Summary
Supplementary bonding was once the signature of a bathroom installation: green-and-yellow 4 mm² looped from the bath taps to the radiator to the basin pipes to the towel rail. Since the 17th Edition (BS 7671:2008) it has been permissible to leave it out in most new bathrooms, and the 18th Edition and its four amendments have kept that position. The result is two decades of confusion on site. Some electricians still bond everything; some bond nothing; many customers have been told by one tradesperson that the bonding "must be ripped out" and by the next that its absence is a fail. Both are wrong unless the conditions have actually been checked.
The logic of the regulation is simple. Supplementary bonding exists to limit the touch voltage between two pieces of metal a person might hold at the same time while wet, during the time it takes a protective device to clear a fault. If every circuit in the room will disconnect fast, every circuit has a 30 mA RCD to catch a fault before it reaches a dangerous level, and every piece of extraneous metal is already tied to the main earthing terminal by the main bonding, then the extra local bonding adds nothing. If any one of those protections is missing, it does. The decision is therefore a test and a check of the installation, not an opinion, and it has to be made room by room.
This article explains the three conditions and how to verify each, how to decide which metalwork is actually extraneous (plastic plumbing has changed the answer in most modern bathrooms), the conductor sizes and resistance test when bonding is required, what to do with existing bonding, and how to code the findings on a condition report. For the broader earthing and bonding picture see earthing and bonding; for the zones and equipment rules in the same room see bathroom zones and ip ratings.
Key Facts
- The regulation — BS 7671:2018+A4:2026 Regulation 701.415.2, supplementary protective equipotential bonding in locations containing a bath or shower; unchanged in substance since BS 7671:2008.
- Condition 1: disconnection times — all final circuits in the location comply with Regulation 411.3.2: 0.4 s for final circuits up to 63 A (32 A for socket outlets and mobile equipment in some cases) on a TN system, 0.2 s on a TT system, 5 s for distribution circuits. Verified by measured Zs against the maximum Zs for the protective device (Tables 41.2 to 41.4) or by an RCD.
- Condition 2: 30 mA RCD on every circuit — all final circuits of the location have additional protection by an RCD with a rated residual operating current not exceeding 30 mA (Regulation 415.1). Not just the shower; the lighting, the fan, the shaver socket's supply, the towel rail, the underfloor heating, the mirror, and any socket circuit that passes through the room.
- Condition 3: main bonding in place — all extraneous-conductive-parts in the location are effectively connected to the protective equipotential bonding under Regulation 411.3.1.2: the incoming metallic water, gas, oil and other services and metallic structural parts are main-bonded at the main earthing terminal with the correct conductor size (10 mm² minimum on a PME supply, 6 mm² or half the earthing conductor otherwise).
- All three, not two — omission is permitted only when all three are met. An RCD-protected bathroom in a house with no main bonding to the water still requires supplementary bonding (and the missing main bonding is a C2 in its own right).
- Extraneous-conductive-part — a conductive part liable to introduce a potential, generally earth potential, that is not part of the electrical installation: metal pipes entering the room from outside the equipotential zone, metal structural steel, metal baths and trays that are connected to earth via their waste or supply. A metal part is treated as extraneous if its resistance to the main earthing terminal is below about 22 kΩ (IET Guidance Note 8); above that it cannot introduce a dangerous potential.
- Not extraneous — metal taps, towel rails and radiators fed entirely by plastic pipe with no other connection to earth; metal window frames and door architraves not connected to structural steel; a metal bath on plastic supplies and plastic waste; isolated metal accessories. Verify with the resistance test rather than assume.
- Exposed-conductive-part — metalwork of Class I electrical equipment in the room: an electric shower, a towel rail, a fan, a Class I light fitting. These are earthed through their CPC, which is why the bonding connects to the CPC terminals of each circuit.
- Conductor size (Regulation 544.2) — between two exposed-conductive-parts: not less than the smaller of the two CPCs; between an exposed and an extraneous part: not less than half the CPC of the circuit; between two extraneous parts: 2.5 mm² copper if mechanically protected (sheathed cable or in conduit), 4 mm² if not. In practice 4 mm² single-core green-and-yellow is used throughout.
