Summary

Ventilation is the second most misunderstood building regulation after insulation, and the 2021 revision of Approved Document F significantly increased the requirements — particularly for airtight new-build dwellings where inadequate ventilation causes condensation, mould growth, and poor indoor air quality.

The fundamental principle of Part F is a two-tier system: background ventilation (continuous low-level air exchange through trickle vents and purpose-provided openings) plus rapid ventilation (openable windows or extract fans for wet rooms and cooking areas). For new buildings, the whole-dwelling ventilation rate must be calculated and documented. For existing dwellings, when ventilation is modified or replaced, the replacement must meet current standards.

For tradespeople, Part F is most relevant when: fitting or replacing kitchen extractor fans or cooker hoods, installing bathroom extract fans, fitting replacement windows (trickle vent requirements), and installing whole-house MVHR systems. Understanding the minimum extract rates and background ventilator requirements prevents costly remedial work.

Key Facts

Quick Reference Table

Need to quote compliant work? squote includes relevant regulations in your quotes.

Try squote free →
Room Minimum Extract Rate (Intermittent, Table 1.1) Minimum High Rate (Continuous, Table 1.2)
Kitchen (cooker hood extracting to outside) 30 l/s 13 l/s
Kitchen (no hood, or hood not extracting to outside) 60 l/s 13 l/s
Utility room 30 l/s 8 l/s
Bathroom (with bath or shower) 15 l/s 8 l/s
Sanitary accommodation (WC / cloakroom) 6 l/s 6 l/s
System Description Typical Application
System 1 Natural ventilation: intermittent extract fans + background ventilators Existing dwellings and less airtight new build only (design air permeability >5 m³/(h·m²), as-built >3)
System 2 Passive stack ventilation (PSV) Legacy only — not covered as a system type in ADF 2021
System 3 Continuous mechanical extract (MEV / dMEV) All dwellings, including airtight new build
System 4 Balanced MVHR (supply + extract) All dwellings; Passivhaus, high-performance new build, flats

Detailed Guidance

System 1 — Intermittent Extract Fans

System 1 is the most common domestic ventilation strategy. It relies on:

Fan specification: For a bathroom, the minimum 15 l/s means the fan's certified flow rate (from the manufacturer's data sheet, measured at a typical installed resistance) must be ≥15 l/s. Do not rely on the nominal rating alone — measure or verify against resistance in the installed duct run.

Run-on timer: ADF paragraph 1.51 requires a 15-minute overrun only where the room has no openable window — the classic internal bathroom or internal WC. In rooms with an openable window a run-on timer is good practice rather than a requirement. Where automatic (e.g. humidity) controls are fitted, ADF paragraph 1.50 requires a manual override so the occupant can switch the fan on or off. Note that humidity sensors should not be used in sanitary accommodation, where odour rather than moisture is the main pollutant.

Kitchen extract: A cooker hood that extracts to the outside must achieve at least 30 l/s (and should span at least the full width of the cooker, mounted 650–750mm above the hob unless the manufacturer specifies otherwise). Where there is no hood, or the hood only recirculates, the kitchen extract must achieve at least 60 l/s. This is why a 100mm (4 inch) fan in a kitchen is marginal — a 150mm (6 inch) fan delivering 60 l/s is preferred. Extract terminals and fans other than cooker hoods should be as high as practicable and no more than 400mm below the ceiling.

Duct length and resistance: Centrifugal fans in extract fans work against the duct resistance. A long duct run (over 3m) with bends will significantly reduce flow rate. For each 90° bend, add an equivalent length of 1.5m to the duct. For metal duct (150mm diameter) with a 5m run and two bends (8m equivalent), the actual flow rate may be 25% lower than rated. Use larger-diameter duct or a more powerful fan to compensate.

Recirculation vs ducted cooker hoods: A recirculation cooker hood does NOT provide Part F ventilation — it filters and recirculates kitchen air without removing moisture. Ducted extraction is required for Part F compliance. For retrofit where ducting is impractical, a System 1 compliant alternative must be provided.

