Summary
Grant UK is one of the best-known names in UK off-mains-gas heating, having built its reputation on the Vortex oil boiler range before expanding into air source heat pumps with the Aerona3 monobloc and the HPiD/HPiD6 hydro-box (split) ranges. The Aerona3 is a common choice on Boiler Upgrade Scheme (BUS) installations replacing oil boilers in rural off-gas-grid properties, often installed by the same OFTEC-registered heating engineers who service Grant's oil range, which makes cross-brand familiarity with "how Grant present a fault" genuinely useful — see oil boiler fault codes grant for the equivalent oil-boiler diagnostic approach from the same manufacturer.
Unlike some heat pump brands whose fault-code architecture is shared across a huge international commercial air conditioning range (as with Daikin or Samsung), Grant's heat pump documentation is comparatively compact and specific to the Aerona3/HPiD platform itself. When a fault occurs, the remote controller in the house — the interface most engineers and customers interact with day-to-day — shows a flashing red LED on the ON/OFF switch, a warning triangle icon, and an alphanumeric fault code on its LCD screen. The outdoor unit's own terminal PCB also displays a code, which is useful when the remote controller itself is suspected of a fault or communication issue.
Note on code confidence: the fault codes below are drawn from Grant's own published Aerona3 series installation and servicing instructions. Grant's documentation is less exhaustively cross-referenced across third-party sources than for the market's longest-established heat pump brands, and the precise code list can vary between the original Aerona3, later Aerona3 R32 refrigerant revisions, and the HPiD/HPiD6 hydro-box models. Codes and descriptions not directly confirmed against the specific installed model's manual are marked **** — always check the data plate and the matching manual before ordering parts or condemning a component.
Key Facts
- Code format — an alphanumeric code, typically a letter followed by a digit (e.g. A0, A1, P1) or a fuse-reference code (CF1, CF3, CF4, CF6, CF7), shown on the remote controller LCD
- Displayed on — the in-house remote/command controller, with a flashing red LED on the ON/OFF switch and a warning icon; the outdoor unit's terminal PCB also carries its own display for on-site diagnosis
- A-series faults — confirmed in Grant's Aerona3 installation and servicing instructions: A0 (DC voltage/power supply error), A1 (discharge temperature error — discharge sensor, gas leakage, or abnormal compressor operation), A2 (DC current detection fault in the main PCB, often linked to a momentary power interruption such as a lightning strike), A3 (CT/current-transformer disconnection, causing abnormal compressor operation or excess-voltage protection to activate), A4 (AC current detection fault, again often linked to a momentary power interruption)
- P1 fault — reported in field/user diagnostic sources as a pump-related fault ****
- CF-series (fuse) faults — CF1, CF3, CF4, CF6, and CF7 relate to blown fuses protecting different circuits: the power supply, main PCB, fan motor, pump, and reactor respectively; the specific fuse rating differs by model (e.g. the HPiD6 range uses a 250V 15A fuse, HPiD10 a 250V 25A fuse) — always match the replacement fuse rating to the specific unit's data plate and manual, never assume a rating across models
- F-Gas Regulations — refrigerant recovery, leak testing, and recharge on the sealed circuit require F-Gas certification appropriate to the refrigerant fitted; do not open the refrigerant circuit without it
- R32 vs earlier refrigerant — later Aerona3 revisions use R32 refrigerant; confirm which refrigerant type is fitted from the data plate before any refrigerant-related diagnostic work, as handling requirements and A2L mildly-flammable classification considerations apply to R32
- MCS commissioning record — every MCS-installed Aerona3 should have a commissioning sheet recording refrigerant charge, pipe run length, and initial settings — useful reference when diagnosing charge-related faults
- Reset procedure — typically via the remote controller's own reset function, or by power-cycling the outdoor unit isolator; allow the manufacturer's specified time before re-power (check the specific model's manual rather than assuming a boiler-style reset timing)
- Exact code subset varies by model/generation — the Aerona3 monobloc, HPiD, and HPiD6 hydro-box ranges do not necessarily share an identical fault code table; always confirm against the installation and servicing manual for the exact model fitted
- OFTEC and MCS familiarity crossover — many Grant Aerona3 installations are carried out by engineers already OFTEC-registered from Grant oil boiler work; heat pump installation and servicing additionally requires MCS certification (for BUS grant compliance) and F-Gas certification for refrigerant-circuit work — OFTEC registration alone does not cover heat pump refrigerant work
- CF fuse faults are not refrigerant faults — a blown fuse on the power supply, PCB, fan, pump, or reactor circuit is an electrical fault, checkable and often fixable by a competent heating engineer without F-Gas certification, provided the underlying cause of the blown fuse (a shorted component) is also correctly diagnosed rather than simply replacing the fuse and re-energising
Quick Reference Table
Diagnosed the problem? Create a repair quote in minutes with squote.
