Summary

A sagging ceiling frightens customers more than almost any other building defect, and sometimes they are right to be frightened: a lath-and-plaster ceiling that has lost its key can weigh 30–40 kg per square metre and comes down with very little warning. More often the sag is a slow, harmless creep in old plasterboard that has been there for twenty years, or a bulge where a plumber once stood on the boards from the loft. The job on the first visit is to decide which it is, quickly and safely, before anyone stands under it or on top of it.

There are three families of cause and they look different. Fixing failure shows as a sag confined to one board or one bay between joists, with a crack along the joist line where the board has dropped away from its neighbour. Structural failure shows as a sag along a line, often running the full width of the room, or a general dish towards the centre, and it is usually accompanied by a floor above that bounces or slopes. Water damage shows as staining, soft or powdery plaster, a sag that is localised under a bathroom, tank or roof leak, and sometimes the characteristic tide mark of a leak that has dried out.

This guide gives a decision sequence, the checks to make from above and below, the thresholds at which repair stops being sensible and the ceiling has to come down, and the fixing specifications for the repair. For the leak itself see damp patch on ceiling diagnosis; for joist capacity and strengthening see joist installation and joist span calculator; for pricing a replacement see ceiling replacement pricing guide.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Sag pattern What you see Probable cause Urgency Fix
Patch between two joists, one board Crack along joist line, nail/screw heads showing Fixings pulled through or missed joist Low Refix with 38 mm screws into joist, tape and fill
Wide bulge, lath ceiling, moves when pushed Crazed cracks, dust from above, visible nibs sheared Lost key HIGH — prop Take down or secure and overboard
Straight-line dip across the room Floor above dips/bounces; sag follows one joist Undersized, notched, split or rotten joist Medium–high Expose joist, strengthen or replace
General dish to centre, several joists Loft heavily boarded and stored Ceiling joists overloaded Medium Remove load, strengthen (sister/bind) or accept
Localised sag under bathroom/tank Stain, soft or powdery plaster, tide mark Water Medium — may fall Stop leak, cut out and replace board
Sag at edge near wall Cracks at wall junction, coving open Joist bearing failed, wall plate rotten, or lintel movement High Investigate bearing and structure
Boards sagging evenly between all joists Loft insulation directly on board; 12.5 mm at 600 mm centres Long-term creep from wrong board spec Low Overboard with 15 mm or add noggins
Bulge round a light fitting or hatch Cut edges unsupported Missing noggins at opening Low Add noggins, refix
Cracks at every board joint, slight drop Tapers not filled/taped, adhesive-fixed board Poor original fixing Low Screw off, re-tape, skim

Detailed Guidance

The first visit: decide if it is safe

SAGGING CEILING — FIRST VISIT
│
├─ Lath and plaster or plasterboard?
│   (Tap: lath sounds dull and uneven; plasterboard rings hollow and even.
│    Look from the loft or at a hatch edge: laths visible = lath and plaster.)
│
├─ LATH AND PLASTER
│   ├─ Does it move under gentle hand pressure?
│   │    YES → Keep everyone out from under it. Prop with boards and
│   │          adjustable props. Plan take-down or secure-and-overboard.
│   │    NO  → Check from above for sheared nibs and plaster dust.
│   │          ├─ Nibs mostly intact → cosmetic; local repair possible.
│   │          └─ Nibs sheared over a wide area → secure or take down.
│   └─ Drop more than 10–15 mm from joist line? → treat as unsafe.
│
└─ PLASTERBOARD
    ├─ Sag confined to one bay/board, crack at joist line?
    │    → Fixing failure. Refix.
    ├─ Sag follows a straight line or whole room dishes?
    │    → Look above: joist size, span, notches, loft load, bearing.
    ├─ Stained, soft, crumbly, smells damp?
    │    → Water. Find and stop it, then replace wet board.
    └─ Textured coating? Pre-1985 property?
         → Do not sand or scrape until tested for asbestos.

Propping is cheap insurance. Two or three 2.4 m lengths of 18 mm ply or OSB under the bulge, held up with adjustable steel props or Acrow props on sole boards, spread the load and take the ceiling's weight off its remaining fixings. If the ceiling then has to be taken down, the props come away one at a time with the boards.

Lath and plaster: repair or replace

Lath and plaster ceilings fail by losing their key. Lime plaster was pushed between riven or sawn timber laths spaced about 6–10 mm apart; the plaster that curled over the back of the laths formed nibs, and the whole ceiling hangs from thousands of them. Vibration, water, age and a century of people walking across the floor above shear them. Once a proportion have gone, the remaining ones carry more load and fail faster. A ceiling that has been "fine for years" and then develops a bulge has reached that tipping point.

Three repair routes:

  1. Local repair where the detachment is small (under about 0.5 m²) and the surrounding ceiling is sound. Cut back to firm plaster, fix expanded metal lath or a piece of plasterboard to the laths or joists, and plaster in two coats. A lime-based or a gypsum bonding and finish system is acceptable depending on the building; in a listed building use lime.
  2. Secure and overboard where the ceiling has dropped but is still largely attached. Push the sagging plaster back to the joists and hold it with plasterboard screws through penny washers at about 300 mm centres into the joists, then fix 9.5 mm or 12.5 mm plasterboard across the joists with screws long enough to reach 25–30 mm into the timber (commonly 75–100 mm), then tape, fill and skim. This adds 8–9 kg/m² to a ceiling that is already heavy, so check the joists are sound and the bearings are good. It also lowers the ceiling by the board thickness and buries the coving.
  3. Take down and reboard where the key has gone over a large area, the plaster is water damaged, or the customer wants a flat ceiling. This is dusty, heavy work: a 16 m² room produces 500–700 kg of debris. Sheet everything, wear FFP3 masks (old plaster contains lime and often animal hair and dust from a century of use), and take the laths down as well so the new board sits directly on the joists. Add noggins where board ends fall between joists. This is the only option in a loft conversion or over a garage where the ceiling has to achieve 30 minutes' fire resistance.

