Summary
Extract ventilation rates are one of the most frequently misquoted numbers in UK domestic building work — not because the figures are obscure, but because they're easy to misremember room-to-room, easy to confuse with the separate whole-dwelling background ventilation rate, and easy to under-deliver in practice once duct losses are accounted for. A fan rated at the correct l/s figure on its datasheet can still fail to meet Part F on site if the duct run is long, has multiple bends, or uses undersized flexible ducting.
This article is a focused reference on the extract rates themselves — the numbers you need at your fingertips when specifying a fan, checking a spec sheet, or answering a Building Control query on site. For the broader ventilation strategy context (System 1–4, background ventilators, MVHR design and whole-dwelling ventilation rates), see part f ventilation.
The rates matter for two connected reasons. First, they're a Building Regulations compliance requirement — a Building Control inspector or a competent person scheme assessor can and will check them, and getting them wrong risks a failed sign-off. Second, and more practically, they're the actual number that determines whether the room works — inadequate kitchen and bathroom extraction is the single biggest preventable cause of condensation, mould growth and the resulting disputes that end up as fault-finder callbacks months after a job is signed off.
Key Facts
- Approved Document F (2021 edition, Volume 1: Dwellings) — in force from 15 June 2022, supersedes ADF 2010. Always check you're working to the current published edition, as figures have historically been revised between editions.
- Extract rates are room-specific, not whole-dwelling — do not confuse these figures with the separate whole-dwelling background ventilation rate (calculated per bedroom count or per m² floor area), which is a distinct requirement covered in part f ventilation.
- Kitchen — cooker hood adjacent to hob: 30 l/s intermittent minimum.
- Kitchen — extract fan elsewhere in the kitchen (not adjacent to hob): 60 l/s intermittent minimum — the higher rate compensates for not capturing steam and grease at source.
- Kitchen — continuous extract: 13 l/s minimum, regardless of fan position.
- Utility room: 30 l/s intermittent, or 8 l/s continuous.
- Bathroom (contains a bath or shower — includes en-suites and wet rooms): 15 l/s intermittent, or 8 l/s continuous.
- WC / cloakroom (sanitary accommodation only, no bath or shower): 6 l/s intermittent.
- Recirculating cooker hoods do NOT count toward Part F extract compliance — they filter and return air to the room without removing moisture; only ducted extraction to outside satisfies the requirement.
- Run-on (overrun) timer — intermittent extract fans must run on for a minimum of 15 minutes after use to clear residual moisture; humidity-sensing fans that run until humidity drops below a setpoint are an accepted alternative.
- Rated flow vs actual flow — a fan's nominal/free-air rating on the box is not the figure that matters; the certified flow rate at the installed duct resistance is what must meet the minimum, and commissioning should be verified on site with an airflow measurement, not assumed from the datasheet.
- Duct losses reduce actual flow — long runs and multiple 90° bends materially reduce delivered airflow; each 90° bend adds roughly 1.5m of equivalent straight-duct resistance, and a 5m run with two bends can reduce actual flow by around 25% versus the fan's rated figure.
- Commissioning is a Building Regulations requirement, not an optional extra — an airflow reading (typically with a vane anemometer) at the grille should be recorded as evidence of compliance at handover.
- Continuous systems (MEV/MVHR) run at the lower "continuous" figure as background rate and are typically boosted automatically (humidity, occupancy, or manual boost switch) during and after activities that generate moisture — the boosted rate should meet or exceed the intermittent minimum for that room.
Quick Reference Table
Need to quote compliant work? squote includes relevant regulations in your quotes.
