Summary
Repressurising a boiler is the most common heating "fault" a customer reports and the one most often fixed over the phone. It is also the task most often done wrong: loops left connected, systems pumped up to 2.5 bar because "more is better", keyed loops forced, and inhibitor diluted to nothing by years of fresh-water top-ups. For the heating engineer, the job is partly the two-minute procedure and partly the explanation to the customer of what the pressure gauge is telling them, so that the next call is for the leak rather than for another top-up.
This article covers the four common filling loop arrangements found on UK combi and system boilers, the correct cold-fill pressure and why it matters, the step-by-step procedure for each loop type, what to do when the pressure has been taken too high, the Water Regulations position on temporary connections and backflow, and the point at which topping up stops being maintenance and becomes a symptom. It is written for the engineer and for the tradesperson who wants to leave a customer able to do the safe part themselves. For the diagnosis of why a system is losing pressure see boiler loses pressure repeatedly and boiler losing pressure; for the expansion vessel itself see system pressure and expansion vessels.
Nothing in this guide involves opening the boiler case. Operating a filling loop and bleeding a radiator are not gas work. Anything behind the case, including an internal filling device that has failed, is work on a gas appliance under the Gas Safety (Installation and Use) Regulations 1998 and is for a Gas Safe registered engineer.
Key Facts
- Correct cold pressure — 1.0–1.5 bar with the heating off and the system cold; most manufacturers' installation instructions specify 1.0–1.2 bar. Check the boiler's own manual; a tall house with radiators two floors above the boiler may need the upper end
- Hot running pressure — expect a rise of 0.3–0.7 bar as the water expands; a reading of 1.5–2.0 bar hot is normal. If hot pressure approaches 2.5–3.0 bar the expansion vessel is undersized or has lost its charge
- Pressure relief valve — set to lift at 3.0 bar on domestic boilers; if it has lifted it often weeps afterwards and needs replacing (see boiler pressure relief valve discharging)
- Low-pressure lockout — most boilers lock out or display a fault code below about 0.5 bar, or when a low-pressure switch opens; the common codes are Vaillant F.22, Worcester Bosch E9 or 224 low pressure variants, Ideal F1, Baxi E119
- Expansion vessel pre-charge — typically 0.75–1.0 bar on the air side, checked with the water side at zero; set to the manufacturer's figure
- Filling loop types — external braided flexible loop with two isolating valves and a double check valve; internal keyed filling link (Worcester Bosch, Vaillant); integral filling valve with a lever or knob (Ideal, Baxi, Glow-worm and others); permanent rigid loop with a double check valve (compliant only if it also has an isolating valve and the connection is to a WRAS-approved arrangement)
- Water Regulations — a flexible filling loop is a temporary connection and must be disconnected after use; the connection to the heating circuit must be protected by a double check valve to BS EN 13959 because heating water with inhibitor is fluid category 3 under BS EN 1717 and Schedule 2 of the Water Supply (Water Fittings) Regulations 1999
- Inhibitor — every top-up with fresh mains water dilutes the inhibitor; BS 7593:2019 requires the inhibitor concentration to be checked annually and topped up, and a system that has been repeatedly filled needs a test kit reading and a dose
- Bleeding after filling — adding water introduces air; bleed radiators from the lowest to the highest, then re-check and correct the pressure (see bleeding radiators procedure)
- Frequency rule — a healthy sealed system should hold pressure for a year or more; a top-up more than once or twice a year, or any top-up of more than about 0.5 bar, means a leak, a passing PRV, a failed expansion vessel diaphragm or a weeping automatic air vent
- Overpressure — above about 2.5 bar cold, bleed a radiator (not the PRV) into a container until the gauge reads 1.0–1.5 bar
- Customer call-out — a visit solely to repressurise is typically £60–£120; the engineer should use it to check the expansion vessel charge and look for the leak, not just open the loop
Quick Reference Table
Quoting a heating job? squote turns a 2-minute voice recording into a professional quote.
