Summary
Air bricks are the cheapest bit of a house and one of the most frequently ignored. Under a suspended timber ground floor, the void collects moisture from the ground. Ventilation carries that moisture away. Close the vents and the relative humidity under the floor climbs until timbers sit above 20% moisture content, the point at which fungal decay becomes likely. The result, often years later, is soft, sagging floors, a musty smell and in the worst cases dry rot spreading into skirting and wall plaster.
Tradespeople cause many of these problems by accident. A new patio laid at the level of the air bricks, a side extension built over them, render taken down over the grilles, or a "draught-proofing" job where someone stuffed them with insulation. A competent quote for any of those jobs should say what will be done about the underfloor ventilation.
This article covers how much ventilation is needed, how to work out how many air bricks a floor needs, the types of air brick and telescopic vent, and what to do when an extension or patio covers existing vents.
Key Facts
- Ventilation rate (timber floors) — openings in two opposing external walls of at least 1,500 mm² per metre run of wall or 500 mm² per m² of floor area, whichever gives the greater area (Approved Document C).
- Void depth — at least 150 mm from the top of the ground covering to the underside of the floor or insulation, and at least 75 mm to the underside of wall plates.
- Ground covering — typically 100 mm of concrete on clean hardcore, or 50 mm concrete or fine aggregate on a 0.25 mm (1,200 gauge) polythene membrane laid on sand blinding.
- Covering level — the top of the ground covering should not be below the highest adjoining external ground level unless the void is drained.
- Cross-flow — internal sleeper walls and partitions under the floor must be honeycombed or have openings so air can pass right across.
- Free area — the figure that counts is the declared free (open) area of the vent, not its face size; plastic air bricks usually give much more free area than clay air bricks of the same size.
- Air brick height — keep vents at least 75 mm above external ground or paving, and well clear of splash.
- Telescopic vents — sleeves that carry air across a cavity wall from the outer air brick to the void, adjustable to the floor level.
- Cavity trays — in exposed locations a short cavity tray with stop ends over each telescopic sleeve stops water entering via the sleeve.
- Vermin — grilles should exclude rodents; apertures of about 5–10 mm are typical on modern vents.
- Suspended concrete floors — where a beam and block floor has a ventilated void, the same opening rule is commonly applied, with a void at least 150 mm deep.
- Timber decay threshold — timber kept above around 20% moisture content is at risk of fungal decay.
- Radon and ground gas — ventilated voids are also part of some radon and ground-gas protection designs; do not block them.
Quick Reference Table
Spending too long on quotes? squote turns a 2-minute voice recording into a professional quote.
Try squote free →| Wall length (opposing walls) | Floor area | 1,500 mm²/m rule | 500 mm²/m² rule | Required total |
|---|---|---|---|---|
| 2 × 4 m | 16 m² | 12,000 mm² | 8,000 mm² | 12,000 mm² |
| 2 × 5 m | 25 m² | 15,000 mm² | 12,500 mm² | 15,000 mm² |
| 2 × 6 m | 36 m² | 18,000 mm² | 18,000 mm² | 18,000 mm² |
| 2 × 7 m | 56 m² (7 × 8 m) | 21,000 mm² | 28,000 mm² | 28,000 mm² |
| 2 × 8 m | 80 m² (8 × 10 m) | 24,000 mm² | 40,000 mm² | 40,000 mm² |
The "metre run" is the length of the two opposing walls where the vents go. For deep floors, the floor-area rule usually governs.
Detailed Guidance
Working out how many air bricks you need
- Decide which two opposing walls will take the vents. Ideally they are the long walls, giving the shortest air path.
- Calculate the 1,500 mm² per metre requirement: total length of the two vented walls × 1,500.
- Calculate the 500 mm² per m² requirement: floor area × 500.
- Take the greater figure.
- Divide by the declared free area of the air brick you are using, and round up.
- Split them evenly between the two walls and space them along each wall, with a vent near each corner so there are no dead pockets.
Worked example — a front room 4.5 m wide and 5.0 m deep, vents in the front and rear walls (each 4.5 m):
- Wall rule: 2 × 4.5 m × 1,500 = 13,500 mm²
- Area rule: 4.5 × 5.0 = 22.5 m² × 500 = 11,250 mm²
- Required: 13,500 mm²
- Using an air brick with a declared free area of 4,500 mm²: 13,500 ÷ 4,500 = 3, so fit at least 2 per wall (4 total) to keep the air flow balanced.
The same room using an old clay air brick with a declared free area of around 1,300 mm² would need 11 vents, which shows why replacing clay air bricks with higher free-area plastic vents is a common improvement.
