Summary

Insulation resistance testing is the dead test that finds the faults that will later become RCD trips, nuisance tripping, shock risks and fires: damaged cable sheath, moisture in a junction box, a nail through a cable, an immersion heater element breaking down, old rubber insulation gone brittle, or a rodent-chewed cable in a loft. It is the test that most often reveals something on an EICR and the one most often done badly, because doing it properly means taking things apart: removing lamps, disconnecting neutrals, unplugging appliances, isolating electronic controls and knowing which devices will be damaged by 500 V.

The principle is simple. An insulation tester applies a DC voltage, much higher than the circuit's working voltage, across the insulation and measures how much current leaks through it. The result is expressed in megohms. Good PVC insulation on a dry circuit leaks almost nothing and the reading is in the hundreds of megohms, often beyond the instrument's range. Deteriorated insulation, damp or a direct fault leaks current and the reading falls. BS 7671 sets a floor of 1.0 MΩ for ordinary circuits, but that is a minimum, not a target; a 1.5 MΩ reading on a modern circuit is a latent fault, and IET Guidance Note 3 recommends investigating anything below 2 MΩ.

This article covers the test voltages and minimum values, the test sequence on single-phase and three-phase circuits, what to disconnect and why, how to interpret low readings, how to record results, and the mistakes that produce false fails and damaged equipment. It assumes the circuit has been safely isolated first; see safe isolation procedure. For where IR sits in the full test sequence see test and inspection procedures; for coding the results on a periodic inspection see eicr codes c1 c2 c3 fi explained.

Key Facts

Quick Reference Table

Quoting an electrical job? Describe the work and squote handles the pricing.

Try squote free →
Circuit type Test voltage (DC) Minimum IR (MΩ) Typical healthy reading Notes
SELV / PELV (e.g. 12 V lighting, doorbell transformer secondary) 250 V 0.5 >200 MΩ Test the SELV side separately from the 230 V primary
FELV 500 V 1.0 >200 MΩ Treated as a low-voltage circuit for IR
230 V single-phase final circuit (lighting, sockets, cooker, shower) 500 V 1.0 >200 MΩ Lamps out, loads off, electronics disconnected
230 V circuit with SPD or electronics that cannot be disconnected 250 V 1.0 >200 MΩ Permitted by Reg 643.3.2; note on schedule
400 V three-phase distribution or sub-main 500 V 1.0 >200 MΩ Six live–live/live–N tests plus live–earth
Circuits above 500 V (rare in domestic) 1,000 V 1.0 >200 MΩ Specialist installations
Whole installation from DB, all finals connected 500 V 1.0 Often 20–100 MΩ Parallel paths; test circuits individually if below 2 MΩ
Immersion heater circuit 500 V 1.0 >200 MΩ with element disconnected Low L–E with element connected = element breakdown
Old rubber (VIR/TRS) wiring 500 V 1.0 Often 0.5–5 MΩ and falling Record, code and recommend rewire regardless of a marginal pass

Detailed Guidance

What the test proves and when to do it

Insulation resistance confirms that the insulation separating live conductors from each other and from earth is intact along the whole length of the circuit, including the parts you cannot see. It comes after continuity of protective conductors and ring final continuity in the BS 7671 Part 6 sequence and before polarity, because an insulation fault must be found before the circuit is energised for the live tests. It is carried out on every new circuit before it is connected to the supply (initial verification, Regulation 643), on every altered or extended circuit (Minor Works), and on the agreed sample of circuits at periodic inspection (Regulation 653, with the extent and limitations agreed with the client and recorded on the EICR).

Preparing the circuit

  1. Isolate and prove dead. Switch off, lock off and prove dead at the point of work with a GS38 two-pole tester, proving the tester before and after. See safe isolation procedure.
  2. Disconnect the circuit at the board. Take the line conductor out of the protective device and the neutral out of the neutral bar (or identify the terminals you will test from). On a split-load board or with RCBOs, you may need to lift the neutral from the RCBO's neutral terminal rather than the bar.
  3. Remove lamps and disconnect electronics. Every lamp out (LED lamps and drivers can be damaged by 500 V and will read low), dimmers and electronic switches disconnected or bridged, PIRs and photocells disconnected, smoke and heat alarms unplugged from their bases, boiler, programmer and room stat isolated and disconnected from the circuit, immersion stat disconnected if it has electronics, USB socket outlets disconnected or noted, smart switches and relays removed, EV charger disconnected, SPD disconnected or removed. Unplug every portable appliance on socket circuits.
  4. Switches ON. With lamps removed, close all switches, including two-way and intermediate switches in all positions, so that the switch wires and strappers are included in the test. On a two-way circuit, test with the switches in both combinations if time allows, because one strapper is excluded in each position.
  5. Note borrowed neutrals. Where a neutral from another circuit is shared (common in older two-way lighting between landing and hall), the L–N test will read low or zero. Identify and disconnect, and record the borrowed neutral as a defect.
  6. Check for anything else connected. Fused connection units with equipment, a fan with an electronic timer, a cooker with a clock, an outside light with a photocell, an extract fan with humidistat. All of it either comes off or is accounted for.