Try squote free →| Gauge reading (system cold) | Meaning | Action |
|---|---|---|
| 0–0.5 bar | Too low; boiler will lock out or has locked out | Repressurise to 1.0–1.5 bar; find out where the water went |
| 0.5–1.0 bar | Low; boiler may run but is marginal | Top up to 1.0–1.5 bar; monitor over a week |
| 1.0–1.5 bar | Correct cold-fill range | None |
| 1.5–2.0 bar cold | Slightly high; usually overfilled | Bleed a radiator to bring it down to 1.0–1.5 bar |
| 2.0–2.9 bar cold | Overfilled or filling loop passing | Bleed down; check loop valves are shut and hose disconnected; check for passing internal filling valve |
| 3.0 bar or PRV discharging | Overpressure; PRV has lifted | Bleed down; test expansion vessel; PRV likely to need replacement; find the cause |
| Rises to near 3 bar when hot, drops to normal cold | Expansion vessel flat or failed | Recharge or replace the vessel; do not just keep topping up |
| Drops steadily over days with no visible leak | Slow leak or PRV weeping to outside | Check PRV discharge pipe outside; pressure-test; leak detection (see leak detection) |
Detailed Guidance
Why the pressure matters
A sealed system has no open vent or feed-and-expansion tank. Instead the water is held under a static pressure and an expansion vessel with a rubber diaphragm absorbs the volume change as the water heats. The cold-fill pressure does two things: it keeps the highest radiator full of water (roughly 0.1 bar per metre of height above the gauge, plus a margin), and it sets the starting point against which the expansion vessel works. Too low and the top radiators air up, the pump cavitates and the boiler's low-pressure switch opens. Too high and the hot expansion pushes the pressure to the PRV's 3 bar lift point, water is discharged outside and the cycle repeats.
The manufacturer's figure in the installation manual is the one to follow. The general 1.0–1.5 bar band works for almost every two-storey house; a three-storey property with the boiler in the basement and radiators 8 m above the gauge needs the upper end, and some manufacturers allow up to 2.0 bar cold where the static head demands it, provided the expansion vessel is sized for it.
Identifying the filling loop
Four arrangements cover nearly every domestic boiler installed in the last 25 years:
- External braided flexible loop. A short stainless-braided hose with a valve at each end, connected between a tee on the cold mains and a tee on the heating return under the boiler. One valve is usually a lever or screwdriver-slot ball valve; one end has the double check valve (a small cylindrical body, often marked with a flow arrow). The hose should be stored disconnected with a cap on each tee, although in practice most are left connected.
- Internal keyed filling link. Worcester Bosch and some Vaillant models have a filling point under the boiler operated with a plastic key that is pushed in and turned, with a separate white or grey knob for the flow. The key lives in a clip under the boiler and the manual shows the sequence; forcing the key without the knob released breaks it.
- Integral filling valve. Ideal, Baxi, Glow-worm, Alpha and many others have a lever, knob or tap under the boiler that opens the filling path directly, with an internal double check valve. Some have a push-in style that springs closed when released.
- Permanent rigid loop. A fixed pipe with a double check valve and an isolating valve, sometimes with a pressure gauge. Acceptable to the Water Regulations only if it has the double check valve and a means of isolation; a fixed loop with a single check valve or none is a backflow risk and should be replaced with a compliant arrangement.
If the loop cannot be found, look for the cold mains pipe entering the boiler and follow it; the tee is usually within 300 mm of the boiler's lower connections. On a system boiler the loop may be remote, near the cylinder or at a filling point in the airing cupboard.
