Summary
Samsung entered the UK domestic heat pump market later than Daikin, Mitsubishi and Vaillant, and its EHS (Eco Heating System) monobloc and split units share fault code architecture with Samsung's much larger commercial air conditioning and VRF (DVM) product lines, since they're built on the same inverter compressor and control platform. This means the code numbering logic is broadly consistent and well documented across Samsung's HVAC range, even though the exact subset of codes that appears on any specific EHS model or firmware generation varies, and UK domestic installer documentation for EHS is less mature than for the longer-established brands.
When a Samsung EHS unit faults, the code is shown on the wired MWR-WW10/MWR-WE10-type wall controller as an alphanumeric string, and often also accessible through the Samsung SmartThings/EHS app on more recent installations. As with all Samsung inverter HVAC products, the controller holds a fault history that should be checked first — a code that occurred once and cleared on its own points to a different cause than the same code recurring at a consistent operating condition.
As with every UK-installed heat pump, work on the sealed refrigerant circuit — recovering, leak-testing, or recharging refrigerant — is restricted under the Fluorinated Greenhouse Gas Regulations to F-Gas certified engineers. A significant share of Samsung's compressor and pressure-related fault codes (E4xx range) have simple, non-refrigerant explanations — blocked outdoor unit airflow, a tripped isolator, low water flow rate on hydro-box models — that should be ruled out first by any competent heating engineer before assuming a refrigerant-circuit fault.
Note on code confidence: Samsung's UK domestic EHS documentation is less consistently published than Daikin, Mitsubishi Ecodan or Vaillant aroTHERM. The codes and categories below are drawn from Samsung's published commercial/VRF fault code architecture, which EHS shares, cross-checked against field-reported EHS fault descriptions. Where the exact code-to-fault mapping could not be confirmed against an official Samsung EHS service manual, it is marked **** — always cross-check against the specific model's service manual before ordering parts or condemning a component.
Key Facts
- Code format — a capital "E" followed by three digits, e.g. E101, E407, E462; some display panels show a shortened two-digit form on older units
- Displayed on — the wired wall controller (MWR-WW10/WE10-type) as an alphanumeric code, often with an accompanying short beep sequence; some installations also surface the code via the Samsung SmartThings/EHS smartphone app
- Fault history — accessible through the controller's installer/service menu; always check this log for repeat occurrences before diagnosing the current code alone
- E1xx-series — communication faults between indoor and outdoor units, or between the controller and indoor unit
- E2xx-series — sensor faults (temperature thermistors on the indoor coil, water side, or outdoor unit) ****
- E4xx-series — compressor, inverter drive, and protection faults, covering overcurrent, high pressure, discharge over-temperature, fan motor faults, and inverter module (IPM) faults
- F-Gas Regulations — refrigerant recovery, leak testing and recharge on the sealed circuit require F-Gas certification; do not open the refrigerant circuit without it
- MCS commissioning record — every MCS-installed Samsung EHS unit should have a commissioning sheet recording refrigerant charge, pipe run length and initial settings — a useful reference when diagnosing charge-related faults
- Reset procedure — typically power-cycle the outdoor unit isolator (allow several minutes off) or use the controller's reset function; repeated resetting of a genuine E4xx compressor/pressure fault risks compressor damage
- Exact code subset varies by model and firmware — EHS monobloc, split (with indoor hydro-box), and Gen5/Gen6/Gen7-style platform differences mean not every code below appears on every installed unit; always confirm against the specific unit's service manual
- E101 communication fault — one of the most frequently reported non-refrigerant EHS call-outs; typically traced to a damaged, loose, or corroded communication cable/terminal rather than a component failure
- E122 indoor coil/evaporator sensor fault — points to the indoor coil temperature sensor reading open or short circuit, affecting temperature control and defrost logic; check wiring/connector before sensor replacement
- Total current protection (E461) and inverter module faults (E462-E464) — protection codes designed to shut the compressor down before damage occurs; check airflow, power supply and refrigerant charge before assuming the inverter board has failed
Quick Reference Table
Diagnosed the problem? Create a repair quote in minutes with squote.