- Resistance test (Regulation 415.2.2) — the resistance R between simultaneously accessible exposed and extraneous parts must satisfy R ≤ 50 V ÷ Ia, where Ia is the operating current of the protective device: for a 30 mA RCD, 50 ÷ 0.03 = 1,667 Ω; for a 32 A Type B MCB with 0.4 s disconnection, Ia = 160 A so R ≤ 0.31 Ω; for a 6 A Type B, Ia = 30 A so R ≤ 1.67 Ω. A measured value of a few hundredths of an ohm on a direct bonding conductor comfortably passes.
- Bonding clamps — to BS 951, with the "Safety Electrical Connection — Do Not Remove" label, on clean bare metal, accessible for inspection; not on painted pipe without cleaning back, not on compression nuts.
- Where the bonding runs — it does not have to be visible; it can run under the bath, behind the panel or in the floor void, but the connections must be accessible. The bonding may be made at a single accessible point (for example a bonding terminal block under the bath) with each part connected to it.
- Using the pipework as the conductor — a continuous run of metal pipe may form part of the bonding path, but soldered joints, compression fittings and particularly push-fit plastic fittings in the run break it; test the actual resistance end to end.
- Existing bonding — where the three conditions are now met (for example after a consumer unit change to all-RCBO), existing supplementary bonding may be left in place; it is not a defect and removing it is unnecessary work. It should not be removed where the conditions are not met.
- EICR coding — absence of supplementary bonding where required (conditions for omission not met): C2 under Electrical Safety First Best Practice Guide 4. Absence of 30 mA RCD protection for circuits in the bathroom: C2. Absence of main bonding to a metallic service: C2.
- Part P — installing or extending supplementary bonding is not notifiable in England; in Wales, work in a bathroom beyond like-for-like replacement remains notifiable. Scotland and Northern Ireland have their own regimes.
- Cost — testing and verifying the three conditions during an EICR is part of the inspection; installing supplementary bonding to a typical bathroom (four or five parts, bath panel off, floorboard lifted): 1.5–3 hours, £120–£250 including BS 951 clamps and 4 mm² cable; where the real fix is adding RCD protection, an RCBO per circuit or a consumer unit change is the better spend.
Quick Reference Table
Quoting an electrical job? Describe the work and squote handles the pricing.
Try squote free →| Situation found in the bathroom | Condition 1 (disconnection) | Condition 2 (30 mA RCD all circuits) | Condition 3 (main bonding) | Supplementary bonding |
|---|---|---|---|---|
| Modern all-RCBO board, main bonding present, plastic plumbing | Met | Met | Met (or no extraneous parts) | Not required |
| Dual-RCD board, all bathroom circuits on RCD sides, main bonding OK | Met | Met | Met | Not required |
| Shower on RCD, lighting on non-RCD side of split board | Met | NOT met | Met | Required |
| Old rewireable fuse board, no RCD | Likely met for MCB/fuse Zs | NOT met | Check | Required |
| TT supply, all circuits RCD-protected, main bonding OK | Met (0.2 s via RCD) | Met | Met | Not required |
| No main bonding to incoming metal water pipe | — | — | NOT met | Required, and main bonding is a C2 |
| Zs too high on lighting circuit (Type B 6 A, no RCD) | NOT met | NOT met | — | Required; also fix the circuit |
| All conditions met, old bonding still fitted | Met | Met | Met | May remain; not a defect |
| Metal bath on copper supply and metal waste, all RCD, main bonding OK | Met | Met | Met | Not required (bath is extraneous but main-bonded path exists) |
| Towel rail on plastic pipe, no electrical connection | — | — | — | Not extraneous; no bonding needed to it |
| Electric shower (Class I) and metal radiator on copper from boiler | Met | Met | Met | Not required; both already earthed/bonded |
Detailed Guidance
Why the regulation allows omission
A fault on a Class I appliance in the bathroom, say a shower with a line-to-earth fault, raises the shower casing and its CPC to some fraction of the supply voltage until the protective device clears the fault. The person standing in the tray touching the shower and the metal tap could be exposed to the difference between the shower CPC potential and the tap's potential. Supplementary bonding pulls those two potentials together locally, so even during the fault the voltage between them is small. The three conditions remove the need for that: fast disconnection (Condition 1) limits the duration; a 30 mA RCD (Condition 2) disconnects at a current far too small to raise the CPC potential significantly and protects against the worst case of a person forming part of the fault path; and main bonding (Condition 3) keeps the extraneous metal at earth potential in the first place. Remove any one and the risk the bonding was designed for comes back.