Try squote free →| Code | Category | Likely Cause | F-Gas Required? |
|---|---|---|---|
| A0 | Power supply | DC voltage error | No |
| A1 | Discharge temperature | Discharge sensor fault, gas leakage, or abnormal compressor operation | Possibly — check sensor/wiring first, refer if refrigerant confirmed |
| A2 | Main PCB / DC current detection | Momentary power interruption (e.g. lightning), PCB fault | No |
| A3 | CT (current transformer) | CT disconnected, abnormal compressor operation, excess voltage protection | No, unless compressor fault confirmed |
| A4 | AC current detection | Momentary power interruption (e.g. lightning), supply fault | No |
| P1 | Pump-related | Circulating pump fault or flow issue — confirm exact definition against model manual | No |
| CF1 | Fuse — power supply | Blown fuse; check for underlying short before replacing | No |
| CF3 | Fuse — main PCB | Blown fuse; check for underlying short before replacing | No |
| CF4 | Fuse — fan motor | Blown fuse; check fan motor for locked rotor/short before replacing | No |
| CF6 | Fuse — pump | Blown fuse; check circulating pump for fault before replacing | No |
| CF7 | Fuse — reactor | Blown fuse; check reactor/inverter circuit before replacing | No |
This table reflects codes documented in Grant's published Aerona3 series installation and servicing instructions, cross-checked against field-reported troubleshooting sources where marked. Confirm the exact code list, and exact fuse ratings, against the specific model and generation's own manual before ordering parts.
Detailed Guidance
Fault-Finding Decision Tree
START: Grant Aerona3 showing fault code on remote controller
(flashing red LED, warning icon, alphanumeric code on LCD)
│
├─ STEP 1: Read the code from the remote controller AND check
│ the outdoor unit's terminal PCB display for a matching or
│ supplementary code
│
├─ STEP 2: Which category does the code fall into?
│ ├─ A-series (A0-A4) → go to POWER/COMPRESSOR branch
│ ├─ CF-series (fuse codes) → go to FUSE branch
│ ├─ P-series → go to PUMP branch
│ │ against specific model manual]
│ └─ Not listed above → consult the specific model's
│ installation and servicing manual directly
│
├─ POWER/COMPRESSOR BRANCH (A0-A4)
│ ├─ A0 (DC voltage) → check incoming supply voltage and
│ │ wiring at the outdoor unit isolator
│ ├─ A1 (discharge temperature) → STOP before assuming
│ │ refrigerant fault:
│ │ ├─ Check outdoor unit airflow/clearance
│ │ ├─ Check discharge sensor wiring/connector
│ │ └─ If airflow and wiring check out → F-Gas engineer
│ │ to check refrigerant charge and discharge pressure
│ ├─ A2/A4 (current detection) → check for recent lightning/
│ │ power interruption event; check supply quality; if
│ │ recurring without an obvious power event, suspect PCB
│ └─ A3 (CT disconnection) → check the current-transformer
│ connection at the compressor circuit before assuming
│ compressor fault
│
├─ FUSE BRANCH (CF1, CF3, CF4, CF6, CF7)
│ ├─ Identify which circuit the specific CF code protects
│ │ (power supply / main PCB / fan / pump / reactor)
│ ├─ Isolate power, inspect the corresponding component for
│ │ an obvious short, locked rotor, or seized bearing
│ │ BEFORE replacing the fuse
│ ├─ Replace fuse with the CORRECT rating for the specific
│ │ model (ratings vary — check data plate/manual)
│ └─ If fuse blows again immediately on power-up → component
│ fault confirmed, replace the specific faulty component
│ (fan motor, pump, etc.) not just the fuse
│
└─ PUMP BRANCH (P-series)
├─ Check circulating pump runs and is not airlocked
├─ Check system water pressure and flow rate
└─ If pump confirmed faulty → replace (no F-Gas requirement,
water-side component)
Before Escalating: Checks Any Heating Engineer Can Do
As with every heat pump brand, a meaningful share of Grant Aerona3 fault codes that reference temperature or current protection have simple, non-refrigerant causes that should be ruled out before involving an F-Gas engineer:
- Outdoor unit airflow — check the coil isn't blocked by leaves, debris, snow, or nearby planting, and that manufacturer clearances are maintained
- Isolator and supply voltage — confirm the outdoor unit isolator is on and supply voltage is within the unit's rated tolerance; undervoltage or a recent power interruption is a genuine and recurring cause of A2/A4-type faults
- Water-side flow and pressure — check the circulating pump runs, the system isn't airlocked, and pressure is correct; a restricted flow can cause temperature-related protection trips that mimic a refrigerant fault
- Fuse circuit inspection before fuse replacement — for any CF-series code, check the specific protected component (fan motor, pump, reactor) for an obvious fault before simply fitting a new fuse and re-energising, since a fuse rarely blows without a cause
- Fault history — if the controller retains a fault log, check for a pattern (recurring at the same time of day, weather condition, or DHW demand) rather than diagnosing a single occurrence in isolation
Only once these are ruled out should diagnosis move to the sealed refrigerant circuit — checking pressures, superheat, subcooling, and compressor electrical characteristics — which requires F-Gas certification.