Try squote free →| Code | Category | Likely Cause | F-Gas Required? |
|---|---|---|---|
| E101 | Indoor–outdoor communication fault | Damaged/loose communication cable, terminal corrosion, EMI interference | No |
| E102 | Controller–indoor unit communication fault | Damaged wall controller cable or connection | No |
| E122 | Indoor coil (evaporator) temperature sensor fault | Sensor open/short circuit, or wiring/connector fault | No |
| E201 | Outdoor unit sensor fault (general) | Outdoor thermistor open/short circuit or wiring fault | No |
| E404 | Overload prevention | Sustained high load condition, restricted airflow or water flow | Possibly — check airflow/flow rate first |
| E407 | High-pressure protection | Blocked outdoor coil, closed valve, restricted water flow, or overcharge | Possibly — check airflow/flow rate first |
| E416 | Discharge pipe over-temperature | Refrigerant shortage, restricted flow, or blocked outdoor coil | Yes, if refrigerant shortage confirmed |
| E458 | Outdoor fan motor 1 fault | Fan motor lock, wiring fault, or physical obstruction | No, unless refrigerant-related |
| E460 | Compressor start error | Compressor winding fault, electrical supply issue, or locked rotor | Yes, for compressor investigation |
| E461 | Total current protection | Compressor overcurrent — supply voltage, airflow, or compressor fault | Possibly — check supply/airflow first |
| E462 | Inverter (IPM) module error | Inverter PCB fault, often triggered by another underlying condition | Only if compressor/refrigerant confirmed at fault |
| E466 | DC-link under/over-voltage | Incoming supply voltage out of tolerance, or PCB fault | No |
| E468 | Current sensor error | Sensor or wiring fault on the inverter board | No |
| E471 | Zero-cross (power sync) error | Incoming AC supply irregularity or PCB fault | No |
Confirm the exact code list against the specific EHS model, generation and firmware — Samsung's monobloc, split hydro-box, and successive EHS platform generations do not share an identical fault code table, and UK EHS-specific documentation should always take precedence over the wider Samsung HVAC/VRF reference this table is drawn from.
Detailed Guidance
Fault-Finding Decision Tree
START: Samsung EHS showing fault code on wall controller/app
│
├─ STEP 1: Read code from wall controller + check fault history
│ (installer/service menu — note last several codes and
│ operating conditions, not just the current one)
│
├─ STEP 2: Which range does the code fall in?
│ ├─ E1xx (communication) → go to COMMS BRANCH
│ ├─ E2xx (sensor) → go to SENSOR BRANCH
│ └─ E4xx (compressor/inverter/protection) → go to
│ COMPRESSOR/PROTECTION BRANCH
│
├─ COMMS BRANCH (E1xx)
│ ├─ Check communication cable terminals at both indoor
│ │ and outdoor units — tight, undamaged, uncorroded?
│ ├─ Check for cable damage along the run, particularly
│ │ where it passes through masonry or shares conduit
│ │ with mains cabling
│ └─ Check wall controller cable/connection if the code
│ relates to controller communication specifically
│
├─ SENSOR BRANCH (E2xx)
│ ├─ Check thermistor wiring and connector for corrosion
│ │ or a loose pin — common on outdoor-exposed sensors
│ ├─ Check resistance against manufacturer's temperature/
│ │ resistance table if accessible
│ │ specific model]
│ └─ If wiring and resistance check out → suspect PCB
│ input circuit rather than the sensor itself
│
└─ COMPRESSOR/PROTECTION BRANCH (E4xx)
├─ STOP — before assuming compressor/refrigerant fault:
├─ Check outdoor unit airflow — coil clogged, obstruction,
│ snow/leaf blockage, insufficient clearance
├─ Check outdoor unit isolator and supply voltage against
│ the unit's rated tolerance
├─ Check water-side flow rate (hydro-box models) — a
│ restricted flow can trigger pressure/temperature
│ protection codes that mimic a refrigerant fault
├─ Check for active defrost cycle before assuming a fault
└─ If airflow, power, flow rate and defrost all check out
normally → F-Gas certified engineer required to check
refrigerant pressures, compressor windings and charge
Before Calling an F-Gas Engineer: The Checks Any Heating Engineer Can Do
Most Samsung E4xx codes referencing pressure, temperature or compressor protection are triggered by conditions outside the sealed refrigerant circuit far more often than by a genuine refrigerant fault:
- Outdoor unit airflow — check the coil isn't clogged with leaves, fluff or debris, and that manufacturer clearances are met (typically at least 300–500mm to obstructions — check the specific model's manual, as clearances vary by output).