In a listed building or conservation area, removing a historic lath-and-plaster ceiling may need listed building consent; check before quoting to take it down.

Plasterboard fixing failure

Plasterboard sags when it is no longer held to the joists. The most common causes are nails rather than screws, fixings that missed the joist (hitting it at an angle or into a gap), boards fixed to joists at 600 mm centres with 12.5 mm board, board ends left floating between joists with no noggin, and ceiling boards fixed with adhesive dabs or too few fixings during a quick refurbishment. Loft insulation laid directly on the back of the board adds a small, permanent, evenly spread load that over twenty years produces the gentle scalloping between joists that is so common in 1960s–1980s houses.

The repair is to find the joists (a pilot screw, a magnet on the existing fixings, or a look from above), push the board back up with a T-bar or a prop and a pad, and drive 38 mm plasterboard screws at 230 mm centres along each joist, keeping 13 mm from the board edges. Existing nail pops are driven below the surface or pulled, and a new screw set 50 mm away. Then tape the cracks with self-adhesive scrim or paper tape, fill in two coats, and either skim the area or sand and paint. Where boards have sagged between joists at 600 mm centres, add 47 × 50 mm noggins between the joists at mid-bay from above if there is access, or overboard with 15 mm board.

Joist problems

A sag that runs in a straight line, or a floor above that dips over the same line, is a joist talking to you. Expose it from above if there is a loft, or lift a board from the floor above, and check:

Anything beyond refixing a board or adding noggins is structural work. Sistering, flitching or replacing joists needs a Building Regulations application (Approved Document A) and, where it is a floor rather than a ceiling, an engineer's calculation to justify the repair.

Water damage

Wet plasterboard is replaced. The paper facing delaminates, the gypsum core softens and crumbles, and once dried it does not recover its strength. Cut back to firm, dry board at least 100 mm beyond the visible stain, check the joists and insulation above are dry (wet mineral wool must come out, as it holds water against the timber and against the back of the new board), find and stop the leak, and let the structure dry before closing up. Mould on the back of the board or on the joists is cleaned with a fungicidal wash. The source is usually a bathroom above (see shower leaking through ceiling), a roof or flashing failure, a tank or cylinder, or a pipe joint. A ceiling that sags and drips during rain and is dry otherwise is a roof problem; one that sags and is damp all the time is plumbing.

Frequently Asked Questions

Can I patch a sagging lath-and-plaster ceiling rather than replacing it?

Only if the lost key is confined to a small area and the rest is firm. Test the whole ceiling, not just the bulge: tap and push every square metre and check the nibs from above if you can. If the surrounding plaster is sound, cut back to firm edges, fix metal lath or board to the joists and laths, and plaster in. If the ceiling moves in several places or the nibs are sheared widely, a patch is wasted money because the next bulge appears next to it. Secure and overboard, or take down and reboard.

Is it safe to leave a slight sag in a plasterboard ceiling?

If the board is still attached, the sag is between joists rather than along one, and there is no staining or softness, it is a cosmetic defect and is not dangerous. It will slowly worsen if loft insulation sits on the back of 12.5 mm board at 600 mm centres. The cheap fix is to add noggins between the joists at mid-bay from above and screw the board up to them; the tidy fix is to overboard with 15 mm plasterboard and skim.

Why has the ceiling started sagging since the loft was boarded?

Because the ceiling joists were never designed for it. Traditional ceiling joists in a cut roof carry the ceiling, insulation and an occasional person; a boarded loft full of storage can add two to four times that load. The joists deflect, the plasterboard dips with them, cracks appear along the walls, and sometimes the ceiling joists pull on the rafter feet. Take the weight out, and if the customer wants loft storage, install a raised storage floor on new independent joists or a proprietary stilt system that spreads load to the walls, designed with the joist sizes checked.

Can I just screw plasterboard over the old textured ceiling?

Not until the texture has been tested for asbestos if the property is from before about 1985. Drilling and screwing through an asbestos-containing textured coating releases fibres and is work under the Control of Asbestos Regulations 2012. If the test is negative, overboarding is a sound method provided the old ceiling is secured to the joists first and the screws reach 25–30 mm into the timber. If positive, the work needs to be done by someone with the training and controls for non-licensed asbestos work, with the coating either left undisturbed and encapsulated or removed with appropriate controls.

Does a repaired ceiling need Building Control?

Replacing like-for-like plasterboard on an ordinary ceiling does not. Structural work to joists (sistering, flitching, replacing, altering) is controlled under Approved Document A and needs a Building Regulations application. A ceiling that forms part of a fire-resisting floor, such as under a loft conversion or over an integral garage, must be reinstated to a specification that provides the required 30 minutes under Approved Document B Volume 1, which usually means specific board types, thicknesses and fixing patterns rather than a single layer of standard 12.5 mm.

Regulations & Standards