Summary

Bathroom and kitchen extractor fans fail more often than any other domestic ventilation product. They run wet, dusty, and unattended for years; the failure rates climb sharply after 8 years. A call-out for "the fan's stopped" is usually a 30–60 minute diagnosis followed by either a £40 cleanout or a £180–£280 replacement.

This article is a structured fault tree covering intermittent fans (timer or humidistat triggered, the most common UK domestic type), continuous-running fans (dMEV — decentralised mechanical extract ventilation), and centralised MEV systems. It covers the safety procedure for isolation, the diagnostic logic, the common physical failure points, and the regulatory environment for replacement (Part F ventilation rates, Part P electrical notification, Part L energy efficiency on replacement).

The temptation is to replace any unresponsive fan immediately ("the motor's gone"). Diagnose first — the call-out fee plus a £45 minute spent checking the switched live and the outside grille often saves the customer £250 in needless replacement and earns repeat business.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Symptom Most likely cause Fix
Fan dead — no noise, no air Power isolated OR module failed Check isolator, voltage-test, replace module/unit
Fan hums but doesn't spin Motor seized OR capacitor failed Replace fan (motor not serviceable)
Fan spins but no air at outside grille Ducting blocked OR outside grille seized Clear duct, free grille, check flap
Fan runs but very weak airflow Blade fouled, duct partially blocked, leaky duct Clean blade, inspect duct, seal joints
Fan won't run on light switch (intermittent type) No switched live (only permanent L wired) Re-wire switched live from light
Fan won't turn off Humidistat triggering on damp loft air, timer module stuck Check humidistat setting, replace module
Fan noisy / rattling Bearings failing, blade unbalanced, mounting loose Replace fan (bearings rarely serviceable)
Fan dripping water inside room Condensate from cold loft ducting Add condensate trap, insulate duct
New fan trips RCD on power-up Wiring fault (N-E short, motor winding fault) Re-test, replace fan if motor faulty
Fan rattles when off (windy day) Outside grille flap loose Replace external grille / fit non-return flap

Detailed Guidance

Safety first — isolation procedure

Before opening the fan body or working on the wiring:

  1. Identify the means of isolation. For a bathroom fan, this is the triple-pole isolator (typically a 3-pole rotary switch on the wall outside the bathroom, in the loft, or in the airing cupboard).
  2. Switch off at the isolator.
  3. Verify dead with an approved voltage indicator — test L–N, L–E, N–E on both the permanent and switched live conductors.
  4. Lock off if practical (small isolation tag with the customer's name).
  5. Only then remove the fan cover.

If you cannot find the isolator, switch off the lighting circuit at the consumer unit (the fan is almost always wired off the lighting circuit) and re-verify. If still live, isolate the whole dwelling at the main switch.

Decision tree

Extractor fan not working — start here
│
├── Is anything happening when the trigger is on (light, switch, humidistat)?
│   │
│   ├── No sound, no movement
│   │     ├── Check isolator switched ON
│   │     │     ├── Was off → switch on, test → working? Done.
│   │     │     └── Was on → continue
│   │     ├── Isolate, open fan, voltage-test at fan terminals
│   │     │     ├── No voltage on permanent L → upstream supply fault
│   │     │     │     → trace lighting circuit / fuse / isolator
│   │     │     ├── Voltage on permanent L, none on switched L → switch / wiring fault
│   │     │     │     → check light switch, check wiring from switch to fan
│   │     │     └── Voltage present on both → fan module failed
│   │     │           → replace module OR replace fan
│   │
│   ├── Humming but not spinning
│   │     ├── Capacitor or motor winding fault
│   │     └── Fan is not field-serviceable → replace
│   │
│   ├── Spinning but no air at grille outside
│   │     ├── Check outside grille — flap stuck shut, debris, paint sealed
│   │     │     → clear / replace external grille
│   │     ├── Check ducting — disconnect at fan, blow air through
│   │     │     ├── Blocked solid (lint, mortar, bird nest) → clear
│   │     │     ├── Partial blockage → clear, inspect length
│   │     │     └── Water in duct → cold loft condensation, fit condensate trap, insulate
│   │     └── Duct OK → blades fouled with dust → clean
│   │
│   └── Spinning but weak airflow
│         ├── Blade caked with dust → strip, wash, refit
│         ├── Duct partially blocked OR over-long
│         │     → Inspect duct run, replace flexible with semi-rigid for length >3m
│         ├── Duct leaking at joints (negative pressure loss)
│         │     → Seal joints with foil tape or jubilee clips
│         └── Fan rated below required Part F rate
│               → Upgrade to higher-rated fan (8 l/s bathroom, 15 l/s utility/wet room minimum)
│
└── Won't turn OFF
    ├── Humidistat triggering on ambient humidity → adjust setpoint
    ├── Timer module stuck → power-cycle, then replace module
    └── Wiring fault (switched L permanently live) → re-trace

