Domestic Hot Water Cylinder Sizing: Recovery Rate, Primary Coil, G3 Compliance and Selection by Property

Quick Answer: Size a domestic hot water cylinder on occupancy and bathroom count — roughly 35–45 litres of stored hot water per person for a boiler-fed system, more for heat pumps and high-demand homes. The cylinder must recover fast enough for the household, which depends on the primary coil surface area: a gas/oil boiler cylinder typically has a 1.0–1.5 m² coil, while a heat pump cylinder needs a much larger coil (2.5–3.0 m²+) to transfer heat at low flow temperatures. Unvented cylinders are notifiable under Building Regulations Part G3 and must be installed by a G3-qualified operative with the mandatory safety devices.

Summary

Get the cylinder wrong and the homeowner either runs out of hot water mid-shower or pays to heat a tank far bigger than they need. Cylinder sizing is two questions answered together: how much hot water do they store, and how fast does it recover? Stored volume covers the peak draw (back-to-back showers, filling a bath); recovery rate — driven by the heat source and the primary coil — determines how quickly the tank is hot again. This article covers sizing by property type, recovery and coil sizing (including the much larger coils heat pumps demand), reheat times, vented vs unvented, the G3 legal framework, and the discharge pipework that catches more installers out than any other detail.

The big shift in recent years is the heat pump. A traditional gas or oil boiler runs its primary circuit at 70–80°C, so a modest coil transfers plenty of heat into the cylinder. A heat pump runs the cylinder coil at perhaps 50–55°C, a far smaller temperature difference, so the coil has to be physically much bigger to move the same energy. Fitting a standard boiler cylinder on a heat pump gives glacial reheat times and poor performance — heat pump cylinders are a different specification, not just a different label. This is covered in depth in heat pump cylinders.

The most common misconception is that bigger is always safer. An oversized cylinder costs more to buy, takes longer to reheat, suffers more standing heat loss, and on a heat pump can hurt efficiency. Size to the household's real peak demand, then make sure recovery keeps up. The cylinder-selection fundamentals (direct/indirect, vented/unvented, thermal store) are in cylinder selection and unvented cylinders; this article concentrates on getting the size and coil right.

Key Facts

Quick Reference Table

Quoting a heating job? squote turns a 2-minute voice recording into a professional quote.

Try squote free →
Property Occupants Suggested cylinder (boiler-fed indirect)
1-bed flat 1–2 120–150 L
2-bed, 1 bath 2–3 150–180 L
3-bed, 1 bath 3–4 180–210 L
3–4 bed, 2 baths 4–5 210–250 L
4–5 bed, 2–3 baths 5–6 250–300 L
Large home, 3+ baths 6+ 300 L+ (or twin cylinders)

Heat pump installs typically step up one size and require a high-surface-area coil cylinder.

Heat source Primary flow temp Coil area (typical) Reheat character
Gas/oil condensing boiler 70–80°C ~1.0–1.5 m² Fast (~20–40 min full tank)
Solar thermal (lower coil) variable dedicated lower coil Pre-heat, twin-coil cylinder
Air source heat pump 50–55°C ~2.5–3.0 m²+ Slow by design (1–2+ hr)
Ground source heat pump 50–55°C ~3.0 m²+ Slow; size coil generously
G3 safety device Purpose Key spec
Temperature/pressure relief valve Discharges if water overheats/over-pressurises Opens ~90–95°C / set pressure
Expansion vessel / internal air gap Absorbs expansion of heated water Sized to cylinder volume
Pressure-reducing valve Limits inlet pressure to cylinder rating e.g. set to 3 bar [model-specific]
Expansion relief valve Relieves excess pressure Set above PRV, below cylinder max
Tundish Visible air break in discharge Within 500 mm of relief valve

Detailed Guidance

Sizing by occupancy and bathrooms

Start with peak simultaneous demand, not average use. A four-person family with one bathroom rarely draws hot water simultaneously; the same four people across two bathrooms can run two showers at once. Sizing logic:

Recovery rate and primary coil surface area

Recovery is where sizing gets technical. The coil is a heat exchanger; the heat transferred depends on its surface area and the temperature difference between the primary water and the stored water:

Fitting a standard boiler cylinder on a heat pump is a classic error: the coil is too small, the heat pump short-cycles or runs flat out for hours, reheat is painfully slow, and efficiency suffers. Always specify a heat-pump-rated cylinder for a heat pump install. See heat pump cylinders and low temperature design.