R32 Refrigerant Handling Considerations
Later Aerona3 units use R32 refrigerant, an A2L (mildly flammable, lower toxicity) classification under BS EN 378, which brings specific handling, ventilation, and recovery equipment requirements beyond those for the non-flammable A1 refrigerants used in older heat pump generations. Confirm which refrigerant is fitted from the appliance data plate before any refrigerant-related work, and ensure the attending F-Gas engineer's certification and equipment cover A2L refrigerant handling specifically, not just standard A1 F-Gas work.
Reset Procedure and When Not to Reset
Power supply and current-detection faults (A0, A2, A4) linked to a one-off power interruption event (a lightning strike, a brief supply dropout) will often clear with a single controller reset or power-cycle, and a single reset to confirm the fault clears is reasonable practice. For A1 (discharge temperature) faults and any fault where a genuine refrigerant-circuit or compressor cause is suspected, repeated resetting without addressing the underlying cause risks further compressor damage and is poor practice.
Frequently Asked Questions
Can I reset a Grant Aerona3 fault code myself without calling a specialist?
For power-supply and current-detection codes (A0, A2, A4) linked to an identifiable one-off power event, a single reset to confirm the fault clears is reasonable, provided the likely cause is also checked. For A1 (discharge temperature) or any fault where airflow, wiring, and water-side checks don't resolve it, stop and arrange diagnosis by a suitably qualified (and, where the refrigerant circuit is implicated, F-Gas certified) engineer rather than resetting repeatedly.
Where do I find the complete, authoritative fault code list for my specific Aerona3 model?
Always use the installation and servicing instructions for the exact model and generation fitted — Grant's Aerona3, Aerona3 R32, and HPiD/HPiD6 hydro-box ranges are documented separately, and code sets are not guaranteed to be identical across them. The manual, or Grant UK's own technical support line, should be the primary reference rather than general troubleshooting forums, which can carry unverified or model-mismatched information.
Does OFTEC registration cover Grant Aerona3 heat pump work?
No. OFTEC registration is specific to oil-fired heating equipment and does not itself qualify an engineer to work on a heat pump's electrical/water-side systems or its refrigerant circuit. Heat pump installation and servicing work typically requires MCS certification (for BUS grant compliance) and, for any refrigerant-circuit work, F-Gas certification appropriate to the refrigerant type fitted — an OFTEC-registered engineer moving from Grant's oil range to its heat pump range needs these additional qualifications, not a substitute for them.
Is a blown fuse (CF-series code) something I can just replace myself?
The fuse replacement itself is straightforward and doesn't require refrigerant qualification, but always isolate the unit, identify and inspect the specific component that fuse protects (fan motor, pump, reactor, etc.) for an obvious fault before fitting a new fuse, and use the exact fuse rating specified for that model — ratings differ between Grant heat pump models. If the replacement fuse blows again immediately, the underlying component is faulty and needs replacing or further diagnosis, not another fuse.
Regulations & Standards
Fluorinated Greenhouse Gas Regulations (retained UK law from EU Regulation 517/2014) — F-Gas certification required for any work on the sealed refrigerant circuit
BS EN 378 (series) — refrigerating systems and heat pumps: safety and environmental requirements, relevant to A2L (R32) refrigerant handling
MIS 3005-D / MIS 3005-I — Microgeneration Certification Scheme Heat Pump Design and Installation standards; current issue 1.0 (2025) — confirm the specific edition against the MCS Standards & Tools Library
BS EN 14511 — Air-to-water heat pumps; rating conditions and test methods
Boiler Upgrade Scheme (BUS) — Ofgem-administered grant scheme; requires ongoing maintenance by an appropriately qualified engineer to preserve grant compliance
BS 7671 (IET Wiring Regulations) — applicable to electrical fault-finding and any wiring repair on the outdoor unit isolator, control cabling, or fuse circuits
Grant UK — Air Source Heat Pump product and technical support — official troubleshooting and fault code guidance
Grant Aerona3 Series Installation and Servicing Instructions — primary source for A-series and CF-series fault code definitions
GOV.UK — F-Gas Regulations Guidance — certification requirements for refrigerant work, including A2L refrigerants
MCS — Heat Pump Installation Standards — MIS 3005 Design/Installation standards and commissioning requirements
Ofgem — Boiler Upgrade Scheme — grant maintenance conditions
oil boiler fault codes grant — Grant's oil boiler (Vortex/Vortex Pro/Combi) diagnostic approach — useful cross-brand context given the shared manufacturer and common installer base
heat pump error codes daikin — Daikin Altherma fault code architecture and diagnostic approach, useful comparison for engineers working across brands
heat pump error codes samsung — Samsung EHS fault code categories and diagnostic approach
heat pump error codes vaillant arotherm — Vaillant aroTHERM fault code architecture, another brand sharing codes with its own boiler platform
heat pump faults — general ASHP fault-finding: low COP, defrost cycles, common cross-manufacturer causes
heat pump servicing — annual servicing requirements and F-Gas leak-check thresholds
heat pump wiring — electrical connection, isolator, and circuit sizing requirements