The test sequence on a single-phase circuit

IR TEST — SINGLE PHASE
│
├─ Set the tester to 500 V DC (250 V for SELV/PELV or where Reg 643.3.2 applies).
│
├─ Test 1: L to N  (live conductors)
│     Expect >200 MΩ. Low? → a load, lamp or electronic device is still connected,
│     or there is a borrowed neutral, or L and N insulation is damaged.
│
├─ Test 2: L to E
│     Expect >200 MΩ. Low with L–N fine? → damaged insulation to earth, moisture,
│     an immersion element, or a nail/screw through the line conductor.
│
├─ Test 3: N to E
│     Expect >200 MΩ. Low? → neutral–earth fault: common where a neutral has been
│     terminated in an earth bar in error, or where cable is damaged in a metal box.
│
└─ Alternative where equipment cannot be removed:
      Link L and N together, test L+N to E at 500 V (or 250 V with electronics).
      This protects equipment but does NOT test between L and N. Record it as such.

Hold the test button until the reading stabilises; on long circuits cable capacitance makes the reading climb for a few seconds. Release and allow the instrument to discharge the circuit before touching conductors. Record the lowest reading for L–L and for L–E on the schedule; where the reading exceeds the instrument's range, record the maximum with the greater-than symbol as the instrument displays it.

Three-phase circuits

On a TP&N distribution circuit or sub-main there are more insulation paths and each must be tested: L1–L2, L1–L3, L2–L3, then L1–N, L2–N, L3–N, then each live conductor (or all linked) to earth. Three-phase motors, VSDs and control panels must be disconnected, both because the drive electronics will be damaged and because a motor winding gives a low reading that says nothing about the cable. Testing a sub-main with the downstream board connected tests every circuit on it at once; a low reading sends you downstream to find the circuit responsible.

Interpreting a low reading

A reading below 1.0 MΩ fails. A reading between 1.0 and 2.0 MΩ passes the regulation but indicates something wrong and should be investigated. The pattern of readings tells you where to look:

Readings Likely cause Where to look
L–N low, L–E and N–E fine Load still connected; lamp left in; borrowed neutral; electronic device Check every point on the circuit for a lamp, FCU, fan, control
L–E low, N–E fine Line insulation to earth damaged; immersion element; heat damage at a cooker or shower terminal Immersion heaters, cooker connection units, downlight connections, outside lights
N–E low, L–E fine Neutral terminated to earth; neutral insulation damaged in a metal back box; wet accessory Metal boxes, outside sockets, bathroom fans, junction boxes under floors
All three low together Moisture; damaged cable sheath; old rubber insulation; rodents Lofts, under floors, outside runs, anywhere wet
Falls while holding test Moisture or tracking across contaminated insulation Dry out and retest; may indicate a long-term damp problem
Zero / short Direct fault; nail or screw through cable; L and N or L and E touching in an accessory Recent building work, new fixings, picture hooks over cables
Low only with switches in one position Fault in a strapper or switch drop on two-way lighting The switch wire that is only included in that position

To locate a fault, split the circuit. Disconnect at a convenient point (a junction box, the mid-point of a radial, an accessory) and test each half; keep halving until the faulty section is between two points. On a ring final, open the ring at the board and test each leg from the board to the first socket where the two legs meet.

Old rubber-insulated cable (VIR in conduit or TRS) often reads a marginal 0.5–5 MΩ because the rubber has perished, particularly at terminations where it crumbles when handled. A marginal pass on such a circuit is still a circuit that should be recommended for rewiring and coded appropriately; the insulation will not get better and the handling during the test has probably made it worse.

Protecting equipment from the test

The point of 500 V is to stress the insulation beyond its working voltage. Anything with a semiconductor across the line and neutral or to earth is at risk: LED drivers, dimmers, PIRs, smoke alarms, boiler PCBs, USB sockets, smart switches, RCBO electronics, SPDs, EV chargers, induction hobs, and modern appliances. The rules of thumb are: if it has a PCB, disconnect it; if it cannot be disconnected without unreasonable effort (an SPD module built into a board, a socket with integral SPD), test that circuit at 250 V as Regulation 643.3.2 permits and record it; if even 250 V is a risk, link L and N and test to earth only, and record that L–N was not tested. On a board full of RCBOs, check the manufacturer's data: some are tested in place at 500 V without harm, others require the neutral to be lifted.