- Isolator and incoming supply voltage — confirm the isolator is on and supply voltage is within tolerance; undervoltage on a long or undersized run is a genuine, recurring cause of protection trips (E461, E466, E471).
- Water-side flow rate (hydro-box/monobloc installations) — a restricted flow rate (closed valve, air lock, failed pump, blocked strainer) causes the heat exchanger to overheat on the refrigerant side, triggering codes (E404, E407, E416) that mimic a refrigerant fault.
- Defrost cycle — check whether the unit is mid-defrost before assuming a fault; heavy icing during active defrost in cold, humid UK winters is normal.
- Fault history pattern — an isolated code that cleared and hasn't recurred is less concerning than one recurring at the same operating condition.
Only once these are ruled out should diagnosis move to the sealed refrigerant circuit — checking suction/discharge pressures, superheat, subcooling and compressor electrical characteristics — all of which require F-Gas certification.
Communication Faults (E1xx) — the Most Common Non-Refrigerant Call-Out
E101 and related communication codes are among the most frequently reported Samsung EHS faults and are rarely a component failure. The indoor and outdoor units communicate over a dedicated control cable, separate from the mains supply cabling; a loose terminal, a nicked cable pinched during installation, or interference from a nearby unscreened high-current cable run in the same duct can all cause intermittent or permanent transmission faults.
- Check control cable terminals at both indoor and outdoor units are tight and free of corrosion
- Inspect the cable run for physical damage, particularly where it passes through masonry or shares a duct with mains cabling
- If the fault is intermittent rather than constant, suspect EMI from a nearby unscreened power cable running parallel to the control cable — reroute or use screened cable per the installation manual
- Confirm supply voltage at the outdoor unit isolator is within tolerance — undervoltage during compressor start can trigger transmission faults that present identically to a wiring fault
Sensor Faults (E2xx) — Thermistor Checks
E2xx-range codes point to a specific temperature sensor — indoor coil, outdoor air, or (on hydro-box installations) water-side sensors. These sensors are relatively inexpensive and generally straightforward to check once the unit is safely isolated:
- Inspect the connector for corrosion or a loose pin — a common failure point on outdoor units exposed to weather
- If accessible, check resistance against the manufacturer's temperature/resistance chart for that specific sensor type; a reading well outside the expected range at a known ambient or water temperature confirms sensor failure
- Replacing a confirmed-faulty thermistor does not require F-Gas certification, since it doesn't involve opening the refrigerant circuit — but always follow the manufacturer's specific procedure, as some sensors are strapped to refrigerant pipework and require care not to disturb pipe insulation or supports
Compressor and Inverter Protection Faults (E4xx)
The E4xx range covers the largest and most safety-relevant group of Samsung EHS codes — overload protection (E404), high-pressure protection (E407), discharge over-temperature (E416), fan motor faults (E458), compressor start errors (E460), total current protection (E461), and inverter module (IPM) faults (E462-E471). These are protective shutdowns by design — the control logic is stopping the compressor before damage occurs, which means the root cause is very often external to the compressor and inverter board itself (airflow, supply voltage, water flow, refrigerant charge) rather than the board being faulty. Diagnose in that order — external conditions first, board/component replacement last — to avoid replacing an expensive inverter module that wasn't actually the fault.
Reset Procedure and When Not to Reset
Most Samsung EHS communication and sensor faults (E1xx, E2xx) clear with a power-cycle reset of the outdoor unit isolator (switch off, wait several minutes for the PCB to discharge, switch back on), and a single reset to confirm the fault clears is reasonable while further diagnosis continues. For E4xx compressor and pressure-related faults, repeated resetting without addressing the underlying cause risks compressor damage — these should be properly diagnosed, including by an F-Gas engineer where the refrigerant circuit is implicated, before the unit returns to normal service.
Frequently Asked Questions
Can I reset a Samsung EHS fault code myself without calling an engineer?
