Summary
Legionella risk assessments are sold at two very different price points, and a plumber or heating engineer offering them needs to understand why. At the bottom of the market, letting agents and landlords are offered a "Legionella certificate" for £40–£60 by assessors who spend 20 minutes on site, tick a template and email a PDF; some of these are fine, some are worthless, and the HSE has said repeatedly that there is no such thing as a Legionella certificate and no legal requirement for an annual one. At the top, a competent assessment of a care home or a leisure centre is a day's work by someone with a water-hygiene qualification, producing a schematic of the system, a register of outlets, a temperature survey, a written scheme of control and a monitoring programme — and it is priced in the hundreds or low thousands.
For a tradesperson the opportunity is in the middle: a competent, honest assessment of a domestic let or a small commercial premises that tells the duty holder what their system is, where the risk sits (stored water between 20°C and 45°C, dead legs, little-used outlets, scaled showerheads), and what to do about it, priced to reflect 30–90 minutes on site and an hour of report writing. The follow-on work — removing the dead leg, raising the cylinder stat, fitting a TMV, descaling the showerheads, a six-monthly temperature check — is plumbing, and it is where the assessment earns its keep. This guide gives the price points, the time and the cost base, what a report must contain to be worth the fee, the legal position for landlords (which customers will ask about and which many assessors misstate), and how to structure the follow-on work.
For the technical control measures see legionella risk; for the landlord duties and temperature regime see legionella management; for HMO context see hmo licensing.
Key Facts
- Legal basis — Health and Safety at Work etc. Act 1974 (ss.2, 3, 4), Control of Substances Hazardous to Health Regulations 2002 (reg 6, assessment), Management of Health and Safety at Work Regulations 1999; the ACoP is L8 (4th edition, 2013) and the technical guidance is HSG274 Part 2 (hot and cold water systems)
- Landlords — a landlord's duty under s.3 HSWA 1974 and COSHH applies to the water systems in let property; HSE guidance states the assessment can be carried out by the landlord themselves if competent, need not be by a third party, and does not need annual renewal — it is reviewed when the system or its use changes. There is no statutory "Legionella certificate"
- HMOs — the assessment is routinely requested by licensing authorities as a condition of the licence; most authorities accept a landlord's own assessment but many letting agents require a third-party report
- Domestic single let, combi boiler, no stored water — low risk; 30–45 minutes on site; £60–£120
- Domestic with cylinder and cold water storage tank — 45–60 minutes; £80–£150
- HMO, 4–6 lets, shared bathrooms — 60–90 minutes; £90–£180
- Small commercial (shop, office, surgery, small gym) — 2–4 hours on site plus report; £200–£450
- Care home, hotel, leisure centre, school — half to full day, qualified assessor; £400–£1,200+; usually a specialist water-hygiene contractor
- Report contents — site and system description; schematic of hot and cold systems; outlet register; temperatures at sentinel outlets (cold ≤20°C within 2 minutes of running, hot ≥50°C within 1 minute, stored hot ≥60°C); identification of dead legs, little-used outlets, TMVs, showerheads, tanks and their condition; risk rating; written scheme of control with actions, responsibilities and review frequency
- Temperature targets — hot water stored at ≥60°C, distributed to reach ≥50°C at the outlet within one minute (55°C in healthcare); cold water stored and distributed at <20°C; TMV outlets at 38–44°C with the TMV serviced annually and the hot supply to it at ≥50°C
- Monitoring regime (HSG274 Part 2, Table 2.1) — monthly sentinel outlet temperatures; quarterly showerhead descale and disinfection; six-monthly cold-water tank temperature; annual tank inspection; weekly flushing of little-used outlets; review the assessment at least every two years or on change
- Dead legs — pipework to a removed or disused outlet; cut back to the live main; the single most common remedial on a domestic assessment
- Instruments — a calibrated digital thermometer with a surface probe and an immersion probe (£40–£150); a torch; a camera; a thermometer calibration certificate is what a licensing officer may ask to see
- Qualifications — no statutory requirement, but competence must be demonstrable (L8 requires the duty holder to appoint competent persons and sets out what competence means); a one-day City & Guilds-accredited or Water Management Society Legionella awareness/risk assessment course (£150–£400) is the market norm for domestic work; the Legionella Control Association (LCA) code of conduct is the standard for commercial contractors
- Insurance — professional indemnity for the advice in the report, £300–£800 a year, in addition to public liability; most plumbing PL policies do not cover written risk-assessment advice
- Follow-on work — dead-leg removal £120–£250; cylinder thermostat raised and TMV fitted at the outlet £180–£350; showerhead replacement £30–£60 each; cold-water tank clean and disinfect £200–£400; tank lid and insulation to BS 8558 £120–£250; monthly temperature monitoring visit £40–£80
- Water testing — sampling for Legionella (UKAS lab, £40–£80 per sample) is not routinely required for domestic or low-risk systems under HSG274; it is for high-risk systems, after an outbreak, or where control cannot be achieved
- Markup — materials on remedials at trade cost plus 20–30%; the assessment fee itself is time plus report at the hourly rate plus a margin for the PI cover and the liability
Quick Reference Table
Spending too long on quotes? squote turns a 2-minute voice recording into a professional quote.
