Summary
Scalding water from the hot tap is a safety call, not a comfort call. Water at 60 °C causes a full-thickness burn in about five seconds; at 70 °C in under a second. Children, older people and anyone with reduced sensation are the casualties, and the Building Regulations and HSE guidance treat the hot water temperature as a safety control, not a preference. The usual story is a cylinder thermostat that has either been turned up "to get more hot water" or has failed with its contacts stuck closed, so the boiler heats the cylinder every time the hot water programme runs until the boiler's own thermostat stops it — at 75–82 °C. On an open-vented system the cylinder expands into the cistern, the vent pipe steams, and the airing cupboard is tropical; on an unvented cylinder the stat's overheat cut-out trips, and if that fails the T&P relief valve opens and the tundish runs.
The fix is almost always a £15–£40 thermostat and an hour. The job is diagnosing which thermostat, proving it, and then checking the two things the symptom has exposed: whether the system has the controls it should have, and whether the outlets need thermostatic mixing valves. This guide gives the temperatures that matter, the tests by cylinder type, the decision tree, the wiring of a cylinder thermostat on S-plan and Y-plan systems, the immersion faults, the unvented safety devices, and the repair costs. For the legionella side see legionella management; for the valves that make taps safe see thermostatic mixing valves.
Key Facts
- Target storage temperature — 60 °C at the cylinder stat (set 60–65 °C); HSE HSG274 Part 2 and ACOP L8: hot water stored at 60 °C or above, distributed so it reaches 50 °C at outlets within one minute (55 °C in healthcare premises)
- Scald thresholds — roughly: 60 °C, full-thickness burn in about 5 seconds; 55 °C, about 30 seconds; 50 °C, about 5 minutes; 48 °C is the Approved Document G3(4) bath outlet limit for new dwellings; 41–43 °C is the comfortable shower range
- Approved Document G3(4), England — in new dwellings (and where a bath is provided in a material change of use) the hot water supply to a bath must not exceed 48 °C, achieved by a thermostatic mixing valve; not retrospective, but the standard of good practice in existing homes where vulnerable occupants are present
- Cylinder thermostat — a strap-on or pocket thermostat, typically 50–80 °C range with a 60 °C mark, fixed to the cylinder about one-third up from the base (the manufacturer's position); two-position contacts: "calling" (below setpoint) and "satisfied" (above); on a Y-plan it has a common, a satisfied terminal (1) and a demand terminal (2 or C and 1 and 2 depending on make); on an S-plan it switches the live to the hot water 2-port valve
- Failure modes — contacts welded closed (calls for ever: too hot); contacts stuck open (never calls: no hot water); drift (calls at the wrong temperature); poor contact with the cylinder (strapped over insulation, loose strap, foam jacket between stat and copper) so it reads cold and over-heats
- Gravity primary (pre-1980s) — cylinder heated by convection from the boiler with no pump, no valve and often no stat; the cylinder reaches boiler flow temperature by design. Approved Document L (2021) requires a cylinder stat and a zone valve with boiler interlock when the boiler is replaced; retrofitting them is the correct fix for the scald risk, not turning down the boiler
- Immersion heater thermostat — a rod thermostat inside the immersion element, adjustable 50–80 °C (set 60 °C), and since BS EN 60335-2-73 immersion heaters sold for unvented cylinders must include a thermal cut-out that opens at about 85–90 °C and needs manual reset or element replacement. A failed-closed immersion stat heats the cylinder to boiling on a vented cylinder (steam from the vent, banging) and trips the cut-out on an unvented one
- Unvented cylinder safety — two-stage control: a control thermostat (set 60–65 °C) and an overheat thermostat (cut-out at 85–90 °C, manual reset) on each heat source, plus a temperature and pressure relief valve set at 90 °C and the cylinder's rated pressure (typically 7 bar) discharging via a tundish; required by Approved Document G3; a tundish discharging hot water means an overheat has occurred and the cause must be found
