A wet floor around the toilet is one of the most frequent plumbing call-outs and one of the most often misdiagnosed, because the customer's first assumption is a cracked pan and the plumber's first assumption is the pan connector, and both are sometimes wrong. The water arrives on the floor from several routes that converge at the same place: a leak at the pan connector runs along the underside of the pan and drips off the lowest point at the front; a leak at the close-coupling washer runs down the back of the pan to the same place; condensation on a cold cistern drips off the bottom of the cistern onto the floor behind the pan; a weeping supply fitting drips onto the floor at the side. By the time anyone looks, it is all one puddle.

The diagnosis takes ten minutes with a torch, a mirror, a dry cloth and a bottle of food colouring, and it decides whether the job is a connector, a washer, an extractor fan or a new pan. The risk in guessing is not the £20 part; it is the floor. A slow pan-connector leak that goes on for a year rots a chipboard floor, lifts a vinyl, stains the ceiling below and, on a ground floor, soaks the screed under the tiles. See damp patch on ceiling diagnosis for what it looks like from underneath.

This guide gives the diagnosis sequence, the four leak points and how to tell them apart, the pan connector types and their failure modes, the repair steps for each, and when a pan is beyond saving. For fitting a replacement close-coupled suite see close coupled toilet fitting guide; for a cistern that leaks from the mechanism see leaking toilet cistern.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Symptom Most likely cause Confirm with Fix
Water appears only after a flush, at the back of the pan Pan connector seal Food colouring at the outlet Replace the connector
Water appears after a flush, running down the back of the pan from the cistern Close-coupling washer or bolts Colour under the cistern New washer and bolt kit
Spray or run from behind a low-level pan on flush Flush-pipe cone Watch the pipe-to-pan joint New cone
Constant slow puddle, clear water, no colour Supply nut, tap connector or fill-valve tail Dry and watch the fittings Re-make the joint; new connector
Puddle behind the pan on humid days, cistern beaded with water Condensation Dry cistern, watch after a refill Ventilation; insulated cistern liner
Weep at the foot when someone sits on the pan Cracked foot or outlet spigot Dry, load the pan, inspect with a mirror New pan
Smell as well as water; pan water level low Connector leaking and trap seal lost Water level in the pan Replace the connector
Water from the floor joint on a floor-outlet (S-trap) pan Floor flange seal or connector Lift the pan New S-trap connector or flange

Detailed Guidance

Diagnostic sequence

WATER AT THE BASE OF THE TOILET
│
├─ Dry everything. Wait 30 min. Water back without a flush?
│   ├─ Yes, clear water ───► SUPPLY or CONDENSATION
│   │       Feel the supply nut, tap connector, fill-valve tail
│   │           ├─ Wet ──► re-make or replace the fitting
│   │           └─ Dry ──► cistern sweating? ──► condensation: ventilation, liner
│   └─ No ───► flush-related leak, continue
│
├─ Add food colouring to the cistern. Flush. Torch and mirror.
│   ├─ Colour at the pan outlet / connector ───► PAN CONNECTOR
│   │       Kinked, offset, perished, wrong type?
│   ├─ Colour under the cistern / down the back of the pan ──► CLOSE-COUPLING WASHER / BOLTS
│   ├─ Colour spraying from the flush pipe joint ──► FLUSH CONE (low/high level)
│   └─ No colour but water after flush ──► check the overflow / internal overflow route
│
└─ No leak found at any joint, water only when the pan is loaded?
        └─ Load test, dry mirror check of foot and spigot ──► CRACKED PAN ──► replace

The pan connector

The pan connector is the joint most likely to fail and the one most likely to be blamed when it has not. It is a push-fit seal at both ends, so it only leaks when water is passing through it, which is why the floor is dry in the morning and wet after the first flush. The common failure causes, in order:

  1. Wrong connector for the geometry. A straight connector forced onto a pan outlet that is 20 mm offset from the pipe, or a flexible connector bent to meet a pipe that needed a 90° connector, seals badly and gets worse as the pan is used. Measure the offset and the angle and buy the connector that matches. A pan outlet 100 mm into a 110 mm pipe that is in line needs a straight connector; a floor outlet needs an S-trap or 90° connector; up to 40 mm out of line needs an offset connector
  2. Pan moved after installation. New flooring laid around the pan, tiles that lifted the pan 10 mm, or a pan screwed down after the connector was pushed on; the lip seal is no longer square to the spigot
  3. Flexible connector over-stretched or kinked. The folds split or the fin seal pulls off the pipe. Flexible connectors are for awkward retrofits, not for a permanent solution where a rigid one fits
  4. Perished seals. Rubber lip seals harden after 15–20 years; the fin seal on the pipe end lets water out under the pressure of a 6-litre flush
  5. Blocked pipe behind it. A partial blockage downstream backs water up to the connector on each flush and finds the seal; clear the blockage first or the new connector leaks too. See toilet not flushing properly

To replace it: isolate the supply, flush, bail and sponge the pan, undo the floor fixings (and the cistern wall fixings on a close-coupled suite if the pan cannot be pulled forward with the cistern attached), ease the pan forward off the connector, pull the old connector out of the soil pipe, clean the spigot and the pipe socket, lubricate the new seals with silicone grease, push the connector fully home on the pipe, then push the pan back onto it square. Refit the floor fixings with their plastic washers and a bead of silicone at the foot, leaving the back of the foot unsealed so a future leak shows. Flush three times and check with a mirror.