Procedure — external braided loop
- Turn the boiler off at its controls and let the system cool to room temperature; filling a hot system gives a false high reading and can crack a hot heat exchanger with cold water
- Confirm the gauge reading and note it
- Connect the hose if it is stored disconnected, checking the washers; if it is already connected, check both valves are closed before you start
- Open the valve at the mains end fully
- Open the valve at the heating end slowly, watching the gauge. Water can be heard entering the system
- Close the heating-end valve when the gauge reads 1.0–1.5 bar (or the manufacturer's figure). It takes 10–30 seconds on a typical house
- Close the mains-end valve
- Disconnect the hose and cap both tees; if the installation does not permit this, at minimum leave both valves firmly closed and record on the job sheet that the loop is a permanent connection
- Turn the boiler back on and run the heating; bleed radiators that are cold at the top, then re-check the cold pressure the next day and top up once more if needed
Procedure — keyed and integral filling devices
Follow the manufacturer's sequence exactly. For a Worcester Bosch keyed link the sequence is: insert the key with the arrow aligned, push and turn to lock, open the adjacent knob slowly until the gauge reaches the target, close the knob, release and remove the key, and replace the cap. For an integral lever or knob, open slowly, watch the gauge, close at the target and confirm it has fully returned, because a lever left a fraction open will slowly raise the system to 3 bar over the following week and the PRV will discharge. Where the integral valve does not fully close, the boiler needs a Gas Safe engineer to replace the filling valve; the symptom is a system that keeps rising in pressure rather than losing it (see boiler pressure too high).
When the pressure is too high
Overfilling is as common as underfilling, especially after a customer has topped up "to be safe". Above about 2.0 bar cold, reduce it. Do not use the PRV; it is a safety device, not a drain, and once lifted it tends to weep. Instead:
- Attach a bleed key and a container (or a short hose into a bucket) to a radiator bleed valve, open it and let water out until the gauge drops to 1.0–1.5 bar
- Alternatively use a drain-off cock on the lowest point of the system with a hose to outside
- Re-check after the system has run hot and cooled
If the pressure keeps rising with the loop closed and disconnected, the water is coming from somewhere: a passing integral filling valve, a pinholed plate heat exchanger on a combi letting mains into the primary circuit, or a passing cold-mains top-up valve on a system boiler. All of those are repairs, not adjustments.
Water Regulations: backflow and temporary connections
Heating water containing inhibitor is fluid category 3 under BS EN 1717 and Schedule 2 of the Water Supply (Water Fittings) Regulations 1999. Any connection between it and the wholesome cold mains must be protected against backflow by at least a double check valve to BS EN 13959. The flexible loop meets this provided the check valve is present and working; the Regulations and WRAS guidance treat the braided hose as a temporary connection that should be removed after use, which is why the loop is supplied with caps. In practice many installers leave it connected, and most water companies do not enforce the point on domestic boilers, but the correct position for a professional is to disconnect it and to tell the customer why. An old loop with no check valve, or a home-made length of hose and two taps, is non-compliant and should be replaced with a WRAS-approved filling loop kit (£15–£30).
Topping up is not a repair
A sealed system loses almost no water in normal service. If the customer is topping up monthly, the system has a fault and each top-up makes it worse by diluting the inhibitor and introducing oxygen. On any repressurising visit:
- Ask how often and by how much the pressure drops
- Look outside at the PRV discharge pipe for a drip or a tide mark; a weeping PRV is the most common hidden loss
- Check the expansion vessel: with the system pressure at zero, the Schrader valve on the vessel should hold 0.75–1.0 bar of air; water from the Schrader means the diaphragm has failed
- Look at radiator valve glands, compression joints, the automatic air vent and the condensate trap area for staining
- Test the inhibitor concentration and dose to the manufacturer's level under BS 7593:2019
- Quote the fix: expansion vessel recharge £60–£90; vessel replacement £150–£300 fitted; PRV replacement £90–£180; leak detection and repair from £150 (see boiler repair pricing guide)
Leaving a customer with a loop they can operate is good practice; leaving them to do it every fortnight for a year is not.
Frequently Asked Questions
Can a customer repressurise the boiler themselves?
Yes. Operating the filling loop and bleeding a radiator are not gas work and most manufacturers' user instructions describe the procedure. Show the customer the loop, the gauge and the target range, tell them to do it cold and slowly, and tell them to call if they need to do it more than twice a year or if the pressure ever reaches the red zone. Do not show them how to use an internal filling key if the manufacturer's instructions reserve it for the installer.