- Solar thermal and heat pump cylinders — solar can legitimately take the cylinder to 80–95 °C in summer; the cylinder is sized for it, and a TMV on the outlet (often a 3-in-1 blending valve at the cylinder) limits the distributed temperature; a missing or failed blending valve is the scald cause, not the solar controller. Heat pump cylinders run at 45–55 °C with a weekly legionella pasteurisation cycle to 60 °C by immersion; too hot usually means the immersion stat
- Boiler flow temperature — 70–80 °C on a conventional boiler; the cylinder cannot exceed it; if the cylinder is at 75 °C the stat or valve has failed, not the boiler
- Testing the stat — isolate, disconnect, measure continuity between common and the demand terminal with the cylinder hot: it should be open above the setpoint; turn the dial up past the cylinder temperature and it should close with an audible click. No change of state = replace
- Testing the outlet — probe thermometer in a jug at the nearest hot tap after running for one minute; record the figure; compare with the cylinder stat setting
- Replacement costs — cylinder strap-on stat £15–£40, 30–60 minutes, £70–£140 fitted; immersion thermostat £10–£30, 30–45 minutes, £60–£120; immersion heater element £30–£80, 1 hour with a partial drain, £120–£220; TMV at a bath or basin £40–£120, 1–2 hours, £150–£300; retrofit cylinder stat and 2-port valve to a gravity system, half a day, £350–£650; unvented overheat stat or T&P valve by a G3-qualified installer, £60–£180 part, £150–£320 fitted
- Who may do what — cylinder and immersion stats: a competent heating engineer or electrician (Part P: not notifiable on the existing circuit); unvented cylinder components: an installer holding the unvented hot water (G3) qualification; combi internals: Gas Safe
Quick Reference Table
Diagnosed the problem? Create a repair quote in minutes with squote.
Try squote free →| Symptom | Cylinder type | Most likely cause | Confirming test | Fix |
|---|---|---|---|---|
| Taps scalding, airing cupboard very hot, vent steaming or cistern warm | Open-vented, boiler heated | Cylinder stat set too high or contacts welded; stat strapped over insulation | Stat setting; continuity test; cylinder temperature vs setpoint | Reset or replace stat; re-fix to bare copper |
| Taps scalding, radiators also warm during HW | Open-vented, Y-plan | Stat satisfied contact not switching; valve mid-position | Y-plan wiring and stat test | Replace stat; check valve |
| Taps scalding, no stat or valve on cylinder | Gravity primary | System follows boiler temperature by design | Visual: no stat, no valve on primary | Retrofit stat + 2-port + interlock (Part L) |
| Taps scalding only when immersion used | Any | Immersion stat failed closed or set to max | Immersion stat setting; test | Replace immersion stat (or element on unvented) |
| Taps scalding in summer, boiler off | Solar thermal | No or failed blending valve at cylinder | Cylinder at 80 °C+; outlet unblended | Fit or replace TMV/blending valve |
| Tundish discharging hot water | Unvented | Overheat: control stat failed, overheat stat tripped, T&P opened | Reset overheat stat; test control stat | Replace control stat; check expansion vessel (if discharge is cold, it is expansion, not overheat) |
| Hot water too hot, then none at all | Any | Overheat cut-out tripped after a stat failure | Reset button on immersion/overheat stat | Replace the failed control stat before resetting |
| Boiler cycling constantly on HW, cylinder scalding | Any | Stat calling permanently; cylinder at boiler temp | Stat continuity | Replace stat |
| Water hotter upstairs than downstairs | Any | No fault at the cylinder; downstairs dead leg cooling | Measure at both | Normal; consider secondary return or TMVs |
Detailed Guidance
Decision tree
Hot water too hot at the taps
│
├── Measure at the nearest hot tap after 1 minute: ___ °C
│ ├── 55–65 °C → within the normal storage range; scald risk at outlets
│ │ → recommend TMVs at bath/basins; set stat to 60 °C
│ └── > 65 °C → something is over-heating the cylinder → continue
│
├── What heats the cylinder?
│ ├── Boiler (S-plan / Y-plan / gravity)
│ │ ├── Is there a cylinder thermostat?
│ │ │ ├── No → GRAVITY PRIMARY: cylinder follows boiler
│ │ │ │ → retrofit stat + 2-port + interlock
│ │ │ └── Yes → setting?
│ │ │ ├── > 65 °C → set to 60 °C, re-test
│ │ │ └── ≤ 65 °C → stat fixed to bare copper, strap tight?