Verifying Condition 1: disconnection times
For each final circuit that serves or passes through the room, confirm the protective device will disconnect within 0.4 s (TN) or 0.2 s (TT) under an earth fault. Where the circuit has a 30 mA RCD, the RCD itself provides the disconnection time (an RCD to BS EN 61008 or 61009 trips within 300 ms at IΔn and 40 ms at 5 IΔn) and Condition 1 is satisfied through the RCD. Where a circuit relies on the MCB or fuse alone, measure Zs at the furthest point and compare it with the maximum Zs for that device in Tables 41.2 to 41.4 of BS 7671, applying the 0.8 correction factor for conductor temperature if comparing against the tabulated values measured cold (GN3 gives the corrected figures). A circuit that fails its Zs fails Condition 1 regardless of anything else, and is a defect in its own right. See maximum zs values and testing.
Verifying Condition 2: 30 mA RCD on every circuit
List every circuit in the room, not just the obvious ones. Typical candidates: electric shower, lighting (which may be a landing or whole-floor circuit), extract fan (often off the lighting circuit, sometimes its own), shaver supply unit (fed from the lighting circuit), electric towel rail or radiator (socket circuit via an FCU, or its own circuit), electric underfloor heating, heated mirror or demister pad, bathroom cabinet with lighting, any socket outlet circuit whose cables pass through the room even if there are no sockets in it, and SELV transformers for LED lighting (the 230 V primary circuit counts). Each must be protected by a 30 mA RCD or RCBO. Test the RCD at IΔn and 5 IΔn and record the trip times. A circuit protected by a 100 mA RCD, or by a 30 mA RCD fitted downstream only to the shower but not to the lights, does not satisfy Condition 2 for the room.
Verifying Condition 3: main bonding
Check at the main earthing terminal that the incoming metallic water service, gas service, oil line and any other extraneous service and structural steel are main-bonded with conductors of the correct size (10 mm² minimum on a TN-C-S/PME supply under Regulation 544.1.1; otherwise not less than half the earthing conductor with a 6 mm² minimum), connected within 600 mm of the meter or point of entry on the consumer's side, with BS 951 clamps and labels. Test continuity from the MET to each bonded service. Where the incoming water and gas are plastic there may be no extraneous services to bond, and Condition 3 is met because there are no extraneous-conductive-parts to connect; record that finding. Where a metal service enters the building and is not bonded, Condition 3 fails: supplementary bonding is required in the bathroom and the missing main bonding is coded C2 and must be fixed. See tncs earthing pme for the PME sizing rules.
Deciding what is extraneous in the room
Modern plumbing has changed this part of the job. A bathroom plumbed in plastic push-fit with chrome tails at each fitting has metal taps and a metal towel rail that are electrically isolated from earth and from each other: they cannot introduce a potential and are not extraneous-conductive-parts. Bonding them achieves nothing and, in theory, introduces earth potential onto isolated metal.
Test rather than assume. With the installation isolated, measure the resistance between the metal part and the main earthing terminal (a long lead to the MET, or to a confirmed CPC at a local accessory, with a low-resistance ohmmeter on a high range or an insulation tester at a low voltage). IET Guidance Note 8 gives about 22 kΩ as the threshold: below it the part is treated as extraneous; above it, it is not. A copper pipe system fed from a copper rising main will read very low (it is extraneous, but it is also already connected to the main bonding, which is exactly what Condition 3 checks). A radiator on copper from a boiler elsewhere in the house is extraneous. A metal bath with a plastic waste and plastic supplies will usually read open. Metal window frames and door architraves are not treated as extraneous unless connected to the building's structural steel (Regulation 701.415.2 says so explicitly).