Try squote free →| Room Type | Intermittent Extract Minimum | Continuous Extract Minimum | Run-on Timer Required? |
|---|---|---|---|
| Kitchen — hood/fan adjacent to hob | 30 l/s | 13 l/s | Yes (min. 15 min) |
| Kitchen — fan elsewhere in room | 60 l/s | 13 l/s | Yes (min. 15 min) |
| Utility room | 30 l/s | 8 l/s | Yes (min. 15 min) |
| Bathroom (with bath or shower) | 15 l/s | 8 l/s | Yes (min. 15 min) |
| En-suite (with bath or shower) | 15 l/s | 8 l/s | Yes (min. 15 min) |
| Shower room (no bath) | 15 l/s | 8 l/s | Yes (min. 15 min) |
| WC / cloakroom (no bath/shower) | 6 l/s | — | Yes if mechanically extracted |
| Wet room | 15 l/s | 8 l/s | Yes (min. 15 min) |
Detailed Guidance
Kitchens: why the fan position changes the required rate
Approved Document F sets a noticeably higher requirement (60 l/s vs 30 l/s) for a kitchen extract fan that isn't positioned adjacent to the hob, because a cooker hood mounted directly above the hob captures steam and airborne grease at the source, before it disperses into the room. A wall- or ceiling-mounted fan positioned elsewhere in the kitchen has to move a much larger volume of air to achieve an equivalent moisture-removal effect, because it's extracting already-dispersed, cooled steam rather than capturing it at source.
This has a direct sizing consequence on site: a 100mm axial fan is often adequate for a bathroom but is marginal at best for a kitchen positioned away from the hob — specify a 150mm fan or an in-line centrifugal unit capable of genuinely delivering 60 l/s once duct losses are accounted for, not just the fan's rated free-air figure.
Recirculating hoods do not satisfy Part F. A recirculating cooker hood filters cooking odour through a carbon filter and returns the air to the kitchen — it removes essentially none of the moisture. For new kitchens and kitchen extensions, Part F requires genuine ducted extraction to outside. Where ducting is impractical in a renovation, a separate ducted extract fan meeting the relevant l/s figure must be provided instead of relying on a recirculating hood alone.
Bathrooms, en-suites and shower rooms: one rate, several room names
The 15 l/s intermittent / 8 l/s continuous figure applies to any room containing a bath or shower, regardless of what it's called on the floor plan — bathroom, en-suite, shower room and wet room all fall under the same requirement. The distinguishing test is the presence of a bath or shower, not the room label. A room with only a WC and basin (no bath or shower) is sanitary accommodation, not a bathroom for Part F purposes, and takes the lower 6 l/s figure instead.
Watch for combined rooms — a WC/utility combination, for example, should be assessed against the higher of the two applicable rates (utility room's 30 l/s intermittent generally exceeds the WC's 6 l/s), because the room's function as a utility space with a WC in the corner doesn't reduce the extract requirement driven by the utility use.
Utility rooms: often under-specified
Utility rooms are frequently fitted with an undersized fan because they're treated as an afterthought compared to kitchens and bathrooms, but the required rate (30 l/s intermittent) is the same as a kitchen hood positioned at the hob — utility rooms generate significant moisture from washing machines and tumble dryers venting into the room, and the extract requirement reflects that.
Duct design and why the rated fan number isn't the whole story
A fan's box states its free-air rating — the flow rate achieved with no duct resistance at all. Real installations always have some resistance: duct length, bends, external grilles, and backdraught shutters all reduce the delivered airflow below the free-air figure.
Practical rules of thumb for keeping delivered flow close to rated flow:
- Use rigid duct for the main run wherever possible; limit flexible duct to short connection sections (ideally under 1m) — flexible duct has significantly higher resistance per metre than rigid.
- Treat each 90° bend as adding roughly 1.5m of equivalent straight-duct resistance when assessing whether a fan is adequately sized for the route.
- For cold-zone duct runs (loft spaces, external wall cavities), use insulated duct to prevent condensation forming inside the ductwork itself — uninsulated flexible duct in a cold zone is a common defect that causes dripping inside the loft.
- Where the calculated route resistance is significant, specify a higher-capacity fan (or in-line centrifugal unit) rather than accepting reduced performance from an axial fan rated only just above the minimum.
Commissioning: proving the rate on site, not assuming it
Approved Document F requires commissioning evidence for new and replacement ventilation systems — this is not paperwork for its own sake, it's the only reliable way to confirm the installed system actually meets the required extract rate given the real duct route, not the fan's catalogue figure.
The standard method is a vane anemometer reading taken at the extract grille, converted to a flow rate using the grille's known free area, and recorded against the room and the required minimum. Build in a margin — aim for 10–15% above the regulatory minimum at commissioning, since fan performance can degrade slightly over time as impellers pick up dust and grease.