│ │ │ ├── No → re-fix on copper, re-test
│ │ │ └── Yes → continuity test: does it open above
│ │ │ setpoint?
│ │ │ ├── No → STAT FAILED → replace
│ │ │ └── Yes → stat fine: valve passing or
│ │ │ wiring (Y-plan terminal 1 / 2)
│ │ │ → see radiators-hot guide
│ ├── Immersion
│ │ → immersion stat set 60 °C? → continuity test → replace stat
│ │ (unvented: element with integral cut-out; check cut-out reset)
│ ├── Solar thermal / thermal store
│ │ → blending valve present and working? → fit or replace TMV
│ └── Heat pump
│ → pasteurisation immersion stat / controller setting → correct
│
└── Unvented cylinder: tundish discharging?
├── Hot water discharge → OVERHEAT: control stat failed; overheat
│ stat or T&P operated → replace control stat; test safety
│ devices; G3 installer
└── Cold/warm intermittent discharge → EXPANSION: vessel charge or
diaphragm → not a temperature fault
The cylinder thermostat: position, setting, wiring
The strap-on stat reads the copper through its back plate; it has to be on bare copper, pressed firmly by the strap, with the foam jacket cut away behind it and replaced over it. A stat strapped outside a foam jacket, or over a crease in a factory-foamed cylinder's skin, reads 10–20 °C low and lets the cylinder run away. It sits roughly one-third of the way up the cylinder (most manufacturers specify 300–400 mm from the base on a 900–1,200 mm cylinder) so that it registers the bulk of the stored water, not the hot layer at the top.
On an S-plan the stat simply switches the programmer's hot water live to the hot water 2-port valve motor; valve open, end switch fires boiler and pump. On a Y-plan the stat has a common (fed from programmer terminal 3, hot water on), a demand terminal that feeds the boiler and pump directly for hot water, and a satisfied terminal that feeds the mid-position valve's grey wire to drive it over to heating only. A Y-plan stat wired with the demand and satisfied terminals swapped heats the cylinder continuously and puts the valve in the wrong position: the symptom is too-hot water plus radiators warm during hot water. See zone valves and wiring and radiators hot when heating off.
To test: isolate at the fused spur and verify dead. Disconnect the stat's wires and measure continuity between common and demand with the cylinder hot (above the setpoint): it should be open. Turn the dial up past the cylinder's temperature: it should click and close. Turn it back: it should open. A stat that does neither, or that is closed at every setting, is replaced. Set the new one at 60 °C and mark the dial.
Gravity systems without a stat
A pre-1980s system where the cylinder primary is heated by gravity circulation has no valve, often no stat, and the cylinder heats to whatever the boiler's thermostat is set to — 70–80 °C — every time the boiler runs for heating. The owner turns the boiler stat down to 60 °C to cope and then has cold radiators. The correct fix is the Approved Document L controls package: a cylinder thermostat, a 2-port motorised valve on the primary flow to the cylinder, a wiring centre, and the valve's end switch interlocking the boiler, so the boiler stops when both the cylinder and the room are satisfied. On a gravity primary the valve must be a type suitable for gravity flow (full-bore, mounted to allow convection when open) or the primary converted to pumped. It is half a day and £350–£650, it saves gas, and it is required when the boiler is replaced. See heating controls.
Immersion heaters
The immersion's rod thermostat sits in a pocket inside the element and is adjustable with a screwdriver, 50–80 °C with a 60 °C mark. Failed closed, it heats the cylinder until the water boils on a vented cylinder — banging, steam from the vent into the cistern, the cistern warm — or until the thermal cut-out opens on a modern element. Replacement thermostats are a standard length (commonly 11 inches / 280 mm and 18 inches / 457 mm) and cost £10–£30; swap it with the power isolated and verified dead at the 20 A double-pole switch, test the element's insulation resistance while you are there, and set it to 60 °C. On an unvented cylinder the immersion must be a type with an integral thermal cut-out (BS EN 60335-2-73), and the cut-out is a one-shot or resettable device that opened because the control stat failed: replace the stat or the whole element, do not just reset and leave. The immersion circuit itself — 2.5 mm² minimum on its own 16 A or 20 A circuit with a double-pole switch — is covered in unvented cylinders for the unvented case.
