties up to £30,000
Electricity at Work Regulations 1989 — the duty to maintain electrical systems so as to prevent danger, which periodic inspection discharges in workplaces and HMO common parts
Building Regulations 2010, Approved Document P (England) — notifiable electrical work; much C2 remedial work (consumer unit replacement, new circuits) is notifiable (see part p notifiable work)
Landlord and Tenant Act 1985, section 11 and Homes (Fitness for Human Habitation) Act 2018 — the landlord's general repairing and fitness obligations that sit behind the 2020 Regulations
BS EN 61557 series — the performance requirements for the test instruments used to obtain the readings behind FI and C2 observations
Electrical Safety First — Best Practice Guide 4 — classification codes for domestic EICRs
GOV.UK — Guide for landlords: electrical safety standards in the private rented sector — the official guidance on the 2020 Regulations
legislation.gov.uk — Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 — the statutory instrument
IET — BS 7671 and the Wiring Regulations — the IET's page for the current edition and amendments
NICEIC — EICR guidance — scheme provider guidance for registered contractors
HSE — Electricity at Work Regulations 1989 guidance (HSR25) — the statutory duty to maintain
electrical installation condition report — how an EICR is carried out: extent, sampling, tests and limitations
electrical safety standards private rented sector — the landlord's legal duties, timescales and penalties in full
bs 7671 amendment 4 2026 changes explained — the Amendment 4 changes, including the two-table Appendix 6 EICR form
eicr pricing guide — what to charge for the inspection and the follow-up
earthing and bonding — main protective bonding, the most common C2
cable safe zones in walls — concealed cables and when their absence of protection is C2 or C3
consumer unit upgrade — replacing a consumer unit after an unsatisfactory report
landlord certificates — the full set of landlord certificates alongside the EICR