Summary
Earth fault loop impedance testing is one of the dead-and-live tests every electrician carries out to prove a circuit is safe. The loop impedance (Zs) is the total resistance of the path a fault current would take if a line conductor touched earth — out through the supply line, back through the earth path, and round to the source. If that path has too much impedance, fault current is too low to trip the protective device fast enough, and exposed metalwork can sit at a dangerous touch voltage long enough to kill.
The whole point of measuring Zs and comparing it to a maximum is automatic disconnection of supply (ADS) — the primary protective measure in BS 7671 for most installations. Get the loop impedance low enough and the MCB, RCBO or RCD operates inside the required disconnection time. This is core knowledge for anyone doing an EICR, an initial verification, or signing an Electrical Installation Certificate. It is also one of the most commonly misunderstood areas on site, because the tabulated maxima are stated at 70°C/conductor operating temperature while you measure on a cold installation.
The common misconception is that the table value is the number you compare your meter reading against. It is not. The table values are the design maxima at full operating temperature. Your measured (cold) value must be lower — by convention, no more than 80% of the tabulated figure (the Cmin / rule-of-thumb 0.8 factor). The other frequent error is forgetting that on a TT system you almost never rely on the overcurrent device for ADS at all — the RCD does the job, and the Zs limit is governed by the RCD's rated residual operating current, not the table.
Key Facts
- Zs definition — Zs = Ze + (R1 + R2). Ze is the external loop impedance (supply side, up to the origin); R1 + R2 is the resistance of the circuit's line conductor plus the circuit protective conductor (CPC).
- Disconnection times (Reg 411.3.2.2) — final circuits ≤63A (TN) with sockets, or ≤32A fixed equipment: 0.4s. Final circuits >63A and distribution circuits: 5s (Reg 411.3.2.3). TT systems use the RCD times in Table 41.1.
- The 80% rule (temperature correction) — Tabulated maximum Zs values assume conductors at operating temperature. A measured value on a circuit near ambient must not exceed 0.8 × tabulated maximum to leave margin once the cable heats up. This is the practical site rule; the formal version uses correction factor Cmin (0.95) and conductor temperature factors per the On-Site Guide / GN3.
- TN-S / TN-C-S (PME) — ADS via the overcurrent device is normal; compare measured Zs to 80% of Table 41.2/41.3/41.4 values.
- TT systems — Earth electrode resistance is high, so ADS relies on the RCD. Maximum Zs = 50V ÷ I∆n (e.g. a 30mA RCD gives 50 ÷ 0.03 ≈ 1667Ω theoretical), but BS 7671 recommends Ra (electrode + CPC) be low enough to be stable — typically aim well under 200Ω, ideally <100Ω.
- Ze typical values — TN-C-S (PME): ≤0.35Ω is the DNO declared maximum. TN-S: ≤0.8Ω declared maximum. TT: often tens to hundreds of ohms (electrode-dependent).
- R1 + R2 — measured during dead testing (continuity of CPC). Adding Ze + (R1+R2) gives a calculated Zs; a live loop test confirms it.
- Table 41.2 — covers fuses to BS 88, BS 1361/BS 88-3, BS 3036 and BS 1362 for 0.4s and 5s.
- Table 41.3 — covers circuit-breakers (MCBs) Types B, C and D to BS EN 60898 / RCBOs to BS EN 61009.
- Table 41.4 — maximum Zs for RCDs (residual current devices) for 0.4s and 5s disconnection, based on I∆n.
- Type B MCB trips magnetically at 3–5 × In; Type C at 5–10 × In; Type D at 10–20 × In. Higher multiples mean lower maximum permitted Zs (you need more fault current to trip them).
- Test instrument — a low-current or "no-trip" loop tester avoids tripping RCDs during the measurement; high-current loop testers give a more accurate reading on circuits without an RCD.
- GS38 — test leads, probes and meters must comply with HSE Guidance Note GS38 (finger guards, ≤4mm exposed tip, fused leads).