Unvented cylinders: what the tundish is telling you
An unvented cylinder under Approved Document G3 has, for each heat source, a control thermostat and an independent overheat thermostat (energy cut-out) that interrupts the supply at about 85–90 °C and needs a manual reset; and on the cylinder a temperature and pressure relief valve set at 90 °C that discharges through a tundish to a safe place. There is also an expansion relief valve on the cold inlet set to the cylinder's working pressure plus a margin (6–8 bar typically). Discharges distinguish the faults: hot water from the tundish during heating means an overheat — the T&P has opened because the control stat failed and the overheat stat did not catch it, or the overheat stat opened and the T&P followed; find the failed control stat and replace it, then test the overheat stat and the T&P valve manually (the test lever) and record it. Cold or lukewarm water that discharges intermittently, particularly when the cylinder is heating from cold, is the expansion relief valve dealing with a flat expansion vessel or a failed internal air gap, and is a pressure fault, not a temperature one. Work on an unvented cylinder's safety devices is for an installer with the G3 qualification (Building Regulations Approved Document G, paragraph 3.x on competence). See unvented cylinders.
Solar thermal and the blending valve
A solar cylinder may reach 85–95 °C on a sunny day; the controller is designed to allow it (some limit at 85 °C, some at 95 °C), and the cylinder's T&P valve is set accordingly. The safe outlet temperature comes from a thermostatic blending valve at the cylinder outlet, set to 55–60 °C, feeding the whole hot water distribution. A blending valve that has scaled or whose cartridge has failed passes unblended water: scalding taps on a summer afternoon with the boiler off. Replace the cartridge or the valve (£40–£150, 1–1.5 hours), and check the controller's maximum cylinder temperature setting.
Scald prevention at the outlets
Once the cylinder is back at 60 °C, the taps still deliver 55–60 °C, which scalds in seconds. In new dwellings Approved Document G3(4) requires a TMV limiting the bath to 48 °C; in existing homes with children, older people or disabled occupants, the recommendation is a TMV2-approved valve (BS EN 1111 for mains-pressure systems, BS EN 1287 for gravity) at the bath and basins, set to 41–44 °C at basins and 44 °C at the bath, and in care settings TMV3 (NHS D 08) valves are required. A whole-house blending valve at the cylinder set to 55 °C reduces the risk without a valve at every outlet but leaves the legionella control to the stored temperature. Price the TMVs as an option on the same visit; the customer who has just had a scalding tap usually says yes. See thermostatic mixing valves and thermostatic shower valve replacement pricing guide.
Charging the job
| Job | Time | Parts | Typical charge |
|---|---|---|---|
| Diagnose, measure, test stat, reset to 60 °C | 30–45 min | — | £60–£110 |
| Replace cylinder strap-on thermostat | 30–60 min | £15–£40 | £70–£140 |
| Replace immersion thermostat | 30–45 min | £10–£30 | £60–£120 |
| Replace immersion element (partial drain) | 1 h | £30–£80 | £120–£220 |
| Replace unvented control or overheat stat (G3) | 45–90 min | £30–£90 | £120–£220 |
| Replace T&P relief valve (G3) | 1–1.5 h | £40–£120 | £150–£320 |
| Fit TMV at a bath or basin | 1–2 h | £40–£120 | £150–£300 |
| Retrofit cylinder stat, 2-port valve, wiring centre, interlock on a gravity system | Half a day | £150–£300 | £350–£650 |
| Replace solar blending valve | 1–1.5 h | £40–£150 | £130–£280 |
See plumber hourly rate guide and electrician hourly rate guide.
Frequently Asked Questions
What temperature should a hot water cylinder thermostat be set to?
60 °C, with 65 °C as the upper limit. That is hot enough to control legionella in the stored water (HSE guidance: stored at 60 °C, 50 °C at the taps within a minute) without wasting gas or scalding more than necessary. Below 55 °C the legionella risk rises; above 65 °C the scald risk and running cost rise with no benefit.
Why is my hot water suddenly scalding hot?
