Gas Interlock Systems for Commercial Kitchens: MLG and MES Specification, Commissioning and BS EN 203

Quick Answer: A commercial kitchen gas interlock proves the extract (and where required the make-up air supply) ventilation is running before it allows gas to flow to the catering appliances, shutting the gas off if airflow fails. The two common build types are a Manual Latching Gas valve system (MLG) — manual reset, simplest and most robust — and a Monitored/Electronic System (MES/automated) with current or air-pressure proving and electronic control. Specification follows BS 6173 (commercial catering gas installation), the appliances follow BS EN 203, and ventilation interlock is guided by IGEM ventilation guidance (IGEM/UP/19). All work must be done by a Gas Safe registered engineer on the commercial catering scope (COMCAT).

Summary

This article is the specification and commissioning companion to the interlock systems reference. Where that article explains the solenoid valve, airflow proving and BS 6173 basics, this one takes the commercial-kitchen specifier's and commissioning engineer's angle: how to choose between an MLG and an MES build, how the air-proving is achieved on extract and supply fans, where BS EN 203 sits relative to BS 6173, and exactly what a Gas Safe engineer checks at commissioning and at the annual test.

The principle behind every interlock is simple: a gas catering range or oven dumps combustion products and heat into the kitchen, and if the extract is not running those products — including carbon monoxide — accumulate. The interlock makes the gas supply conditional on proven ventilation. No proven airflow, no gas. It is, in effect, an engineered control that removes the human error of staff lighting the range with the extract switched off.

The common confusion is treating "interlock" as one product. In practice there is a spectrum from a basic manual-latching valve that you physically push to open (and that drops shut on power loss) through to fully monitored electronic systems that prove both extract and supply fans by current sensing or air-pressure switch and integrate CO detection. Choosing the right level for the kitchen — and commissioning it so the proving genuinely reflects real airflow, not a fan merely spinning — is the engineer's job. This article assumes commercial catering competence (COMCAT) and cross-references commercial gas safety.

Key Facts

Quick Reference Table

Need to quote gas work? squote generates accurate, professional quotes fast.

Try squote free →
System type Reset Proving method Best suited to
MLG (manual latching gas valve) Manual push/latch Simple — single proving input Small/single-zone kitchens; robust, low-maintenance
MES (monitored electronic) Manual reset, electronic Current + air-pressure on extract & supply Larger kitchens, multi-zone, CO integration, fault logging
Proving device What it confirms Strength Weakness
Air pressure switch Air is actually moving in the duct Proves airflow directly Needs correct setpoint, clean tappings
Current sensor (CT) Fan motor drawing running current Simple, no duct penetration Spinning ≠ airflow (belt/filter fault fools it)
Combined CT + pressure Motor running AND air moving Most robust More components to commission
Interlock component Function Typical spec
NC gas solenoid/latching valve Shuts gas on power/proving loss Sized to diversified demand, gas-rated
Extract proving switch Enables gas when extract proven Differential pressure 5–20 Pa (adj.)
Supply proving switch Enables gas when make-up air proven On supply fan where fitted
Controller Logic, fault indication, reset 24 V DC, IP-rated, manual reset
CO detector (optional) Trips interlock on high CO BS EN 50291, relay output
Indicator lights Run / fault / gas-on status LED panel

Detailed Guidance

MLG vs MES — choosing the build

The decision is about kitchen scale, ventilation complexity and the level of monitoring the operator needs:

A useful rule: specify the simplest system that genuinely proves the ventilation serving the gas appliances. Over-specifying a small kitchen with a complex MES often just creates maintenance and nuisance-trip problems.

