Summary
Sealed (combi and system-boiler) central heating depends on three pressure-related components working together: the filling loop (which lets you add water to set the cold pressure), the expansion vessel (which absorbs the volume change as water heats), and the pressure relief valve (which dumps water at 3 bar to prevent overpressure damage). When all three are healthy, the system pressure sits at 1.0–1.5 bar cold and 1.8–2.5 bar hot, year after year, with no customer intervention.
When something goes wrong, the symptoms are recognisable but the diagnosis often goes wrong because plumbers reach for the easy answer (top up the pressure, or replace the boiler) rather than systematically test. A 30-minute diagnosis using a pressure gauge and tyre pressure gauge can identify the specific fault and avoid a £200 boiler service that doesn't address the root cause.
This article covers the physics in plain terms, the standard pressure-fault diagnostic sequence, the expansion vessel test procedure, the cure for each common fault, and the typical costs of repair vs replacement. The focus is sealed systems; vented (cold tank in loft) systems work differently and have their own troubleshooting flow not covered here.
Key Facts
- Sealed system pressure range — 1.0–1.5 bar cold, 1.8–2.5 bar hot (when fully warmed)
- Pressure relief valve setpoint — 3.0 bar standard for domestic systems (BS EN 1488 / BS 6283)
- Boiler manufacturer pressure spec — Check the boiler's installation manual; some specify tighter range (e.g. 1.0–1.5 bar cold, 2.0–2.5 bar hot)
- Expansion vessel function — Absorbs thermal expansion of the water (~4% volume increase between cold and hot)
- Expansion vessel pre-charge — Air or nitrogen charge in the vessel, set to the system's cold static head + 0.3 bar; typically 1.0–1.2 bar for a domestic system
- Vessel sizing rule of thumb — Total system volume × 0.07 (litres of vessel per litre of system); a typical 10-radiator domestic system needs ~12 litre vessel
- Standard combi vessel size — 6–8 litres integrated in the boiler (often inadequate for systems with >10 radiators)
- Auxiliary expansion vessel — Fitted externally when the boiler's integrated vessel is undersized; common after extension/rad addition
- Common manufacturer brands — Reflex, Zilmet, Pneumatex, Flomasta (UK availability)
- Diaphragm material — EPDM rubber; lifetime 8–15 years depending on chemical exposure (no kitchen-grade silicone — degrades)
- Filling loop standards — Type CA backflow protection per Water Regs (Schedule 2 paragraph 15); detachable loop (Type AUK1) is the standard UK retail product
- PRV discharge pipe — Must discharge to a safe visible location per Approved Document G; metallic pipe to outside or to a tundish
- System fill water — Should ideally be inhibited per BS 7593:2019 (Code of practice for the preparation, commissioning and maintenance of domestic central heating systems)
- System pressure gauge — Built into combi/system boiler; analog or digital readout
Quick Reference Table
Quoting a heating job? squote turns a 2-minute voice recording into a professional quote.
Try squote free →| Symptom | Likely Cause | Diagnostic |
|---|---|---|
| Pressure low (<1 bar) at all times | System leak (or recently topped up and not fully bled) | Visual inspection + air bleed + monitor over days |
| Pressure jumps high (>2.5 bar) when heating fires | Expansion vessel diaphragm failed | Vessel charge test; replace vessel or recharge |
| Pressure rises very high (>3 bar) — PRV discharges | Expansion vessel failed OR PRV faulty | Vessel test + PRV test |
| Pressure swings between 0.5 and 2.5 bar | Vessel pre-charge low or vessel undersized | Check vessel pre-charge; size against system volume |
| PRV drips continuously | PRV faulty seat or vessel issue causing overpressure | Replace PRV + check vessel |
| Pressure drops slowly over weeks | Small leak somewhere — radiator, pipe joint, AAV | Sniff test, inspect joints, check loft for damp |
| Pressure rises when not heating | Filling loop left open (common DIY error) | Close filling loop; drain to correct pressure |
| Vessel Charge Test | Reading | Conclusion |
|---|---|---|
| Pre-charge = 1.0 bar (cold) | Correct for typical domestic | OK |
| Pre-charge = 0 bar (cold) | Diaphragm failed OR all air leaked out | Recharge OR replace |
| Pre-charge = 0.3 bar | Significant loss; partial diaphragm leak | Recharge; monitor; likely full replacement soon |
| Pre-charge correct but system pressure spikes | Vessel undersized for the system | Add auxiliary vessel |
| Pre-charge correct, system stable | OK | No action |
| Component | Cost (Trade) | Cost (Customer S&F) |
|---|---|---|
| New 8L vessel | £25–£45 | £100–£200 |
| New 12L vessel | £35–£65 | £140–£280 |
| New 18L vessel | £55–£95 | £180–£320 |
| Replace integrated boiler vessel | £45–£90 (part) | £200–£450 (in-boiler labour) |
| Recharge vessel pre-charge (no replacement) | £8–£15 (Schrader valve gas) | £80–£150 (labour) |
| Pressure Relief Valve (PRV) replacement | £15–£35 (valve) | £80–£200 |
| Filling loop replacement | £25–£60 | £100–£250 |
| Combined service: vessel + PRV + filling loop | £50–£120 (parts) | £350–£600 |
Detailed Guidance
Diagnostic Sequence
When a customer reports "pressure keeps dropping" or "PRV is dripping" or "boiler is losing pressure":
- Cold pressure reading. Switch heating off, allow system to cool fully (1–2 hours). Read pressure gauge. Should be 1.0–1.5 bar. Note reading.