Reheat time — what to tell the customer

   Reheat expectation by heat source
   ---------------------------------
   Boiler cylinder (1.0-1.5 m2 coil, 70-80C primary)
     full tank cold -> hot:  ~20-40 minutes
   Heat pump cylinder (2.5-3.0 m2 coil, 50-55C primary)
     full tank cold -> hot:  ~1-2+ hours (by design)

   Implication:
     boiler -> can run smaller tank, reheats between draws
     heat pump -> size tank larger, schedule reheat for
                  off-peak / before peak demand

Heat pump owners need to understand the cylinder reheats slowly and is best scheduled (e.g. a timed reheat before the morning peak, often on a cheaper electricity tariff). This is normal, not a fault — managing expectations at handover prevents callbacks.

Vented vs unvented

G3 compliance, safety devices and discharge pipework

Unvented hot water storage is controlled by Building Regulations Approved Document G3 (part g water). Key requirements:

Standing loss, ErP labelling and insulation

Modern cylinders carry an ErP energy label (A–G) reflecting their standing heat loss — the energy lost from the stored hot water over 24 hours. A well-insulated cylinder (factory-applied rigid foam) holds heat far better than an old felt-lagged copper tank. For heat pump installs especially, low standing loss matters because the heat pump generates expensive low-temperature heat; choose a high-rated, well-insulated cylinder and keep pipe runs short and lagged (pipe lagging).

Frequently Asked Questions

How big a cylinder for a 4-bed, 2-bathroom house on a gas boiler?

Around 210–250 litres for a boiler-fed indirect cylinder is the usual sweet spot — enough stored hot water for two bathrooms with some simultaneous draw, and a fast-recovering coil to refill between events. If the household includes power showers, a large bath, or runs hot water heavily at one time, step up toward 250–300 L. On a heat pump, size up a notch and specify a heat-pump-rated cylinder with a large coil.

Why does the heat pump cylinder have such a big coil?

Because a heat pump runs the primary water far cooler than a boiler — about 50–55°C versus 70–80°C. The smaller temperature difference between the primary water and the stored water means each square metre of coil transfers less heat, so the coil must be physically much larger (typically 2.5–3.0 m²+) to move the heat pump's output into the tank at a useful rate. A standard boiler cylinder fitted to a heat pump reheats far too slowly.

Is an unvented cylinder always better than a vented one?

No. Unvented gives mains pressure at every outlet and removes the loft tank, which is excellent where the incoming mains is strong. But it is G3-notifiable, needs the full safety-device set and correct discharge pipework, and depends entirely on a good mains flow and pressure. On a weak mains supply, a vented cylinder (optionally with a pump) can deliver better real-world performance. Always check the incoming mains before recommending unvented.

Does the cylinder need to store water at 60°C?

Yes, for Legionella control the stored water should reach ≥60°C (and the pasteurisation/immersion cycle on heat pump systems is set to reach this periodically). To prevent scalding, hot water delivered to a bath is limited to 48°C under Part G via a thermostatic mixing valve. Store hot, deliver safe — see legionella management and thermostatic mixing valves.

What size does the discharge (D2) pipe need to be?

D2 must be at least one pipe size larger than the relief-valve discharge (D1) and a minimum of 22 mm, then upsized further according to the run length and number of bends using the G3 / manufacturer's table. A long discharge route with several elbows can require 28 mm or larger. It must fall continuously to a safe, visible termination. Undersizing or running it uphill is a G3 non-compliance and a safety risk.

Regulations & Standards