Types of vent
| Type | Typical use | Notes |
|---|---|---|
| Clay or terracotta air brick | Period and solid-wall houses, matching existing | Low free area; heavy; can clog |
| Plastic air brick (215 × 65 mm and multiples) | New and replacement work | Higher free area, rodent mesh |
| Cast iron grille | Period properties | Rust can reduce free area |
| Telescopic underfloor vent | Cavity walls, new floors | Carries air across the cavity; adjust to floor level |
| Periscope vent | Where the floor void is below external ground level | Takes air from above ground into the void |
| Through-floor duct | Where an extension covers original vents | Ducts air from new external wall to old void |
Use the manufacturer's declared free area in calculations. Do not use the face size.
Raising ground levels, patios and paths
The most common fault is external ground level raised to, or above, the air bricks. Water then runs straight into the void, and soil or paving blocks the vents.
Practical rules for patio and path jobs:
- Keep finished paving at least 150 mm below the DPC, which normally means well below any air bricks too. See damp proof course.
- Never bed paving against air bricks. If levels cannot be dropped, fit periscope vents to lift the intake above the new level.
- Leave a gravel strip and fall paving away from the wall.
- Note existing vent positions before starting and photograph them.
Extensions built over existing air bricks
A rear or side extension often covers the air bricks that ventilate the original floor. If nothing is done, the old void loses its cross-flow. Solutions:
- Ducting — run 100 mm or larger ducts from the old air brick positions through the new floor void or slab to new air bricks in the extension's external walls.
- Ventilate through the new void — if the extension also has a suspended floor, link the two voids so cross-ventilation continues from the original front wall to the new rear wall.
- Add vents elsewhere — if the existing floor can be ventilated from side walls instead, add vents there to restore the total.
Building control will expect this to be shown on the drawings and inspected. See building control inspection stages.
Blocked vents and timber decay
Signs that underfloor ventilation is inadequate:
- Musty smell, especially in cupboards under stairs and at skirting level.
- Soft, springy or sagging floorboards, often near external walls.
- Fungal growth or orange spore dust at skirting boards.
- Condensation or water standing on the ground covering.
- High moisture readings in skirtings and joist ends.
Remedies: clear the vents, add vents to reach the required free area, lower external ground, fix leaking pipes under the floor, and treat or replace decayed timber. See timber rot treatment.
Vents and heat loss
Customers sometimes ask for air bricks to be blocked to stop draughts. The right answer is to insulate and seal the floor itself, not to close the void. Under-floor insulation fitted between joists, with an airtight layer at floor level, stops the draught while the void stays ventilated. Blocking vents saves a little heat and risks the whole floor structure.
Frequently Asked Questions
Can I block air bricks to stop draughts?
No. The air bricks ventilate the void under a suspended timber floor and stop the joists rotting. Insulate and draught-seal the floor instead, and keep the vents open.
How high above the ground should air bricks be?
At least 75 mm above external ground or paving, and in practice as high as the floor void allows, with paving falling away from the wall. Where the void is below ground level, use periscope vents.
Do solid concrete floors need air bricks?
No. A solid ground-bearing slab has no void to ventilate. Air bricks in a house with solid floors may be serving a different purpose, such as a room vent for a gas appliance or a ventilated void that was left when floors were replaced, so find out before blocking any vent.
How many air bricks does a typical terraced house need?
It depends on the floor area and the length of the vented walls. A typical 4.5 × 5 m front room needs around 13,500 mm² of free area, which is three or four modern plastic air bricks or many more old clay ones. Calculate it for each room or connected void.
Does a new extension need air bricks?
Only if it has a suspended floor with a void. Most extensions use a ground-bearing slab or an insulated beam and block floor. If the extension covers existing air bricks for the original house, though, it must restore the ventilation to the old floor.
Regulations & Standards
Building Regulations 2010, Part C — resistance to moisture; Approved Document C Section 4 covers suspended timber ground floors, void depth, ground covering and ventilation openings.
Building Regulations 2010, Part L — floor insulation and air-tightness requirements when floors are renovated.
Building Regulations 2010, Part F — ventilation of habitable rooms, which is separate from underfloor ventilation.
BS 5250:2021 — management of moisture in buildings, including condensation risk in floor voids.
GOV.UK — Approved Document C — ventilation of suspended timber ground floors
RICS isurv — Timber floors: installation and ventilation — surveyors' guidance on void ventilation
Historic England — Energy efficiency and historic buildings: suspended timber floors — insulating while keeping voids ventilated
Forterra — Bison vents and air bricks data — beam and block floor ventilation details
damp proof course — DPC heights and keeping external levels down
timber rot treatment — treating wet and dry rot in floor timbers
beam and block floors — ventilated voids under suspended concrete floors
cavity trays and weep holes — trays over telescopic vents in cavity walls
condensation — how moisture builds up in enclosed voids