The close-coupling washer and bolts

On a close-coupled suite the cistern sits on the pan and the flush passes through a 50–60 mm hole in the pan's inlet horn, sealed by a doughnut washer compressed by the coupling bolts. The washer hardens with age and chlorine; the bolts corrode; and the cistern starts to rock, which widens the gap. Colour under the cistern after a flush, or a wet band across the back of the pan, confirms it.

Replacing it means removing the cistern: isolate, flush, sponge out, disconnect the supply and the internal overflow, undo the wall screws and the coupling wing nuts (usually seized; cut the bolts if needed), lift the cistern off, and clean the pan horn. Fit the new doughnut washer to the flush valve tail or the cistern outlet as the kit directs, fit new bolts with their sealing washers inside the cistern, lower the cistern squarely, and tighten the wing nuts a little at a time on each side until the cistern is firm and does not rock. Overtightening cracks the cistern base. The cistern wall screws take the weight; the bolts only compress the washer. Kits are £8–£20; the job is 45–90 minutes. If the pan's inlet horn is cracked around a bolt hole, the pan is finished.

Flush-pipe cones and older suites

Low-level and high-level cisterns flush through a 38 mm or 50 mm flush pipe into the back of the pan, sealed with a rubber cone or an internal connector. A perished cone sprays on each flush and the water runs down the back of the pan. A new cone, lubricated and pushed over the pipe and into the pan horn, is a 20-minute fix. On a high-level cistern check the pipe clips as well: a pipe that has dropped pulls the cone out of the horn.

Condensation and supply leaks

Clear water that collects without a flush, in a bathroom with no extractor or a fan that does not run, with a cistern beaded with moisture after a refill, is condensation. Dry the cistern, run a bath or shower, and watch. The fix is ventilation first (Approved Document F requires 15 l/s intermittent extract in a bathroom; see bathroom extractor fan guide), then a cistern liner or an insulated cistern if the problem persists. A dual-flush cistern that refills with 3 litres sweats less than a 9-litre one.

A supply leak is a weeping nut on the fill valve tail, a flexible tap connector with a failed olive, or an isolation valve that drips from its spindle. Dry each fitting, wrap a dry tissue round it and come back in ten minutes. Re-make compression joints with a new olive rather than overtightening; replace a flexible connector rather than cutting a new seal. See pipe joint leak.

When the pan is cracked

A crack around the outlet spigot, the inlet horn or a foot bolt weeps only when the pan is loaded or flushed, and can be invisible until the surface is dry and a torch is held at a low angle. Load the dry pan, hold a mirror under the foot and at the spigot, and look for a dark line growing. A crack in vitreous china cannot be repaired reliably; epoxy will hold for a few months and fail when the customer has forgotten about it. Replace the pan, and if it is a close-coupled suite more than 15 years old, price the matched pan and cistern as a pair under BS EN 997, because a new pan under an old cistern often flushes badly. See toilet types and bathroom suite installation pricing guide.

Pricing and what to tell the customer

Repair Time Parts Typical charge
Diagnosis and pan connector replacement 30–60 min £15–£30 £90–£160
Close-coupling washer and bolt kit 45–90 min £8–£20 £110–£190
Flush cone (low-level) 20–30 min £5–£12 £80–£130
Supply fitting re-make or new tap connector 20–30 min £5–£15 £80–£130
New close-coupled pan, reuse cistern 1.5–2.5 h £80–£200 £220–£400
New close-coupled suite 2–3 h £150–£400 £300–£550

Most are within the half-day minimum (£150–£220 for a plumber in 2026). Tell the customer the floor has been checked: a chipboard floor that is soft around the pan needs a section replaced before the pan goes back, and that is a separate price. See stopcock replacement pricing guide for the common add-on when the isolation valve will not close during the job.

Frequently Asked Questions

Can I just put silicone around the base of the toilet to stop the leak?

No. Silicone around the foot hides the leak and traps the water under the pan, where it rots the floor and breeds the smell. The leak is at a joint above the floor, and sealing the perimeter does nothing to the joint. Fix the joint, then seal the front and sides of the foot for hygiene and leave the back open so any future leak shows itself.

Why does the toilet only leak sometimes?

Because the connector and the coupling washer only see water during a flush, and a marginal seal passes a little on a full flush and nothing on a short one. A dual-flush suite may leak only on the big button. Condensation only happens when the bathroom is humid and the mains water is cold, so it is a winter and a shower-day problem. Ask the customer when they see it; the pattern is half the diagnosis.

The toilet rocks. Is that the cause?

Usually a cause of the leak rather than a separate fault. A pan that rocks on an uneven floor works the connector seal with every use; a cistern that rocks works the coupling washer. Pack the pan level on a mortar bed or with plastic packers, refit the floor screws with their washers, and tighten the coupling bolts evenly before deciding the seals have failed. If the rocking has gone on for years, the seals have probably failed as well.

Is a flexible pan connector acceptable?

Yes where the geometry needs it and the connector is within its rated length and bend, and it is well supported. A flexible connector stretched 400 mm across a void, bent 90° and unsupported will hold solids and split. Where a rigid straight, offset or bent connector fits, use it. Keep the trap seal and the gradient to the branch within BS EN 12056-2 either way.

Do I need to tell anyone about replacing a toilet?

Replacing a pan, cistern or connector like-for-like is not notifiable under the Building Regulations. A new WC must have a flush of no more than 6 litres (Water Supply (Water Fittings) Regulations 1999, Schedule 2 paragraph 25) and WRAS-approved fittings, and if the soil pipe or branch is altered, Approved Document H1 applies to the new drainage. Moving the toilet to a new position is a drainage alteration and may need building control.

Regulations & Standards