Installing supplementary bonding where it is required
- Identify every exposed-conductive-part (Class I equipment: shower, towel rail, fan, light fittings) and every extraneous-conductive-part (metal pipes to taps and radiators, metal waste pipes, metal bath or tray connected to earth, structural metal).
- Run 4 mm² single-core green-and-yellow (or 2.5 mm² where the conductor is sheathed or enclosed throughout) between the CPC terminal of each circuit (typically at the shower isolator, the fan, the light fitting or a junction box feeding them) and each extraneous part. A common method is a bonding terminal block under the bath or in the airing cupboard with each part connected to it, so there is one accessible point of inspection.
- Fix BS 951 clamps on cleaned bare metal, tightened so the conductor cannot pull out, each with the warning label. Where pipes are chromed or painted, clean a small section back to bare metal at the clamp position.
- Keep connections accessible: behind a removable bath panel, in an airing cupboard, at a cabinet, not plastered in.
- Test. Measure the resistance between each pair of simultaneously accessible exposed and extraneous parts with a low-resistance ohmmeter and confirm R ≤ 50 V ÷ Ia for the protective device of the circuit concerned. Record the values. Direct 4 mm² runs of a few metres read 0.01–0.05 Ω.
- Record on the certificate (EIC or Minor Works) that supplementary bonding has been installed and tested, and why (which of the three conditions is not met).
Do not rely on a run of copper pipe as the bonding conductor without testing it end to end; a single push-fit or pressed plastic-bodied fitting in the run breaks the path, and a soldered or compression joint can read high with age.
Existing bonding when the conditions are now met
A consumer unit upgrade to an all-RCBO board very often satisfies Condition 2 for the first time in a 1980s house, with Conditions 1 and 3 already met. The old supplementary bonding is now surplus, but it is not a defect and there is no requirement to remove it. The usual advice is to leave it in place unless it is damaged, incorrectly connected or in the way of the work. Where it is removed during a refurbishment and the conditions are confirmed met, record on the certificate that supplementary bonding is not required under Regulation 701.415.2 and state the verification done. If bonding is found connected to a non-extraneous part (an isolated towel rail on plastic pipe), it is harmless but unnecessary; it is not a code.
Coding on an EICR
Electrical Safety First Best Practice Guide 4 gives the agreed codes. No supplementary bonding in a bathroom where the conditions for omission are not met: C2. Bathroom circuits without 30 mA RCD protection: C2. Main bonding absent to an incoming metallic service: C2. Supplementary bonding present but of inadequate size or with a resistance exceeding the Regulation 415.2.2 limit: C2 where it is relied upon (conditions for omission not met), C3 or no code where it is surplus. Supplementary bonding to parts that are not extraneous: not a defect. Where the inspector cannot determine whether a part is extraneous or whether bonding exists behind finishes, a limitation is recorded and the item may be FI. See eicr codes c1 c2 c3 fi explained.
Frequently Asked Questions
My customer's new bathroom has all plastic pipes. Does anything need bonding?
If the taps, radiator and towel rail are fed entirely by plastic and nothing metallic in the room is connected to earth elsewhere, there are no extraneous-conductive-parts to bond and the question does not arise, whatever the state of the RCDs. Confirm it with the resistance test to the MET: an open reading above about 22 kΩ means the part is not extraneous. Class I equipment (shower, fan, towel rail) is earthed through its own CPC. The circuits in the room still need 30 mA RCD protection for their own sake under Regulation 701.411.3.3, but that is a separate requirement from bonding.
The shower is RCD protected but the lights are not. Is the bathroom compliant?
No, on two counts. Condition 2 requires every final circuit in the room to have 30 mA additional protection, so the bathroom does not qualify for omission of supplementary bonding and bonding is required. Separately, Regulation 701.411.3.3 requires 30 mA additional protection for all low-voltage circuits serving or passing through the location, so the unprotected lighting circuit is itself a C2 on a condition report. The practical fix is an RCBO on the lighting circuit, which resolves both.