- Part P — adding or altering circuits in a dwelling is notifiable work in England/Wales; loop testing forms part of the certification that supports notification.
Quick Reference Table
Quoting an electrical job? Describe the work and squote handles the pricing.
Try squote free →Indicative maximum Zs at the stated disconnection time — tabulated (operating temperature) values, 230V. Apply the 0.8 factor before comparing to a cold measured reading. Always confirm against the current BS 7671 tables; figures marked.
| Device | Rating | Max Zs (0.4s, tabulated) | × 0.8 (measured limit) |
|---|---|---|---|
| Type B MCB | 6A | 7.28Ω | 5.82Ω |
| Type B MCB | 16A | 2.73Ω | 2.18Ω |
| Type B MCB | 20A | 2.19Ω | 1.75Ω |
| Type B MCB | 32A | 1.37Ω | 1.09Ω |
| Type C MCB | 6A | 3.64Ω | 2.91Ω |
| Type C MCB | 16A | 1.37Ω | 1.09Ω |
| Type C MCB | 20A | 1.09Ω | 0.87Ω |
| Type C MCB | 32A | 0.68Ω | 0.55Ω |
| Type D MCB | 32A | 0.34Ω | 0.27Ω |
| 30mA RCD (any rating) | — | 50V ÷ 0.03 ≈ 1667Ω | use Table 41.5 / ≤200Ω guidance |
The MCB values follow the relationship Max Zs ≈ U0 ÷ (trip multiple × In), e.g. Type B 32A: 230 ÷ (5 × 32) = 1.44Ω before the 0.95 Cmin factor is applied. Use this to sanity-check a table figure but always cite the printed table.
Detailed Guidance
Why the 80% rule exists
The maximum Zs values in Tables 41.2–41.4 are calculated for conductors at their normal operating temperature (typically 70°C for thermoplastic/PVC insulation). At that temperature copper has a higher resistance than when cold. When you test, the circuit is usually near ambient (20°C-ish) and unloaded, so its actual resistance — and therefore measured Zs — is lower than it will be in service.
If you measured a value that was right on the tabulated limit while cold, the circuit would exceed that limit once it warmed up under load, and disconnection could become too slow. To prevent that, the accepted approach is to compare your measured value against 80% of the tabulated maximum (the rule-of-thumb 0.8 factor). The rigorous method in Guidance Note 3 / the On-Site Guide uses the 0.95 (Cmin) factor combined with a temperature-correction factor; the simplified 0.8 figure rolls these together for site use and is conservative.
Is measured Zs ≤ (0.8 × tabulated max Zs)?
│
┌─────┴─────┐
YES NO
│ │
PASS Investigate: high Ze? long cable run?
undersized CPC? loose connection?
→ reduce R1+R2, improve earthing,
or upsize CPC. Re-test.
Working out Zs: measured vs calculated
You can establish Zs two ways and they should agree:
- Calculated: Zs = Ze + (R1 + R2). Measure Ze at the origin with the main earth disconnected (and the installation isolated), measure R1 + R2 during dead testing, and add them. Useful when a live loop test would nuisance-trip RCDs.
- Measured (live): a direct loop impedance test at the furthest point of the circuit. Use a no-trip/low-current range on RCD-protected circuits, or a high-current range on non-RCD circuits for best accuracy.
On a final circuit protected by a 30mA RCD, ADS for very small fault currents is provided by the RCD regardless of the overcurrent device's Zs — but you still record Zs to confirm the circuit's earth fault path is sound and within limits.
TT systems and RCDs
On a TT system the earth return is through an electrode in the ground, so Ze is high and the overcurrent device will not reliably disconnect on an earth fault. ADS is provided by an RCD. The maximum Zs is then governed by Reg 411.5.3:
- RA × I∆n ≤ 50V, where RA is the electrode resistance plus the CPC resistance.