- Heat the system up. Bring to full operating temperature (radiators all hot, return on boiler at 50–60°C). Read pressure. Should be 1.8–2.5 bar.
- Calculate the swing. Difference between cold and hot. Normal is 0.5–1.0 bar; >1.5 bar swing suggests vessel issue.
- Cool the system back down. Pressure should return to cold reading. If pressure does NOT return to cold reading, there may be air absorbed into water or a vessel charging issue.
- Test the expansion vessel. Drain to 0 bar at boiler (close isolators first), test vessel charge with a tyre pressure gauge on the vessel's Schrader valve. Compare to expected (1.0–1.2 bar for standard domestic).
- Test the PRV. With normal system pressure, lift the manual lever momentarily — should discharge water then seal back. If continuously drips after lifting, replace.
- Leak check. Visual inspection of all visible pipework, joints, radiator valves, pump connections. Pay attention to under-floor runs and loft pipework.
Expansion Vessel — The Critical Component
The expansion vessel is a steel cylinder with a rubber diaphragm dividing it into two chambers: one connected to the system (water side), the other pre-charged with air or nitrogen (gas side). As the water heats and expands, the diaphragm moves into the gas side, compressing the air; this absorbs the volume change without significant pressure rise.
When the diaphragm fails, the gas escapes into the water side (lost to the air bleed at radiators) and the vessel is full of water. There is now no buffer for thermal expansion — system pressure rises rapidly when heating fires, often triggering the PRV.
Testing the vessel charge:
- Isolate the system from the vessel (close any valve on the vessel branch; if none, isolate the boiler)
- Drain the system to 0 bar at a low-point drain
- The vessel water side now has no system pressure; only the pre-charge gas remains
- Push the Schrader valve cap aside; apply a tyre pressure gauge to the valve stem
- Read the pre-charge pressure
Result interpretation:
- Reading near nominal (1.0–1.2 bar): vessel is OK; the symptom is something else
- Reading significantly low (0.3–0.7 bar): pre-charge has slowly leaked; recharge with a foot pump (or replace if old)
- Reading zero: diaphragm has failed or all gas has leaked; recharge and test; if it leaks again within 24 hours, replace vessel
Recharging:
- Drain system as above
- Pump air into Schrader valve with a foot pump (or use a compressed gas cylinder for accuracy)
- Set to nominal pre-charge (1.0–1.2 bar typical)
- Refill system to 1.2 bar cold
- Heat and observe
Pressure Relief Valve
The PRV (also called safety valve, overflow valve) discharges at 3.0 bar to protect the system from overpressure damage. It is set at the factory and cannot normally be adjusted in the field.
PRV failures:
- Continuous drip from PRV discharge — Either seat is dirty/scored, or the vessel is causing repeated overpressure
- No discharge at lift test — Stuck closed; replace (potentially dangerous if system overpressures)
- PRV opens at normal pressure — Setpoint changed (gunged, damaged); replace
Replacement is straightforward: drain system to 0 bar, unscrew old PRV, screw in new one (PTFE on threads), refill. Cost £15–£35 part, 1–2 hours labour.
Filling Loop
The filling loop is the flexible braided hose that connects the mains cold supply to the heating system, with two isolation valves and (in newer designs) a check valve to prevent backflow.
Common issues:
- Filling loop left open after top-up — System pressure continues to rise; PRV may discharge. Always close both valves after topping up.
- Filling loop check valve failed — Backflow into mains potential; replace whole loop assembly
- Filling loop hose perished — Visible cracks; replace as a unit
Filling loop replacement is a Water Regs notifiable change (different from sister regulation but is a backflow-prevention device); check WRAS for the specific filling loop product compliance.
System Top-Up Procedure
For a customer or trade top-up:
- Confirm cold (system off, no recent operation)
- Confirm where the filling loop is and how to open/close the valves
- Slowly open the filling loop valves
- Watch the gauge rise to 1.2 bar
- Close both valves
- Bleed any high points (radiator at the top of the run, towel rail in the bathroom)
- Top up again to 1.2 bar
- Confirm cold reading stable
- Heat system; check hot reading is within 2.5 bar
- Cool back; confirm cold reading returns to ~1.2 bar
If the system needs topping up more than once a year, there is a leak somewhere — investigate before another top-up.