Do I have to remove the old bonding now the board has RCBOs?
No. Once the three conditions are met the bonding is not required, but its presence is not a defect and nothing in BS 7671 asks for it to be removed. Leave it unless it is damaged or in the way. If it is removed as part of a refit, record on the certificate that the conditions of Regulation 701.415.2 were verified.
Is a metal bath an extraneous-conductive-part?
Only if it is connected to earth through something: a copper supply, a metal waste, or contact with structural metal. A pressed steel bath on copper hot and cold supplies and a copper waste reads low to the MET and is extraneous; it is also already connected to the main bonding through those pipes, so where Conditions 1 to 3 are met nothing more is needed. The same bath on plastic supplies and a plastic waste reads open and is not extraneous. Acrylic baths are not conductive at all, though their metal cradle may be if it touches pipework.
What size cable is supplementary bonding?
4 mm² copper where it is not mechanically protected (the usual single-core green-and-yellow clipped under a bath), 2.5 mm² where it is sheathed or in conduit throughout, for connections between extraneous parts. Between an exposed-conductive-part and an extraneous part, not less than half the CPC of the circuit; between two exposed parts, not less than the smaller CPC. In practice 4 mm² covers every case in a domestic bathroom and avoids the argument.
Regulations & Standards
BS 7671:2018+A4:2026, Regulation 701.415.2 — supplementary protective equipotential bonding in locations containing a bath or shower, and the three conditions for its omission.
BS 7671:2018+A4:2026, Regulation 701.411.3.3 — 30 mA additional protection for all low-voltage circuits of the location.
BS 7671:2018+A4:2026, Regulation 415.2 — supplementary protective equipotential bonding: requirements and the R ≤ 50 V ÷ Ia verification.
BS 7671:2018+A4:2026, Regulation 411.3.2 and Tables 41.1 to 41.4 — maximum disconnection times and maximum earth fault loop impedances.
BS 7671:2018+A4:2026, Regulation 411.3.1.2 and Section 544 — main protective bonding and the sizing of protective bonding conductors (544.1 main, 544.2 supplementary).
BS 951:2009 — Electrical earthing: clamps for earthing and bonding; specification.
IET Guidance Note 8: Earthing and Bonding (5th edition) — extraneous-conductive-part determination, the 22 kΩ guidance, bonding methods.
IET Guidance Note 7: Special Locations (6th edition) — bathrooms and shower rooms.
IET Guidance Note 3: Inspection and Testing (10th edition) — Zs verification, RCD testing, bonding continuity tests.
Electrical Safety First Best Practice Guide 4 — EICR classification codes for bonding and RCD omissions.
Building Regulations 2010, Approved Document P (2013 edition) — notifiability of electrical work in England; Welsh Government Approved Document P for Wales.
Electricity at Work Regulations 1989 — the duty to maintain systems to prevent danger.
IET — BS 7671 Wiring Regulations — current edition and amendments.
IET — Wiring Matters: Supplementary bonding in bathrooms — IET technical articles on Regulation 701.415.2.
Electrical Safety First — Best Practice Guide 4: Electrical installation condition reporting — coding of bonding defects.
Electrical Safety First — Best Practice Guide 1: Replacing a consumer unit — verifying bonding at a board change.
Approved Document P: Electrical safety in dwellings — GOV.UK — notifiable work in England.
NICEIC — Technical guidance on bathrooms and special locations — scheme guidance for registered contractors.
earthing and bonding — main bonding, earthing conductor sizes and the overall protective system.
bathroom zones and ip ratings — zones, IP ratings and equipment selection in the same room.
tncs earthing pme — PME supplies and the 10 mm² main bonding requirement.
rcd types explained — RCD and RCBO types that satisfy Condition 2.
maximum zs values and testing — verifying disconnection times for Condition 1.
eicr codes c1 c2 c3 fi explained — coding bonding and RCD findings.
electric shower installation — the Class I appliance most often at the centre of the question.
consumer unit upgrade — the board change that usually brings a bathroom within the omission conditions.