Boiler Pressure Too High: PRV Operation, Expansion Vessel Fault & How to Reduce

Quick Answer: Sealed central heating systems should operate at 1.0–1.5 bar cold (no heating running) and rise to 1.5–2.5 bar when hot — check manufacturer instructions. Pressure above 2.5 bar hot (or consistently above 2 bar cold) indicates a fault. The most common cause is an under-pressurised or failed expansion vessel. The pressure relief valve (PRV) will discharge water if pressure reaches its set point (usually 3 bar) — repeated PRV discharge is a fault, not normal operation.

Summary

Boiler overpressure is the opposite problem from losing pressure, but both symptoms point to the same component: the expansion vessel. In a sealed central heating system, water expands as it heats up — a closed system has nowhere for that extra volume to go unless an expansion vessel (a membrane-type pressure vessel) absorbs it.

When the expansion vessel fails (most commonly because the pre-charge pressure is too low, or the membrane ruptures), the system pressure rises sharply when heating runs. If pressure reaches the PRV set point (typically 3 bar), the PRV opens and discharges water from the system. After the system cools, pressure drops — and customers often re-pressurise from the filling loop, making the problem worse over time.

Understanding this cycle is essential: a customer who fills up to 1 bar every month and doesn't know why, or whose PRV keeps weeping, has an expansion vessel problem until proven otherwise.

Key Facts

Quick Reference Table

Need to quote a plumbing job? squote generates accurate quotes from a voice recording.

Try squote free →
Pressure Reading Situation Likely Cause
0–0.5 bar cold Too low Leak, over-discharge from PRV, air in system
1.0–1.5 bar cold Normal
2.0+ bar cold Too high Over-pressurised filling, failed expansion vessel
2.5–3.0 bar hot High Expansion vessel under-charged or failed
3.0+ bar PRV opens System fault — do not ignore
Test Method Result
Expansion vessel membrane Depress Schrader valve Air = OK; water = membrane failed
Expansion vessel pre-charge Depress Schrader valve with system fully depressurised Should read 1.0 bar (or calculated for system height)
PRV operation Check for weeping or discharge staining Any discharge is abnormal — investigate

Detailed Guidance

Diagnosing an Overpressure Fault

Step 1: Record pressures carefully.

Step 2: Check for PRV discharge.

Step 3: Test the expansion vessel.

Step 4: Check and re-pressurise the vessel (if membrane intact).

Step 5: Replace vessel if membrane is ruptured.

PRV Replacement

If the PRV has been repeatedly opening, it may no longer reseat cleanly. The PRV is a safety device — a PRV that weeps continuously reduces system pressure slightly over time and eventually the system loses water. A weeping PRV must be replaced.

PRV replacement procedure:

  1. Isolate and drain the system to below the PRV level
  2. Unscrew the PRV (3/4" BSP thread is standard for most domestic boilers)
  3. Fit new PRV of the same pressure rating (typically 3 bar; confirm on the original)
  4. PTFE tape or hemp on threads; hand tighten plus 1.5 turns with wrench; do not overtighten
  5. Ensure discharge pipe is reconnected and terminates safely

Never increase the PRV set pressure to prevent discharge — this is dangerous. If the system pressure exceeds the PRV rating, the PRV is the last line of defence against catastrophic failure.

Expansion Vessel Sizing

If replacing or adding an expansion vessel to a system, correct sizing is important. Undersized vessels lead to overpressure recurrence.

Simplified sizing method:

  1. Estimate system water volume: boiler manual specifies vessel size for typical system; or calculate from radiator outputs (typically 12–15 litres per kW of boiler output for a fully loaded system)
  2. Use expansion vessel sizing charts or online calculators
  3. For a typical domestic system (15kW, 10 radiators): expansion vessel of 12–18 litres
  4. For large systems or underfloor heating (more water volume): 18–35 litres

The vessel must be installed on the cold side of the heat source (before the pump and boiler, on the return), in an accessible location for future servicing.

Overpressure Due to Filling Loop Left Connected

A common cause of persistent overpressure in combi boilers is a filling loop left connected or partially open. Mains water pressure (typically 2–5 bar) can bypass through a worn filling loop valve into the system, which is at lower pressure — forcing system pressure up continuously.

Check: Is the flexible filling loop connected at both ends? Both valves should be fully closed when not in use, and the flexible hose disconnected entirely if a permanent filling connection is used (Worcestershire Heat Systems and others now require Combi-Fill or FlexFill-type permanent filling connections with double-check valve).

Documenting and Advising the Customer

After repair:

Frequently Asked Questions

Can I reduce boiler pressure by bleeding radiators?

Yes — opening bleed valves releases air and some water, reducing system pressure temporarily. But this does not fix the underlying fault. If pressure is consistently too high when cold, bleeding will only provide temporary relief. Find and fix the root cause (expansion vessel).

My customer's PRV is weeping slightly — is this an emergency?

Not immediately — but it is a fault that must be repaired. A weeping PRV will eventually result in the system losing water and low pressure, and the PRV seat may deteriorate further, leading to full discharge. Schedule repair promptly. In the interim, check the pressure regularly.

How often should the expansion vessel pre-charge be checked?

At every boiler service. It takes 30 seconds to check with the Schrader valve once the system is depressurised, and finding a low pre-charge before it causes repeated PRV discharge saves a callout.

Regulations & Standards