Most often the cylinder thermostat has failed with its contacts closed, so the boiler keeps heating the cylinder until the boiler's own thermostat stops it at 75–80 °C. Other causes: someone turned the stat up, the stat is not making good contact with the cylinder, the immersion heater's thermostat has failed, or on a solar cylinder the blending valve has failed. Test and replace the thermostat; do not just turn the boiler down.
Is it dangerous if my hot water is too hot?
Yes. Water at 60 °C causes a serious burn in about five seconds and at 70 °C in under a second; children and older people are most at risk. On an unvented cylinder, an over-heating cylinder also means the safety devices are being relied on. Have the thermostat fixed promptly and consider thermostatic mixing valves at the bath and basins.
Why is water coming out of the pipe by my hot water cylinder?
If it is hot and happens while the cylinder is heating, the cylinder has overheated and the temperature and pressure relief valve has opened: the control thermostat has probably failed. If it is cold or warm and happens intermittently, the expansion relief valve is discharging because the expansion vessel has lost its charge. Either way it needs a G3-qualified installer; the tundish is doing its job by making the fault visible.
Can I just turn the boiler thermostat down to stop the water being too hot?
On a system with a working cylinder stat it will not help, because the cylinder stat sets the water temperature. On an old gravity system with no cylinder stat it will reduce the water temperature, but it will also make the radiators cooler and does not fix the missing control. The correct fix is a cylinder thermostat and motorised valve with boiler interlock, which Approved Document L requires when the boiler is replaced.
Regulations & Standards
Building Regulations 2010, Approved Document G (2015 edition incorporating 2016 amendments) — G3 hot water supply and systems: unvented cylinder safety devices, competence, discharge pipework; G3(4) 48 °C bath outlet in new dwellings
Building Regulations 2010, Approved Document L, Volume 1: Dwellings (2021 edition) — cylinder thermostat, zone valve and boiler interlock for stored hot water
Domestic Building Services Compliance Guide (2021) — control specifications for hot water systems
HSE Approved Code of Practice L8 (2013) and HSG274 Part 2 (2014) — legionella control; storage at 60 °C, distribution at 50 °C
BS EN 1111:2017 and BS EN 1287:2017 — thermostatic mixing valves, high and low pressure; TMV2 scheme
NHS Estates D 08 / TMV3 — thermostatic mixing valves in care settings
BS EN 60335-2-73:2003+A2:2009 — safety of electric immersion heaters; thermal cut-outs
BS 1566-1:2002+A1:2011 — copper indirect cylinders for domestic purposes (open-vented)
BS EN 12897:2016+A1:2020 — indirectly heated unvented (closed) storage water heaters; safety devices
BS 7671:2018+A4:2026 — immersion heater circuits (Regulation 554.3) and isolation
Building Regulations 2010, Approved Document P (2013 edition) — like-for-like thermostat replacement not notifiable
Water Supply (Water Fittings) Regulations 1999 — hot water temperature and expansion provisions (Schedule 2, paragraph 17)
Housing Health and Safety Rating System (England) Regulations 2005 — hot surfaces and scalding as a hazard in rented housing
Approved Document G: Sanitation, hot water safety and water efficiency — gov.uk; G3 safety devices and 48 °C limit
Approved Document L, Volume 1: Dwellings (2021) — gov.uk; hot water controls
HSE HSG274 Part 2 — Legionella in hot and cold water systems — storage and distribution temperatures
HSE — Legionnaires' disease: ACOP L8 — duties and control measures
Hot Water Association — unvented cylinder guidance — safety devices and competence
TMV2 scheme — BEAMA — thermostatic mixing valve approvals
Child Accident Prevention Trust — bath water scalds — scald thresholds and prevention
heating controls — cylinder stats, zone valves and interlock
zone valves and wiring — Y-plan and S-plan stat wiring
radiators hot when heating off — the companion symptom on a failed valve or stat
no hot water but heating works — the same stat failing open
unvented cylinders — G3 safety devices and the tundish
legionella management — why 60 °C is the storage target
thermostatic mixing valves — making the outlets safe
hot water cylinder types guide — vented, unvented, solar and heat pump cylinders
domestic hot water cylinder sizing — sizing so nobody turns the stat up for "more hot water"
thermostatic shower valve replacement pricing guide — pricing TMV work