Air-proving on extract and supply

The whole safety case rests on the proving genuinely reflecting real airflow:

   Commercial kitchen interlock logic
   ----------------------------------
   Power on
     |
   Extract fan proven? (pressure switch / CT)
     no  -> gas valve CLOSED, fault indicated
     yes -> continue
     |
   Supply fan fitted? 
     yes -> supply proven?
              no  -> gas valve CLOSED, fault indicated
              yes -> continue
     no  -> continue
     |
   CO detector fitted and below threshold?
     no  -> gas valve CLOSED, requires manual reset
     yes -> GAS VALVE OPEN (latched)
     |
   Any proving lost OR power lost OR CO high
     -> gas valve CLOSES (fail-safe)
     -> MANUAL RESET required to restore

Where BS EN 203 fits versus BS 6173

These two are frequently confused:

As the installing engineer you verify the appliances are suitable (BS EN 203 approved) and install them to BS 6173, with the interlock and ventilation designed per the IGEM ventilation guidance (IGEM/UP/19). Don't cite BS EN 203 as the source of the interlock requirement — that comes from BS 6173 and the IGEM ventilation guidance.

Commissioning sequence

Commissioning is where an interlock is proven to actually work, not just be installed. A Gas Safe COMCAT engineer should:

  1. Confirm the install — correct NC gas valve sized to the diversified demand, ECV in place and accessible upstream, proving devices fitted on the correct fans, controller and reset accessible.
  2. Set the extract proving — with the extract running normally, set the air-pressure switch so it proves at normal airflow and drops out when airflow falls below safe (test by partially blocking the canopy/filters).
  3. Set the supply proving (if fitted) — confirm gas is only enabled with both extract and supply proven.
  4. Test the trip — with gas enabled, stop the extract fan; confirm the gas valve closes promptly.
  5. Test manual reset — confirm the system requires a deliberate manual reset and does not auto-restart.
  6. Test CO integration (if fitted) — apply CO test gas; confirm the interlock trips above threshold.
  7. Verify appliance performance — check working pressures and that the solenoid is not throttling supply (gas rate / pressure with all appliances firing).
  8. Document — record the commissioning, settings, and test results; the interlock test forms part of the commercial gas safety record. Submit the Gas Safe notification within the required period.

Annual test and maintenance

The interlock is a safety-critical control and must be re-tested at least annually alongside the commercial gas safety inspection:

Frequently Asked Questions

What is the difference between an MLG and an MES interlock?

An MLG (Manual Latching Gas valve system) is the simplest build: a normally-closed gas valve held open while ventilation is proven, with a manual reset after any trip and no automatic restart. An MES (monitored electronic system) adds an electronic controller, current and air-pressure proving on both extract and supply fans, fault indication, optional CO integration and logging. MLG suits small single-zone kitchens; MES suits larger, multi-zone or higher-monitoring installations. Both must use manual reset.

Is current sensing on the fan enough to prove airflow?

Not on its own. A current sensor confirms the fan motor is drawing running current, but a motor can run with a snapped belt, a blocked grease filter or a slipping coupling — current flows, but no air moves. A differential air-pressure switch proves air is actually moving and is the more rigorous method. Best practice is to prove airflow directly (pressure switch), or to combine current sensing with pressure proving.

Do I need to prove the supply (make-up air) fan as well as extract?

Where the kitchen has mechanical make-up air, yes. A large extract running without make-up air depressurises the kitchen, can pull combustion products back down other flues, and starves the space of replacement air. The interlock should prove both extract and supply running before allowing gas. If make-up air is purely natural (grilles/openings), only the extract proving applies — but verify the design with the IGEM ventilation guidance.

Does BS EN 203 require the interlock?

No. BS EN 203 is the appliance standard — it covers the safety and performance of the gas catering appliances themselves. The requirement for a ventilation interlock comes from the installation standard BS 6173 and the IGEM ventilation interlock guidance (IGEM/UP/19). You install BS EN 203-approved appliances to BS 6173 with the interlock specified per the IGEM guidance.

How often must a commercial kitchen interlock be tested?

At least annually, as part of the commercial gas safety inspection, by a Gas Safe engineer with the relevant commercial catering competence. The test covers proving, the gas-valve trip, the manual reset, and CO integration if fitted, and the results are recorded. The interlock must never be bypassed to keep the kitchen operating if it trips — the fault must be investigated and rectified.

Regulations & Standards