Summary

The safe zones are one of the most-searched and most-misunderstood parts of the Wiring Regulations. Electricians know them as the lines they are allowed to chase cables along; kitchen fitters, plumbers and carpenters know them, or should, as the lines where they must not drill. The two uses are the same rule from opposite sides. The regulation exists because a cable buried in plaster is invisible to the next person to fix a shelf, and the only defences are predictability (the zones), physical protection (steel) or a device that cuts the supply fast enough when a screw goes through the cable (the RCD).

The requirement has been stable in substance since the 17th Edition in 2008, when 30 mA RCD protection was added to the zone rule for domestic installations, and it was carried unchanged through the 18th Edition and its amendments to A4:2026. What changes between installations is the wall. A 100 mm block wall with 15 mm of plaster, a 1930s lath-and-plaster partition, a dot-and-dab plasterboard dry-lining and a metal-stud partition are all treated differently, and the most common real-world error is to run flat twin-and-earth down the dab line of a dry-lined wall outside any zone, without RCD protection, because "it's behind plasterboard, not in the wall".

This guide sets out the regulation as written, with the depth, zone and RCD logic laid out so that both the installer and the person fixing to the wall can apply it; the special cases of metal partitions, floors and ceilings; what an inspector codes on an EICR when the rule is not met; and how to price the remedial work. For cable fixing and support see cable clipping and fixings; for the RCD types that satisfy the requirement see rcd types explained.

Key Facts

Quick Reference Table

Quoting an electrical job? Describe the work and squote handles the pricing.

Try squote free →
Cable position Depth Wall type Mechanical protection? In a zone? RCD 30 mA required by 522.6? Compliant?
Chased into block, plastered ≥50 mm Solid No Not relevant No Yes
Chased into block, plastered <50 mm Solid No Yes Yes Yes, with RCD
Chased into block, plastered <50 mm Solid No No — No
In earthed steel conduit <50 mm Any Yes (ii) Not required No Yes
SWA or MICC <50 mm Any Yes (i) Not required No Yes
In PVC oval conduit, in zone <50 mm Solid No Yes Yes Yes, with RCD
Under steel capping, in zone <50 mm Solid No (capping is not sufficient) Yes Yes Yes, with RCD
Behind dot-and-dab plasterboard <50 mm Dry-lined masonry No Yes Yes Yes, with RCD
Behind dot-and-dab plasterboard <50 mm Dry-lined masonry No No — No
In timber stud partition Any Timber stud No Yes Yes Yes, with RCD
In metal stud partition Any Metal stud No Yes or no Yes (regardless of zone) Yes, with RCD
In metal stud partition, in earthed steel conduit Any Metal stud Yes (ii) Not required No Yes
Through joist, hole centred ≥50 mm from top and bottom Floor No — No Yes
Notched into top of joist under floorboards <50 mm Floor No — — No without protection (i)–(iii)

Detailed Guidance

What the regulation is trying to achieve

Section 522 of BS 7671 deals with external influences on wiring systems, and 522.6 with impact. The concealed-cable rules recognise that a cable in a wall will, sooner or later, be in the path of a drill or a nail driven by someone who cannot see it. The regulation offers three ways to make that event safe and one way to make it less likely:

The 50 mm figure reflects the length of a typical fixing; the vast majority of domestic screws and nails are shorter. A cable deeper than that is deemed out of reach.

The three zones, precisely

The zones are measured on the face of the wall:

  1. Within 150 mm of the top of the wall. A horizontal band 150 mm deep immediately below the ceiling, the full length of the wall. The equivalent band at the bottom of the wall is not a zone; the floor junction is where skirting is fixed, which is exactly why it was excluded.
  2. Within 150 mm of a corner. A vertical band 150 mm wide running full height along each side of every internal and external corner formed by two adjoining walls or partitions. A corner formed by a wall and a chimney breast counts; a window reveal does not create a zone along the window.
  3. In line with an accessory. From every socket, switch, fused connection unit, light point, consumer unit or other item fixed to the wall surface, a vertical zone the width of the accessory running up to the ceiling and down to the floor, and a horizontal zone the height of the accessory running to the edges of the wall in both directions. The zone belongs to the accessory; remove the accessory and the zone no longer exists, which matters when a socket is blanked off and plastered over.

The reverse-side rule: a zone created by an accessory extends to the other face of the wall only if the wall is 100 mm thick or less, because only then could someone on the other side reasonably infer where the cable is. A cable dropping to a socket on one side of a 215 mm brick wall is not in a zone when viewed from the other side, and must be protected accordingly, or kept 50 mm deep from that face.

Depth: how it is measured and why dry-lining is caught

Regulation 522.6.202 is the wall rule. Depth is measured from the finished surface of the wall or partition to the cable. In a chased solid wall with a 15 mm plaster coat, a chase 35 mm deep puts the cable at 50 mm and outside the rule; most domestic chases are 20–25 mm, so the cable sits at 35–40 mm and the zone and RCD rules apply.