When existing rooms need reassessment
Part F applies most clearly to new work — new bathrooms, new kitchens, kitchen extensions, and any new or replacement ventilation system. In existing dwellings undergoing renovation, a like-for-like fan replacement of equivalent or better performance is generally compliant without a full reassessment. However, certain triggers should prompt a fresh look at the extract rate:
- An existing fan rated below the current minimum (common in pre-2000s installations, which were designed to older, lower ADF figures) being replaced — the replacement should meet the current 2021 figures, not match the old, non-compliant one.
- A loft conversion or extension that changes the room's use or adds a new wet room.
- Visible mould or condensation, which typically indicates the existing extraction is inadequate regardless of what it was originally designed to — this is the point to recommend an upgrade to the customer rather than a like-for-like swap, with the difference in scope and cost explained clearly.
Frequently Asked Questions
What's the difference between the intermittent and continuous figures?
Intermittent extract runs only when the room is in use (triggered by a light switch, humidity sensor, or occupancy sensor) plus a run-on period, and must meet the higher of the two rates (e.g. 15 l/s in a bathroom) during that active period. Continuous extract runs constantly at a lower background rate (e.g. 8 l/s in a bathroom) and is typically boosted to the intermittent-equivalent rate during and after moisture-generating activity. Continuous systems (MEV, MVHR) are increasingly the default in new-build and higher-airtightness renovation work because they manage condensation risk around the clock rather than only when someone remembers to switch the fan on.
Does a WC with no bath or shower need mechanical extract at all?
Yes, if it has no openable window, or as standard new-build practice even where a window is present — the minimum figure is 6 l/s intermittent. If the WC has an openable window and building control accepts natural ventilation as sufficient for that specific room in that specific project, mechanical extract may not be mandated, but this should be confirmed with the relevant Building Control body for the job rather than assumed, since practice varies.
My fan's box says 90 l/s — does that automatically satisfy a 60 l/s kitchen requirement?
Not automatically. The 90 l/s figure is almost certainly the fan's free-air rating with zero duct resistance. Once installed with real ductwork, bends, and an external grille, the delivered flow at the room could be meaningfully lower. Specify with a safety margin above the regulatory minimum, and verify the actual delivered flow with an on-site airflow reading at commissioning rather than relying on the box figure.
Do these figures apply to non-domestic buildings too?
No — Approved Document F Volume 1 (Dwellings) sets these specific figures for homes. Non-domestic buildings (offices, commercial kitchens, etc.) are covered by Approved Document F Volume 2, which uses a different methodology (often based on occupancy and CIBSE guidance rather than these fixed per-room l/s figures) and should not be used interchangeably with the domestic figures in this article.
Can I use these same extract rates for a loft conversion en-suite?
Yes — a loft conversion en-suite containing a bath or shower is assessed the same as any other bathroom: 15 l/s intermittent or 8 l/s continuous, with a 15-minute run-on timer if intermittent. The duct route in a loft conversion is often the more challenging part of the job (longer runs, more bends to reach an external wall or roof termination), so pay particular attention to duct sizing and insulation in cold zones to actually deliver the rated flow.
Regulations & Standards
Approved Document F (2021 edition) — Ventilation: Volume 1 Dwellings (in force from 15 June 2022)
BS EN 13141 — Performance testing of ventilation components and products for residential buildings
BS 5250:2021 — Code of practice for control of condensation in buildings
CIBSE TM61 — Ventilation commissioning guidance referenced in ADF 2021 commissioning requirements
BS 5422:2009 — Method for specifying thermal insulating materials for ducts (relevant to cold-zone duct insulation)
GOV.UK — Approved Document F (2021) — full text of the current revision
NHBC Technical Guidance — Ventilation — practical guidance on ADF 2021 compliance
BRE Group — Ventilation in Housing — BRE Digest 498 and related research referenced by ADF
part f ventilation — full ventilation strategy guide: Systems 1–4, whole-dwelling background ventilation, MVHR design and commissioning
bathroom ventilation — bathroom-specific extract fan guidance including zones and humidity control
bathroom extractor fan guide — bathroom fan installation detail, dMEV vs intermittent, BS 7671 zone interaction
kitchen extraction ventilation — kitchen-specific extraction detail including duct sizing and recirculating hood pitfalls
extractor fan not working — diagnostic decision tree for extract fan faults
extractor fan installation pricing guide — pricing guide referencing these extract rates in a real quote