What pressure should the boiler be when it is running?
Hot, the gauge normally reads 0.3–0.7 bar above the cold figure, so 1.5–2.0 bar is typical. The expansion vessel is doing its job if the pressure returns to the cold figure when the system cools. A hot reading of 2.5 bar or more, or a PRV discharge when hot, points to a flat or failed expansion vessel rather than to overfilling.
Is it safe to leave the filling loop connected?
It is common but not strictly compliant. The Water Supply (Water Fittings) Regulations 1999 treat the flexible hose as a temporary connection to be removed after use; the double check valve provides the backflow protection while it is connected. Best practice is to close both valves, disconnect the hose and cap the tees. If it is left connected, both valves must be closed, because a loop left cracked open will raise the system pressure until the PRV lifts.
The pressure drops in winter but not in summer. Why?
A system that only loses pressure when the heating runs is usually losing water through the PRV when the hot expansion pushes it to 3 bar because the expansion vessel has lost its charge, or through a joint that only opens up when the pipework is hot and moving. In summer the system sits cold at a steady pressure and the fault is dormant. Test the vessel charge first.
Does repressurising fix a boiler that keeps locking out on low pressure?
Only if the cause was a one-off, such as bleeding radiators after decorating or a radiator removal. If the lockout recurs within weeks, the system is leaking or the PRV is passing, and the fix is the leak, the PRV or the expansion vessel. Repeated lockouts also put the pump and heat exchanger at risk from running with air in the system.
Regulations & Standards
Water Supply (Water Fittings) Regulations 1999 — Schedule 2 backflow protection; filling loops as temporary connections with a double check valve; applies in England and Wales (Scotland: Water Byelaws 2014)
BS EN 1717:2000 — protection against pollution of potable water; fluid category 3 classification of inhibited heating water
BS EN 13959:2004 — anti-pollution check valves (the double check valve in a filling loop)
BS 7593:2019 — code of practice for the preparation, commissioning and maintenance of domestic central heating and cooling water systems; annual inhibitor check and re-dosing
BS EN 12828:2012+A1:2014 — heating systems in buildings: design for water-based heating systems, including sealed system pressure and expansion provision
BS EN 13831:2007 — closed expansion vessels with built-in diaphragm for installation in water systems
Gas Safety (Installation and Use) Regulations 1998 — any work behind the boiler case, including replacement of an internal filling valve or PRV, is for a Gas Safe registered engineer
Building Regulations 2010, Approved Document L (England) and the Domestic Building Services Compliance Guide — commissioning requirements for heating systems, including the Benchmark checklist recording system pressure at commissioning
Manufacturer's installation and user instructions — the governing document for cold-fill pressure, expansion vessel charge and the filling device sequence on any specific boiler
WRAS — Water Regulations Approval Scheme — guidance on filling loops, temporary connections and backflow protection
legislation.gov.uk — Water Supply (Water Fittings) Regulations 1999 — Schedule 2 backflow requirements
Gas Safe Register — what is and is not gas work on a boiler
Heating and Hotwater Industry Council (HHIC) — Benchmark — commissioning checklist including system pressure
HSE — Gas safety — statutory guidance on domestic gas appliances
BSI Knowledge — BS 7593:2019 — water treatment and maintenance of domestic heating systems
boiler loses pressure repeatedly — why a fix did not hold and how to break the top-up cycle
boiler losing pressure — one-off pressure loss diagnosis: leaks, PRV, filling loop
system pressure and expansion vessels — vessel sizing, pre-charge and testing
boiler pressure too high — when the pressure keeps rising instead of falling
boiler pressure relief valve discharging — the PRV that will not stop dripping
bleeding radiators procedure — removing the air you introduced when filling
system cleansing inhibitors — restoring inhibitor concentration after repeated top-ups
leak detection — finding the water that keeps disappearing