In a dry-lined wall the plasterboard is the surface. A cable clipped to the masonry behind 12.5 mm board on 10 mm dabs is at about 25 mm and is concealed in the wall for the purposes of 522.6. It must be in a zone and RCD protected, or mechanically protected. Running cables anywhere convenient behind dry-lining is a widespread practice and a common C2 on EICRs when discovered during a socket replacement.

In a timber stud partition the cable passes through holes in the studs and lies in the void. It is concealed at less than 50 mm from at least one face unless the partition is unusually thick. The zone rule applies; running the cable through the centre of 100 mm studs puts it at roughly 56 mm from each face and outside the rule in theory, but where it drops in the void to an accessory it is in that accessory's zone anyway.

Metal partitions: RCD regardless of depth

Regulation 522.6.203 deals with partitions. Where the partition has metal studs, metal lath, metal channel or other metallic parts in its construction (fixings such as screws are excluded), a fixing driven into the wall can make the whole frame live if it penetrates a cable. The regulation therefore requires every concealed cable in such a partition, at any depth and whether or not in a zone, to have an earthed metallic covering, earthed steel conduit or trunking, adequate mechanical protection, or 30 mA RCD protection, or to be SELV or PELV. In practice, in a domestic metal-stud wall this means RCD protection on every circuit in the partition, and grommets or sleeving where cables pass through the studs to prevent chafing.

Floors and ceilings

Regulation 522.6.201 covers cables under floors and above ceilings. They must be run where they will not be damaged by contact with the floor or ceiling or their fixings. For cables through joists, the IET On-Site Guide gives the practical rule: holes drilled on the joist centreline, at least 50 mm from the top and bottom surface, within the permitted zone along the joist; notches in the top of a joist with the cable less than 50 mm from the floorboard face need the cable protected by (i) to (iii), in practice earthed steel conduit or a steel plate. Cables laid loose across the top of ceiling joists in a loft are not concealed in a wall and 522.6 does not apply, but they must be supported and protected from mechanical damage under Section 522.8 (see cable clipping and fixings and joist installation).

Design and installation practice

For other trades fixing to walls: assume there are cables within 150 mm of the ceiling, within 150 mm of every corner, and in vertical and horizontal lines from every socket, switch and light. Use a cable detector, drill shallow first, and keep fixings for kitchen units, shelving and curtain rails out of those bands where the design allows. The zones do not make drilling into them safe; they tell you where the danger is.

What the inspector codes

An EICR observation about concealed cables is one of the commonest items on a report for a 1980s to 2000s house. The accepted coding, consistent with Electrical Safety First Best Practice Guide 4:

The remedial work is almost always RCD protection at the consumer unit: RCBOs at £70–£120 per circuit fitted, or a consumer unit replacement at £550–£1,100 (see consumer unit upgrade). Re-routing or re-running a cable that is outside a zone is only necessary if RCD protection cannot be provided, which is rare.

Frequently Asked Questions

If the cable is in a safe zone, does it still need an RCD?

Yes, in a domestic installation. The zone on its own satisfies the location requirement, but a cable relying on the zone rather than on an earthed metallic covering, earthed steel conduit or adequate mechanical protection must also be protected by a 30 mA RCD. The two requirements work together: the zone makes a strike less likely, the RCD makes a strike survivable.

Does steel capping count as mechanical protection?

No. Steel capping protects the cable from the plasterer's trowel and makes a future cable pull possible; it will not stop a screw or a masonry drill. A cable under capping is treated as an unprotected cable: it must be in a zone and RCD protected, or be deeper than 50 mm.

Are the zones different in Scotland or on commercial jobs?

BS 7671 applies across the UK, so the zones are the same, and since Amendment 3:2015 the RCD requirement attached to the zone rule applies to every installation. The old exemption for commercial and industrial installations under the supervision of skilled or instructed persons was removed; a concealed cable in a zone in an office or shop needs 30 mA RCD protection or one of the mechanical alternatives just as it does in a house.

Can I run a cable horizontally at socket height around a room?

Only in the horizontal zone of an accessory on that wall, which extends from the accessory to the edges of that wall at the accessory's height. On a wall with no accessory there is no horizontal zone at socket height, and a cable there must be 50 mm deep, mechanically protected, or re-routed via the ceiling band or a corner. Looping a ring final horizontally between sockets on the same wall is fine; carrying on across a wall with no socket is not.

What should a kitchen fitter do before drilling for wall units?

Assume the ceiling band, both corners and the vertical and horizontal lines from every socket, switch and the cooker switch contain cables, and that a cable also runs behind the worktop sockets to feed them. Use a cable detector, mark the lines, and position fixings between them. Where a fixing has to go into a zone, drill shallow, check, and use the shortest fixing that will do the job. If the circuit is not RCD protected, say so to the customer; it is a legitimate reason to add RCBOs before the kitchen goes in.