Try squote free →| Premises | Time on site | Report time | Regional (outside London/SE) | South East | London |
|---|---|---|---|---|---|
| Single let, combi boiler, no storage | 30–45 min | 30–45 min | £60–£100 | £70–£120 | £80–£140 |
| Single let, cylinder + loft tank | 45–60 min | 45 min | £80–£130 | £90–£150 | £100–£170 |
| HMO, 4–6 bedrooms, shared bathrooms | 60–90 min | 1 hr | £90–£160 | £110–£180 | £130–£220 |
| Block of flats, communal cold-water storage and risers (per block) | 2–3 hrs | 2 hrs | £250–£450 | £300–£500 | £350–£600 |
| Small commercial: shop or office, 1 cylinder, 2–6 outlets | 2–3 hrs | 2 hrs | £200–£350 | £240–£400 | £280–£450 |
| Dental or GP surgery, hairdresser, small gym with showers | 3–4 hrs | 2–3 hrs | £300–£500 | £350–£550 | £400–£650 |
| Care home, hotel, school, leisure centre | 1 day+ | 1 day | £400–£1,200+ | £500–£1,400+ | £600–£1,600+ |
| Review of an existing assessment (no system change) | 30–60 min | 30 min | £50–£100 | £60–£110 | £70–£130 |
| Monthly sentinel temperature monitoring visit | 20–40 min | 10 min | £40–£80 | £45–£90 | £55–£100 |
| Cold water storage tank clean and disinfect (to BS 8558) | 2–4 hrs | — | £200–£400 | £240–£450 | £280–£550 |
Detailed Guidance
What the customer is actually buying
The report. A Legionella risk assessment with no schematic, no outlet register, no temperatures and no scheme of control is a letter saying someone visited. For the fee to be defensible, the report needs:
- Scope and identification — address, duty holder (the landlord or employer), responsible person, date, assessor and their competence (course certificate reference)
- System description — mains cold water supply and stopcock; cold-water storage (tank size, location, lid, insulation, condition, temperature); hot water generation (combi, vented cylinder, unvented cylinder, size, thermostat setting, stored temperature); distribution (materials, insulation, secondary circulation, pipe runs); outlets (register with type, location, usage frequency, TMV present)
- Schematic — a hand sketch is acceptable for a flat; a line diagram for anything with risers or a cylinder, showing tanks, cylinder, pumps, TMVs, outlets and dead legs
- Temperature survey — cold at the sentinel (nearest and furthest) outlets after 2 minutes, hot at the sentinels after 1 minute, stored hot at the cylinder, tank water temperature. Record the ambient and the readings
- Risk factors found — water stored between 20°C and 45°C; dead legs and blind ends; outlets used less than weekly (spare bedroom en-suites, outside taps in winter); scaled or dirty showerheads; tank with no lid, debris or sediment; TMVs not serviced; pipework insulated so cold runs warm; susceptible occupants (over 45, smokers, immunocompromised — relevant in care settings)
- Risk rating — low, medium, high, with the reasoning
- Written scheme of control — the actions, who does them, how often, and where the records go: cylinder stat to 60°C; cut back the dead leg; weekly flush of unused outlets by the tenant (and a note in the tenancy); quarterly showerhead clean; six-monthly tank check; review date
- Photographs — tank, cylinder stat, showerheads, any dead leg
A one-page template with tick boxes can carry all of that for a flat. A commercial premises needs a proper document. Either way, the report is the product; the visit is how it is made.
Time and cost base
For a plumber or heating engineer adding assessments to an existing business, the cost base is small: a calibrated thermometer, a one-day course, a report template, and the PI insurance. The time is the price driver:
| Element | Single let, combi | HMO with cylinder and tank | Small commercial |
|---|---|---|---|
| Travel (in and out) | 30 min | 30 min | 45 min |
| Survey and temperatures | 30 min | 60–90 min | 2–3 hrs |
| Report | 30 min | 60 min | 2 hrs |
| Total time | 1.5 hrs | 2.5–3 hrs | 5–6 hrs |
| At £45/hr | £68 | £113–£135 | £225–£270 |
| Add PI and liability margin, 15–25% | £80–£85 | £130–£170 | £260–£340 |
That reconciles with the Quick Reference Table. It also shows why the £40 "certificate" cannot be done competently: it allows for no report time and no visit beyond the front door. Letting agents who buy at £40 are buying a document, and a plumber who competes at that price is giving away three hours.