For communication and sensor codes (E1xx, E2xx), a single power-cycle reset to see if the fault clears is reasonable, provided the likely cause (loose connector, damaged cable) is also investigated. For compressor and pressure-related codes (E4xx), do not repeatedly reset — if the fault recurs after one reset, stop and arrange diagnosis by a qualified (and where necessary F-Gas certified) engineer, since repeated resets on a genuine compressor fault can cause further, more expensive damage.
Where do I find the exact fault code list for my specific Samsung EHS model?
Samsung's E-prefix code structure is broadly consistent across its wider HVAC and VRF range, but the exact codes present on a given EHS model, and their precise meaning, vary between monobloc, split hydro-box, and successive platform generations, and UK-specific EHS documentation is not as consistently published as some competitor brands. Always check the specific model's installation and service manual, obtainable via the installer, or contact Samsung's technical support with the model and serial number from the data plate or commissioning paperwork.
My Samsung EHS unit shows no fault code but isn't heating properly — where do I start?
If there's no fault code, the unit believes it's operating normally, so the issue is more likely a settings problem than a component fault: check the flow temperature setpoint and weather compensation curve, check DHW priority if hot water and heating compete, and check the actual water flow rate and ΔT. See the general heat pump fault-finding guidance for symptoms like low COP and short-cycling.
Is a Samsung-specific F-Gas certification needed, or is any F-Gas card sufficient?
Any engineer holding a valid F-Gas certification appropriate to the refrigerant type and system category (typically Category 1 for stationary refrigeration/air conditioning/heat pump equipment) can legally work on a Samsung EHS refrigerant circuit — there is no brand-specific F-Gas qualification. Samsung-specific product training is valuable for efficient fault-finding and may be a manufacturer warranty condition on parts and labour cover — check the specific warranty terms before undertaking refrigerant-circuit work if the unit is still under warranty.
Why is there less UK-specific documentation for Samsung EHS than for Daikin, Mitsubishi or Vaillant?
Samsung's EHS range has a shorter track record on UK Boiler Upgrade Scheme installations than the three longer-established brands, and its published documentation leans more heavily on the wider commercial air conditioning/VRF range EHS shares a control platform with. This makes some EHS-specific fault code detail harder to source than for Daikin Altherma, Mitsubishi Ecodan or Vaillant aroTHERM — always prioritise the specific model's own service manual over general Samsung HVAC references.
Regulations & Standards
Fluorinated Greenhouse Gas Regulations (retained UK law from EU Regulation 517/2014) — F-Gas certification required for any work on the sealed refrigerant circuit
MIS 3005-D / MIS 3005-I — Microgeneration Certification Scheme Heat Pump Design and Installation standards (split from the single MIS 3005 into separate Design and Installation standards from 1 April 2022) — confirm the current issue against the MCS Standards & Tools Library
BS EN 14511 — Air-to-water heat pumps; rating conditions and test methods
Boiler Upgrade Scheme (BUS) — Ofgem-administered grant scheme; requires ongoing maintenance by an appropriately qualified engineer to preserve grant compliance
Part L of the Building Regulations — energy efficiency requirements relevant to heat pump installation and major component replacement
BS 7671 (IET Wiring Regulations) — applicable to electrical fault-finding and any wiring repair on the outdoor unit isolator or control cabling
Samsung UK — Heating and Cooling Support — product and service documentation by model
GOV.UK — F-Gas Regulations Guidance — certification requirements for refrigerant work
MCS — Heat Pump Installation Standards — MIS 3005 Design/Installation standards and commissioning requirements
Ofgem — Boiler Upgrade Scheme — grant maintenance conditions
heat pump error codes daikin — Daikin Altherma fault code architecture and diagnostic approach
heat pump error codes mitsubishi ecodan — Mitsubishi Ecodan fault code categories and diagnostic approach
heat pump error codes vaillant arotherm — Vaillant aroTHERM fault code architecture
heat pump faults — general ASHP fault-finding: low COP, defrost cycles, cross-manufacturer causes
heat pump servicing — annual servicing requirements and F-Gas leak-check thresholds
heat pump wiring — electrical connection, isolator, and circuit sizing requirements