UK Kitchen Extraction Rules: Part F Ventilation Guide

Quick Answer: Building Regulations Approved Document F (England, 2021 edition) requires mechanical extraction in every kitchen with a cooking facility. The minimum intermittent extract rate is 30 L/s if directly above the hob, or 60 L/s elsewhere in the kitchen. Continuous extraction may be used at lower rates (13 L/s minimum). Ducting should be the minimum length possible, ideally <3m with no more than two bends, and discharge to outside air via a fixed external grille. Recirculating hoods do not meet Part F — there must be ducted extraction to outside.

Summary

Kitchen extraction does two jobs: removes cooking smells and moisture that would otherwise condense on walls and cause mould, and removes combustion products from gas hobs and any flueless gas appliances. Under Approved Document F (2021), all new and refurbished kitchens require mechanical extraction designed to specific rates.

Most domestic kitchens use an over-hob extractor hood (cooker hood). These come in two types: ducted (extracts to outside) and recirculating (filters through charcoal and returns to the room). Only ducted extraction meets Part F for new build and the extension of existing kitchens. Recirculating hoods are sometimes acceptable for replacement-like-for-like in existing kitchens but Building Control will normally require an additional wall fan.

The ducting matters as much as the hood. A "1000 m³/h" hood with cheap flexible 100mm corrugated duct and 4 bends might deliver 200 m³/h to the outside — failing the regs and leaving the customer with greasy ceilings. Specifying and installing the duct correctly is half the job.

Key Facts

Quick Reference Table

Spending too long on quotes? squote turns a 2-minute voice recording into a professional quote.

Try squote free →
Kitchen Type Intermittent Rate (L/s) Continuous Rate (L/s)
Kitchen — extract above hob 30 13
Kitchen — extract elsewhere 60 13
Utility room 30 8
Bathroom 15 8
WC (separate) 6 6
Open plan kitchen-diner 60 (kitchen) + room volume calc 13+
Duct Configuration Equivalent Extra Length
Standard 90° bend +1.0m
Long radius 90° bend +0.5m
45° bend +0.5m
Flexible duct (per 1m) +0.3m vs rigid
External grille (cowl with backdraft flap) +1.0m

Detailed Guidance

Selecting the cooker hood

Three primary hood types in UK kitchens:

The published "extraction rate" on the box (m³/h or L/s) is the maximum free-air flow with no duct attached. Real-world delivered flow is typically 50–70% of the rated figure after duct losses. Sizing rule of thumb: choose a hood rated at least 50% above the regulatory requirement.

For a 30 L/s (108 m³/h) requirement, specify a 200–250 m³/h+ hood; for 60 L/s (216 m³/h), specify 400 m³/h+. Larger and more powerful motors give margin for less-than-perfect duct runs.

Duct sizing

The first principle: never reduce the duct below the hood spigot diameter. A common error is fitting a 150mm spigot hood and ducting it to a 100mm wall vent — the wall vent becomes the limiting factor and flow drops dramatically.

Equivalent areas:

For 60 L/s and above, 150mm round (or equivalent rectangular) is the minimum. Many manufacturers now ship hoods with 150mm spigots specifically to meet ADF rates.

Duct routing

The shortest, straightest run to outside air. Critical rules:

  1. Minimise bends — every 90° bend costs ~1m of equivalent length
  2. Use rigid duct where possible — galvanised steel or rigid plastic
  3. Flexible duct only at the hood connection (max 600mm) and at the external grille
  4. No 180° bends or reverse turns
  5. Duct sloped slightly down to outside (1:50) so condensation runs out
  6. Insulate ducts running through cold roof spaces to prevent condensation drips
  7. Seal all joints with aluminium tape or duct silicone — not standard duct tape (degrades in heat)

Discharge to outside

The duct must discharge to outside air via a fixed external grille or cowl. Options:

External grille types:

Never discharge to a roof void, ceiling void, eaves overhang or any internal space — moisture damage will follow.

Make-up air

When extraction is running, air must enter the building somewhere. In modern airtight homes (post-2010 build), there is rarely enough natural infiltration to make up 60 L/s. This causes:

Provide make-up air via:

For powerful extract rates (>60 L/s) in airtight homes, consider a balanced MVHR system as part of the kitchen design.

Gas hob requirements

BS 5440-2 requires gas hob installations to have a dedicated openable window or permanent ventilation in the room. For an open-plan kitchen, the volume calculation applies. The cooker hood does not replace this — even if the hood is extracting, the room still needs combustion air.

Continuous vs intermittent

Two strategies allowed under ADF:

Continuous gives better overall air quality and is required in many new builds for compliance with the overall whole-dwelling ventilation rate. Many new build kitchens have both: an MVHR taking continuous background extract, plus a separate cooker hood for high-rate cooking extract.

Common installation faults

Fault Consequence Fix
100mm duct on 150mm hood Extraction rate halved Re-pipe to 150mm or hood-matched size
Flexible duct on the whole run 30%+ loss per 3m Use rigid duct, flexible only at terminations
Joints sealed with brown tape Tape degrades, joint blows Aluminium foil tape or duct silicone
Duct discharges into roof space Moisture condenses on rafters Extend duct to external grille
External grille blocked by mesh Reduces flow significantly Coarser mesh or no mesh (vermin guard only at hood end)
No trickle vents Backdraft from flueless gas Install vents to ADF specification
Recirculating hood used as compliance Doesn't meet ADF Add ducted extract; consider wall fan as backup

Frequently Asked Questions

Is a recirculating hood compliant with Part F?

In general no, for new build and extensions. Recirculating hoods filter air through a charcoal cartridge and return it to the room — they do not extract moisture or combustion gases. For Part F compliance you need ducted extraction. The exception is a like-for-like replacement of an existing recirculating hood in a kitchen that already has alternative ventilation.

Can I duct through a cold loft space?

Yes, but insulate the duct to prevent condensation drips. Use pre-insulated flexible duct (e.g. Manrose ALD150) or wrap a rigid duct with 25mm mineral wool, foil-faced. The duct should be sloped slightly downward toward the outside grille so any condensate that does form drains out.

What's the maximum duct run for a 60 L/s hood?

3m total equivalent length is the practical maximum for a standard motor. Add bends as ~1m each. If your physical route is 4m straight with two bends (equivalent 6m), the hood rate will drop below 60 L/s. Either re-route (shorter), upsize the duct to 175mm or 200mm, or specify a higher-rated hood.

How do I test the actual extraction rate?

Use an anemometer at the grille. Multiply the average air velocity (m/s) by the grille free area (m²) to get flow in m³/s. Multiply by 1000 to get L/s. For commissioning, take readings at multiple points across the grille and average.

Does Part F apply if I'm just replacing the hood?

If you're replacing like-for-like (ducted to ducted), no notifiable work occurs and Part F doesn't trigger. If you're changing the type (e.g. installing ducted where there was no extraction), or if part of wider refurbishment, then Part F applies and the installation must meet the rates.

Regulations & Standards