Where Do Cavity Trays and Weep Holes Go, and How Do You Form Them?
Where cavity trays go (over lintels, meter boxes, vents, roof abutments and other cavity bridges) and how to form them: rise of about 150 mm across the cavity, 150 mm past each lintel end, stop ends, 100 mm sealed laps; weep holes at no more than 900 mm centres under Approved Document C (450 mm on NHBC-referenced and many manufacturer details) with at least two per opening; steel lintels with integral profiles; stepped trays at lean-to roofs; the 225 mm cavity below the DPC; weep vent types; and a defect table for damp above windows and at reveals.