Recording and coding

On an Electrical Installation Certificate or EICR Schedule of Test Results, IR is recorded per circuit in two columns, live–live and live–earth, in megohms. A test at other than 500 V is noted. At periodic inspection, under Electrical Safety First Best Practice Guide 4, an IR below the Table 64 minimum is a C2; a reading between 1 and 2 MΩ is generally recorded with a recommendation for investigation (an FI where the cause cannot be determined within the agreed scope, or a C3 where it indicates deterioration that is not yet dangerous). An immersion heater element reading low to earth with the element connected is a C2 if the circuit is not RCD protected, and in all cases a recommendation to replace the element. Where IR could not be tested on a circuit because equipment could not be disconnected, the limitation is recorded; it is not left blank.

Common mistakes

  1. Testing with lamps in. LED lamps read low, and 500 V damages the driver. A circuit "failing" IR on an EICR because the inspector did not remove the lamps is a false fail that leads to unnecessary work.
  2. Switches left off. On a lighting circuit that excludes the switch drop and the pendant from the test, which is where damage from heat and handling is most likely.
  3. Boiler or heating controls left connected. Causes a low L–N reading and can destroy the boiler PCB, an expensive mistake.
  4. Not disconnecting the SPD. Reads a few MΩ or less and may degrade the SPD. Disconnect it or test at 250 V.
  5. Testing from the board with all circuits connected and accepting a low result. The parallel reading is not a fault; test circuits individually.
  6. Ignoring a pass under 2 MΩ. 1.2 MΩ on a 2015 circuit is a fault waiting to trip an RCD, not a pass to move on from.
  7. Wrong test voltage. Testing a 230 V circuit at 250 V without the Regulation 643.3.2 justification understates the stress on the insulation and is a lower standard than the regulation requires.
  8. Missing borrowed neutrals. Two-way lighting between circuits gives a low L–N reading and, worse, a live neutral on an isolated circuit.
  9. Not discharging. Long three-phase sub-mains hold a charge after the test; allow the meter to discharge and confirm dead.
  10. Forgetting to reconnect. Neutrals left out of the bar, boiler not reconnected, smoke alarms left off their bases, lamps not refitted. Make a list as you disconnect.
  11. Handling perished rubber. On old VIR, flexing the cable at terminations to connect the tester cracks the insulation; be deliberate and warn the customer that the circuit needs rewiring whatever the reading.
  12. Testing damp new work. Fresh plaster and a wet screed around new cable runs can give low readings that recover when dry; note it, dry it, retest before signing off, and do not sign off a circuit that has not reached 1.0 MΩ.

Frequently Asked Questions

Why do I test at 500 V when the circuit only runs at 230 V?

Because the point is to prove a margin. Insulation that is barely adequate at 230 V will fail at a transient, a surge or a warm summer in the loft; applying roughly twice the working voltage finds weak insulation before it fails in service. Table 64 ties the test voltage to the circuit's nominal voltage band: 250 V for SELV/PELV, 500 V for anything up to 500 V, 1,000 V above that.

Does 1 MΩ mean the circuit is fine?

It means the circuit meets the regulation's minimum and can legitimately be energised. It does not mean the circuit is in good condition. A sound PVC circuit reads hundreds of megohms; 1 MΩ is a reading that would have been 200 MΩ when the circuit was new and has fallen by a factor of 200. IET Guidance Note 3 recommends investigating anything below 2 MΩ. Record it, look for the cause, and advise the customer.

Can I test a circuit with the RCBOs or SPD in place?

Check the manufacturer's data. Many RCBOs are rated to withstand a 500 V IR test with the circuit conductors connected, but some electronic types need the neutral disconnected or the device bypassed. An SPD will generally read low and may be damaged; disconnect it (most are modular with a removable cartridge) or, where it is built into a socket or board and cannot reasonably be removed, Regulation 643.3.2 lets you test that circuit at 250 V DC provided the result is still 1.0 MΩ or more.

What is the difference between testing L+N linked to E and testing separately?

Linking L and N together and testing to earth stresses the insulation between the live conductors and earth without putting a potential difference between L and N, which protects connected equipment. It does not test the L–N insulation at all, so a cable with L and N insulation damaged against each other passes. It is a legitimate method where equipment cannot be disconnected, provided the schedule records that live–live was not tested and why. On a new circuit with nothing connected there is no reason not to do the three separate tests.

The immersion heater circuit reads 0.3 MΩ to earth. Is the cable faulty?

Almost certainly not. Disconnect the immersion heater element at the thermostat and retest; the cable will read >200 MΩ and the element on its own will read low. Immersion elements take on moisture through a cracked sheath as they age and leak to earth, which is why they trip RCDs. The element needs replacing; the circuit is sound. See immersion heater tripping fuse.

Regulations & Standards