- A 30mA RCD gives a theoretical maximum RA of 50 ÷ 0.03 ≈ 1667Ω, but BS 7671 and good practice call for a stable electrode resistance — aim for well under 200Ω, and ideally below 100Ω, because ground conditions vary with weather and a borderline electrode can drift.
Common reasons Zs is too high
- High Ze — poor supply earth (especially TN-S with a degraded cable sheath earth) or a long service.
- Long circuit / small CSA — high R1 + R2 because of run length or thin conductors. Voltage drop will usually be flagged too.
- Undersized CPC — a reduced CPC raises R2 significantly; check it satisfies the adiabatic equation as well as the Zs limit.
- Loose / corroded connections — at the consumer unit, accessories, or a junction. Often shows as an unstable reading.
- Borrowed neutrals or shared CPCs — give misleading or unstable readings; investigate before passing.
Frequently Asked Questions
Do I compare my meter reading to the table value or to 80% of it?
To 80% of it. The printed maximum Zs values assume conductors at operating temperature. Your test is on a cold circuit, so apply the 0.8 rule-of-thumb factor (or the formal Cmin/temperature method in GN3) and compare against that lower figure. If your meter has a built-in "pass/fail" function it usually applies the correction for you, but always know which value it is using.
What disconnection time applies — 0.4s or 5s?
0.4s for final circuits up to 63A on a TN system supplying socket-outlets, or fixed equipment up to 32A (Reg 411.3.2.2). 5s for distribution circuits and final circuits over 63A (Reg 411.3.2.3). On TT systems use the times in Table 41.1, with the RCD providing disconnection.
My RCD-protected circuit has a high Zs but the RCD trips fine — is it a pass?
The 30mA RCD provides ADS for earth faults, so the circuit can satisfy the disconnection requirement via the RCD even with a higher loop impedance. But a high Zs still points to a problem — undersized CPC, long run, or a loose connection — and you should record it and investigate. Don't treat the RCD as a licence to ignore an out-of-spec earth path.
Is loop impedance testing notifiable under Part P?
The testing itself isn't notifiable, but the work that requires it often is. In England and Wales, new circuits and certain alterations in dwellings are notifiable under Part P (Approved Document P). Loop testing is part of the verification you document on the certificate that supports the Building Control notification or competent-person scheme registration.
Why did my loop tester trip the RCD?
A standard high-current loop test injects enough current to operate a 30mA RCD. Use the instrument's no-trip / low-current loop range on RCD-protected circuits, or test upstream of the RCD where practical. The trade-off is slightly lower accuracy on the no-trip range.
Regulations & Standards
BS 7671:2018+A2:2022 (IET Wiring Regulations, 18th Edition Amendment 2) — Reg 411.3.2 (disconnection times), Reg 411.5 (TT systems), Tables 41.2–41.4 (maximum Zs), Table 41.1 (disconnection times).
IET Guidance Note 3: Inspection & Testing — full method for loop impedance testing, temperature correction (Cmin), and measured-vs-tabulated comparison.
IET On-Site Guide — practical maximum Zs tables already corrected to the rule-of-thumb 80% figures for site use.
HSE Guidance Note GS38 — test equipment and probes for electrical test work.
Building Regulations Approved Document P (England) — notifiable electrical work in dwellings.
Electricity at Work Regulations 1989 — duty to ensure systems are safe; underpins ADS and testing obligations.
BS 7671 / IET Wiring Regulations — IET — primary standard and amendments
GOV.UK — Approved Document P: Electrical safety — Part P notifiable work
HSE GS38 — Electrical test equipment for use by electricians — test lead and probe requirements
HSE — Electricity at Work Regulations 1989 — statutory duties
testing commissioning — full inspection and testing sequence (continuity → IR → polarity → Zs → RCD) and certification
earthing bonding — earthing systems (TN-S, TN-C-S/PME, TT) and bonding that determine Ze
consumer units — RCBO vs split-load boards and the protective devices whose Zs limits you test against
part p notifications — when the circuit work behind your testing is notifiable