Common Misdiagnoses
- "The boiler is broken" when it's a vessel. A combi that won't fire because pressure is too high is being asked to protect itself from the vessel fault, not failing in itself. Fix the vessel, not the boiler.
- "The boiler needs replacing" when it's a PRV. A continuous PRV drip looks like a boiler problem to the customer; usually a £150 fix, not a £2,500 fix.
- "Pressure is fine" when the vessel pre-charge is wrong. Pressure swing between cold and hot tells you. A 1.5 bar swing is excessive; a 0.5 bar swing is healthy.
- "It's leaking somewhere" when the vessel is full of water. A vessel that's lost its charge looks like a leak — system pressure drops because thermal expansion now goes somewhere else (PRV discharge, slow loss). The leak is "inside the vessel" not in pipework.
Worked Example: Vessel Diagnosis and Replacement
Job: Customer reports boiler "keeps cutting out" and they have to top up the pressure weekly. Visit.
Tests:
- Cold pressure 0.5 bar (below normal)
- After 30 min heating, pressure 2.8 bar (PRV almost discharging)
- Stop, cool, drain to 0
- Vessel pre-charge reading: 0 bar
- Vessel diagnosis: diaphragm failed, vessel waterlogged
Repair: replace integrated 8L vessel (or fit auxiliary vessel external to boiler, depending on access).
| Item | Cost |
|---|---|
| Replacement 8L vessel + bracket + connector | £55 |
| 22mm copper tee, fittings, washers | £25 |
| Inhibitor (BS 7593) for system refill | £25 |
| Spirit level, sealant, tape | £8 |
| Materials subtotal | £113 |
| Labour 2.5 hours @ £55/hr | £138 |
| System drain + refill + bleed | £40 |
| Test, commission, hand-over | £35 |
| Labour subtotal | £213 |
| Subtotal | £326 |
| Markup 20% | £65 |
| Net price | £391 |
| VAT 20% (if registered) | £78 |
| Customer price (VAT-reg) | £469 |
In real markets this is the typical "boiler losing pressure" service call. A new boiler quote at £2,500 would be wrong unless the boiler is genuinely old and other components are also failing.
Frequently Asked Questions
What's the correct cold pressure for my heating system?
Typically 1.0–1.5 bar. Specifically, the boiler manufacturer's installation manual specifies the range — check the brand and model. Higher cold pressure means higher hot pressure (potentially over the PRV setpoint); lower cold pressure means low system head and potential pump cavitation.
How do I know if my expansion vessel has failed?
Three signs: (1) system pressure rises sharply when heating fires and drops back when cool; (2) PRV discharges water periodically; (3) pre-charge test reads zero. The pre-charge test is definitive — drain the system, apply a tyre pressure gauge to the Schrader valve, read.
How often should I top up my system pressure?
Once or twice a year is acceptable as routine; more than that suggests a leak or vessel issue. Investigate, don't just keep topping up. If you're topping up every week the system has either a small leak or a failed vessel; both need professional diagnosis.
Can I recharge an expansion vessel myself, or do I need a plumber?
Technically possible — drain system, recharge vessel with a foot pump to 1.2 bar, refill system. Practically, most homeowners don't have the gauge, the foot pump with correct fitting, and the confidence to drain and refill correctly. £80–£150 to have a plumber do it is usually money well spent.
What does it mean when the PRV is dripping?
System pressure has exceeded 3.0 bar at some point and discharged through the PRV. Once a PRV has discharged, the seat sometimes doesn't re-seal cleanly and a slow drip continues. The underlying cause is usually a failed expansion vessel; fix that and then either replace the PRV (recommended) or test if it re-seals.
Regulations & Standards
BS EN 12828:2003 — Design of water-based heating systems
BS EN 12831:2003 — Heating systems in buildings — calculation of design heat load
BS EN 1488:2000 — Building valves — expansion valves
BS 6283 — Safety devices for use in hot water systems (PRV reference)
BS 7593:2019 — Code of practice for preparation, commissioning, operation and maintenance of domestic central heating and cooling systems
Water Supply (Water Fittings) Regulations 1999 — Backflow protection on filling loops (Schedule 2 paragraph 15)
Approved Document G — Building Regulations Part G (hot water safety; PRV discharge requirements)
Approved Document L — Building Regulations Part L (energy efficiency; system pressure and commissioning)
Boiler Plus regulations 2018 — Combi-boiler controls; weather/load compensation, smart controls
BS 7593:2019 on BSI — Central heating commissioning standard
Worcester Bosch technical guide — Manufacturer technical resources
Vaillant technical guide — Major UK boiler manufacturer
Reflex Winkelmann (expansion vessels) — Major European vessel manufacturer
boiler selection — Boiler selection and sizing
heating controls — Controls and Boiler Plus
powerflush — System cleaning as related maintenance
vaillant — Boiler-specific pressure fault codes