Wiring — permanent L, switched L, and neutral

Most modern bathroom fans need three conductors plus earth:

A common fault on older installations is that only the switched live is wired (no permanent live). The fan runs while the light is on but the timer overrun doesn't work because the timer needs permanent power. Fix: run a permanent live from the lighting circuit junction box to the fan.

For a fan with humidistat (no light-switch trigger), only permanent L and N are needed; the humidistat does the switching internally.

For a triple-pole isolator: switches all three (L, SL, N) at once. Required for any bathroom fan circuit per BS 7671 to give a complete means of isolation.

Intermittent vs dMEV vs MEV — what to specify on replacement

If the existing fan is an intermittent (runs on light switch / humidistat / timer):

If the customer wants better long-term ventilation and reduced condensation/mould, upgrade to dMEV:

Centralised MEV (one unit serving multiple rooms via ducting in the loft) is a whole-house refurb decision, not a like-for-like fan replacement.

Cooker hood (kitchen) specifics

Kitchen extract requirements differ from bathrooms:

If a customer reports "kitchen extractor not working" and it's a recirculating hood, the carbon filter is often the culprit (saturated, blocked). Replace filter (£10–£30) before condemning the unit.

A ducted hood with weak airflow is usually duct blockage (grease build-up in the metal ducting), an outside grille fouled with cooked-on grease, or the filter under the hood blocked solid.

Common physical faults

Replacement: Part P, Part F, Part L summary

For a domestic bathroom like-for-like replacement, the only paperwork is the customer's invoice. No notification, no certificate beyond the install commissioning.

Frequently Asked Questions

Can I replace a fan myself without Part P notification?

If you're a competent person within the dwelling (homeowner) and the replacement is like-for-like on the existing circuit, yes — Part P does not require notification for replacement of accessories on existing wiring. If you create a new circuit or run new cable to a new fan position, Part P applies and the work must be notified.

Why does my fan run on after the light is off?

This is the timer overrun, an intentional feature. Most fans run for 5–25 minutes after the switched live drops to clear remaining humidity. Adjust the overrun on a small potentiometer or DIP switch on the fan body (consult the manual).

How much air should an extractor move?

Part F minimums: bathroom 8 l/s, WC 6 l/s, utility 8 l/s, kitchen with hood 30 l/s, kitchen without hood 60 l/s. These are minimum rates and the fan should be rated equal to or higher. Boost rates on humidistat-controlled fans are typically 15–25 l/s.

Why does the fan drip water onto the bathroom ceiling?

Condensate. The fan duct runs through a cold loft, warm moist bathroom air enters the duct, cools, condenses to water on the duct walls, and drips back. Fix: insulate the duct with proprietary ducting lagging, or fit a condensate trap at the lowest point of the duct run (it catches water in a small reservoir that evaporates between uses).

Does a window in the bathroom mean I don't need a fan?

For new installations under Part F, an openable window of adequate area (1/20th of floor area is the historic rule) can sometimes substitute for mechanical ventilation, but most new builds and refurbs install a fan regardless. For a wet room or shower room without an openable window, mechanical extraction is required.

My fan is rated higher than Part F — why is the room still steamy?

Likely a duct problem. Specified airflow is at zero static pressure; with ducting added, real-world flow drops 30–60%. Long runs of flexible ducting, sharp bends, and partial blockages collapse the real flow rate. Use semi-rigid or rigid duct, minimise bends, keep runs short.

Regulations & Standards