For a plumber the better sale is the bundle: assess the HMO at £140, and quote the dead-leg removal, the TMV and the tank lid on the same report at £450–£700. That is a half-day of plumbing at proper rates, sold by the assessment.
The landlord question, answered correctly
Customers will ask whether they legally need this and whether it has to be renewed every year. The honest answer, which is also the HSE's published position, is:
- Landlords have a duty to assess and control the risk from Legionella in the water systems of property they let, under HSWA 1974 s.3 and COSHH 2002 reg 6
- For most domestic lets the risk is low — small systems, mains-fed cold water, hot water used daily, combi boilers with no storage — and a simple assessment is proportionate
- The landlord can carry out the assessment themselves if they are competent to do so; there is no requirement to use a contractor
- There is no statutory requirement for a certificate, and no fixed annual renewal; the assessment should be reviewed if the system or its use changes (a new tenant, a void period, a new cylinder) and periodically — two years is the common review interval taken from HSG274
- Sampling the water for Legionella is not routinely required in domestic premises
Say this in the quote and the report. A tradesperson who tells a landlord they legally need an annual certificate is misrepresenting the law, and the letting agents who do so have been corrected by the HSE in print. The sale is still there: most landlords want a competent third-party assessment and a written scheme of control because it shows they discharged the duty, and most licensing authorities and agents ask for one. See legionella management and renters rights act 2025 landlord compliance for the wider landlord-compliance context.
Remedials: the follow-on work and how to price it
| Remedial | What it involves | Price (supplied and fitted, regional) |
|---|---|---|
| Dead leg removal | Trace the redundant run, cut back to the live main, cap, make good | £120–£250 per dead leg |
| Cylinder thermostat to 60°C and anti-scald TMV at bath/basin | Adjust stat; fit TMV2/TMV3 valve under the basin or at the bath; test outlet temperature | £180–£350 per TMV |
| Showerhead and hose replacement | Replace scaled head and hose; note quarterly clean in scheme | £30–£60 each |
| Cold-water storage tank: lid, insulation, screened overflow and vent to BS 8558 | Fit close-fitting lid kit, insulation jacket, insect screens | £120–£250 |
| Tank clean and disinfect | Drain, clean, chlorinate to 50 mg/l for 1 hour, flush, re-test (to BS 8558 and PD 855468) | £200–£400 |
| Secondary return pump or trace heating on long hot runs | Where hot outlets will not reach 50°C within a minute | £400–£1,200 |
| Outlet flushing regime and record sheet for the tenant | Written instruction, sheet in the property file | Included in the report |
| Monthly or quarterly monitoring visit | Sentinel temperatures, showerhead check, record | £40–£80 per visit |
Price materials at trade cost plus 20–30% and the labour at your hourly rate; these are plumbing jobs and the margin is the plumber's margin. See thermostatic mixing valves for TMV selection and domestic hot water cylinder sizing for cylinder temperature settings.
Commercial premises and when to refer on
A shop with a kitchen sink, a staff WC and an electric point-of-use heater is a 2-hour job. A premises with a calorifier, secondary circulation, showers, a cold-water tank room and vulnerable occupants (a care home, a nursing home, a hospital, a hotel, a school with showers) is HSG274 Part 2 territory where the written scheme needs a monitoring programme, a named responsible person, training records and, in some cases, sampling and a water-treatment regime. Price it only if you hold a recognised Legionella risk-assessment qualification and PI cover to match; otherwise refer to a Legionella Control Association member and take a referral or subcontract the remedials. Cooling towers and evaporative condensers (HSG274 Part 1) must be notified to the local authority under the Notification of Cooling Towers and Evaporative Condensers Regulations 1992 and are a specialist's work entirely.
Worked example: 5-bed HMO, vented cylinder, loft tank
Travel 30 min
Survey: tank (loft), cylinder, 2 bathrooms, kitchen,
5 bedroom basins, outside tap; temperatures at 6
outlets + cylinder + tank; photographs; sketch 80 min
Report: schematic, register, temperatures, risk rating,
scheme of control, tenant flushing sheet 60 min
--------
Total ~2.8 hrs at £45 = £128
PI/liability margin 20% £26
Assessment fee quoted £150
Findings: tank with no lid, 15°C ambient loft, sediment;
cylinder stat at 50°C; dead leg to removed bath in bed 3;
en-suite in bed 5 unused for 6 months.
Remedials quoted on the same report:
Tank lid kit, insulation, screens £180
Cylinder stat to 60°C + TMV at kitchen and 2 bath/basins
(3 TMVs) £720
Dead leg cut back and capped £160
Flushing regime sheet for tenants included
--------
Remedials £1,060
Total invoice if all accepted £1,210
The assessment at £150 is competitive and competent. The job is £1,210 and a day's work. That is the model.