System 4 — MVHR (Mechanical Ventilation with Heat Recovery)

MVHR is increasingly common in new-build housing (especially detached and semi-detached housing where duct runs are shorter) and in Passivhaus or EnerPHit retrofit projects.

How it works: A central unit with two fans draws stale air from wet rooms (kitchen, bathroom, WC) and supplies fresh air to habitable rooms (bedrooms, living rooms). A heat exchanger in the unit transfers 75–93% of the heat from extract air to supply air — avoiding the heat loss penalty of conventional extract ventilation.

Design requirements:

Duct design:

Commissioning certificate: ADF 2021 requires a commissioning certificate for MVHR systems, which must be provided to the building control inspector on completion.

Trickle Vents (Background Ventilators)

Background ventilators allow a low level of continuous air exchange even when windows are closed. The most common form is the trickle vent in a window frame — a small controllable slot ventilator, typically 4000–10,000 mm² equivalent area (EA), in the window head or frame. ADF sizes ventilators by equivalent area, not free area, measured to BS EN 13141-1.

When do trickle vents apply?

Part F and window replacement: Replacing a window is controlled building work, notifiable either through a competent person scheme (FENSA, CERTASS) or to the building control body. Part L (energy efficiency) and Part F (background ventilation) both apply. A window installer who removes trickle vents on replacement windows without providing equivalent background ventilation is creating a Part F defect.

Part F and Existing Dwellings (Renovation)

In existing dwellings, Part F applies to replacement ventilation systems (new extract fans replacing old ones) and to new extensions that create new habitable or wet rooms. The key rule: any new or replacement ventilation element must meet ADF 2021 standards.

For renovations and extensions:

Note: Part F does not typically require wholesale ventilation upgrades in a like-for-like renovation. The trigger is disturbance or change — replacing like with like (e.g., new extract fan of equivalent or better performance) is compliant.

Frequently Asked Questions

Does a new bathroom in an extension need an extract fan if there's an openable window?

Yes for a bathroom. ADF paragraph 1.47 requires intermittent extract fans in all wet rooms, and a bathroom must achieve 15 l/s. An openable window provides purge ventilation but does not substitute for extract ventilation in a bathroom. A 15-minute run-on timer is only mandatory where the room has no openable window (ADF 1.51), though it is good practice everywhere.

The one exception is sanitary accommodation (a WC or cloakroom without a bath or shower): ADF paragraph 1.49 allows the extract rate to be met using windows by following the purge ventilation guidance instead of fitting a fan.

I've installed a new cooker hood that only recirculates. Is this compliant?

No. ADF 2021 Diagram 1.2 states explicitly that a recirculating cooker hood on its own does not provide a means of ventilation that complies with Part F. Recirculation hoods filter cooking fumes and odour but do not remove moisture or provide air exchange. Where the hood does not extract to the outside, the kitchen extract rate is 60 l/s, not 30 l/s — so a separate ducted extract fan in the kitchen delivering 60 l/s is needed.

What's the difference between Part F and Part L on window replacement?

Approved Document L Volume 1: Dwellings (2021 edition, the current in-force version — the old "Part L1B" naming was retired in 2021) deals with the thermal performance of the replacement window: a whole-window U-value of 1.4 W/m²K or better, or WER band B. Part F deals with background ventilators. Both apply to replacement windows. FENSA or CERTASS self-certification covers both — the installer must confirm compliance with both parts. Removing trickle vents on replacement windows without equivalent provision is a Part F defect, and so is fitting replacement windows with no ventilators where the original windows also had none (see ADF 3.15 above).

My MVHR unit needs servicing. What's involved?

MVHR servicing typically every 12 months:

  1. Clean or replace supply air filters (G4/F7 filter pads)
  2. Clean heat exchanger core (remove and brush or wash according to manufacturer's guidance)
  3. Clean extract grilles and supply diffusers
  4. Check and clean condensate drain from heat exchanger
  5. Check and clean external air intake and exhaust terminals
  6. Verify airflow rates using an airflow measurement hood (commissioned units should be re-verified) Record the service in a commissioning/service log.

Regulations & Standards