Frequently Asked Questions
How much does a Legionella risk assessment cost for a rental property?
£60–£120 for a single let with a combi boiler, £80–£150 with a cylinder and tank, and £90–£180 for an HMO, in 2026 outside London. The £40 "certificate" offers exist but rarely include a schematic, temperatures or a scheme of control, which are what make the document worth having.
Do landlords legally need a Legionella certificate?
No. Landlords must assess and control the risk, under the Health and Safety at Work etc. Act 1974 and COSHH 2002, but the HSE's guidance is explicit that the assessment can be done by the landlord themselves, that no third-party certificate is required, and that there is no fixed annual renewal. Most landlords still choose a third-party assessment because it evidences the duty, and HMO licensing authorities and letting agents routinely ask for one.
How often should the assessment be reviewed?
When the system or its use changes — a new cylinder, a void period, a new tenant group — and periodically otherwise; two years is the review interval most assessors use, drawn from HSG274 Part 2. Monitoring (monthly sentinel temperatures, quarterly showerhead cleaning, flushing of little-used outlets) is continuous and is set out in the scheme of control, not by repeating the assessment.
Do I need a qualification to do Legionella risk assessments?
There is no statutory qualification, but competence must be demonstrable under L8. The market norm for domestic and small commercial work is a one-day accredited Legionella awareness and risk assessment course, a calibrated thermometer, and professional indemnity insurance that covers written risk-assessment advice. For care homes, hotels and premises with calorifiers and secondary circulation, use a Legionella Control Association member or hold an equivalent qualification yourself.
Should the water be tested for Legionella?
Not routinely in domestic or low-risk premises. HSG274 Part 2 treats sampling as a tool for high-risk systems, systems where temperature control cannot be achieved, or after a case of Legionnaires' disease. Temperature control and flushing are the controls; a lab sample at £40–£80 proves a point on one day and does not replace them.
Regulations & Standards
Health and Safety at Work etc. Act 1974 (ss.2, 3, 4) — duties of employers, the self-employed and those in control of premises, including landlords
Control of Substances Hazardous to Health Regulations 2002 (SI 2002/2677, reg 6) — duty to assess the risk from biological agents including Legionella
Management of Health and Safety at Work Regulations 1999 (SI 1999/3242, reg 3) — risk assessment
HSE L8 (4th edition, 2013) — Legionnaires' disease: the control of legionella bacteria in water systems, Approved Code of Practice and guidance
HSE HSG274 Part 2 (2014) — The control of legionella bacteria in hot and cold water systems; temperature targets, monitoring frequencies (Table 2.1), sampling guidance
HSE HSG274 Part 1 — evaporative cooling systems; Part 3 — other risk systems (spa pools etc.)
Notification of Cooling Towers and Evaporative Condensers Regulations 1992 (SI 1992/2225) — local authority notification
Water Supply (Water Fittings) Regulations 1999 (SI 1999/1148) — storage cistern requirements (lids, screens, insulation) and backflow
BS 8558:2015 — guide to the design, installation, testing and maintenance of services supplying water for domestic use within buildings; cistern cleaning and disinfection
BS EN 806-1 to -5 — specifications for installations inside buildings conveying water for human consumption
PD 855468:2015 — guide to the flushing and disinfection of services supplying water for domestic use
BS 7592:2022 — sampling for Legionella bacteria in water systems; code of practice
BS EN 1111:2017 / BS EN 1287:2017 and NHS D 08 — thermostatic mixing valves (TMV2 / TMV3 schemes)
Housing Act 2004 (Part 2, HMO licensing) and the Housing Health and Safety Rating System — Legionella as a hazard in HMO licensing conditions
Consumer Rights Act 2015 — reasonable care and skill in the assessment service
HSE — Legionella and landlords — the HSE statement that no certificate or annual renewal is required and landlords may self-assess
HSE — HSG274 Part 2: hot and cold water systems — temperature targets, monitoring table and sampling guidance
Legionella Control Association — Code of Conduct — standards for commercial service providers
Water Management Society — Legionella training — accredited courses and competence
BSI — BS 8558:2015 — cistern and system maintenance guidance
legionella risk — temperatures, dead legs and the technical control measures
legionella management — landlord duties, temperature control and monitoring in detail
thermostatic mixing valves — TMV selection and servicing for the remedials
hot water cylinder types guide — vented and unvented cylinders and their thermostats
domestic hot water cylinder sizing — stored volume and the 60°C setting
hmo licensing — where the assessment sits in licence conditions
landlord certificates — the other landlord documents that go with it
plumber hourly rate guide — the hourly rate behind these figures