Summary

"The bathroom fan never turns off" is one of the few extractor complaints where the first job is to decide whether there is a fault at all. Since the 2010 edition of Part F, and far more since 2021, new and refurbished homes have been fitted with continuous-running fans: dMEV units in each wet room that run quietly all day at 6–13 l/s and boost when the light or humidistat calls, or a central MEV unit in the loft running continuously. A tenant moving into one of these, or a homeowner whose builder did not explain the system, hears a fan that never stops and calls someone to fix it. Switching it off at the isolator is the worst outcome: the house loses its only ventilation and the mould arrives within a winter.

When the fan is an intermittent type — the standard axial fan with a timer overrun that runs on the light and stops 5–25 minutes later — continuous running is a fault, and it is almost always in the control: a humidistat whose sensor has drifted or is set at 60% RH in a bathroom that is always at 65%, a timer relay that has welded, or wiring where the switched live from the light and the permanent live have been swapped so the timer sees a demand all the time. This guide gives the tests to tell the two situations apart, the decision tree for the intermittent fan, the Part F rates that decide whether the continuous fan is doing its job, and what to charge. For the dead-fan version of this call see extractor fan not working; for the noisy version see extractor fan noisy vibrating.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
What you find Fan type Verdict Action
Quiet fan, runs always, louder when light is on, labelled continuous or trickle/boost dMEV Not a fault Explain; check boost works; check filter if fitted
Fan in loft ducted to several rooms, runs always MEV Not a fault Explain; check it is on the right speed setting
Standard axial fan, runs always, no change with light Intermittent Fault L/SL crossed, or timer relay welded
Runs always in winter, stops in summer Intermittent with humidistat Fault (setting) Raise setpoint to 70–80% RH; clean sensor
Runs always, stops when humidistat turned fully up Humidistat Fault (drift or setting) Reset; replace module if drift returns
Runs always, stops only at isolator; timer adjuster has no effect Timer module Fault Replace module or fan
Runs always after a new light fitting or switch was installed Wiring Fault Switched live has been made permanent — correct at the switch
Runs always after a new fan was fitted Wiring or DIP switch Fault / config Check L vs SL at the terminals; check trickle mode switch
PIR fan runs always, stops when sensor covered PIR Fault (siting) Move the fan or shield the sensor; reduce sensitivity
Runs always and is noisy or hot Motor or bearing Fault Replace the fan

Detailed Guidance

Safety first — isolation

The fan is on the lighting circuit through a triple-pole isolator. Isolate at the isolator, remove the fan cover and verify dead on L, SL and N with an approved voltage indicator. If the isolator does not kill the fan, the isolator is wired wrongly (switching N only, or bypassed) and that is the first fault to put right — a single-pole isolation on a bathroom fan leaves a live switched conductor at the unit. Lock off at the consumer unit if the isolator cannot be trusted.

Decision tree

Fan runs continuously — start here
│
├── Is the fan designed to run continuously?
│   ├── Data plate says "continuous", "dMEV", "trickle/boost", or gives two
│   │   rates (e.g. 6/13 l/s); or it is a central unit in the loft
│   │     └── NOT A FAULT → explain to the customer; check:
│   │           ├── Boost works on light / humidistat / pull cord?
│   │           ├── Trickle rate still audible but not loud (bearings OK)?
│   │           ├── Filter (if fitted) clean?
│   │           └── Running at the commissioned speed (DIP/jumper)?
│   └── Single-rate axial fan with timer or humidistat → continue
│
├── Does the fan stop when the light has been off for 30 minutes?
│   ├── Yes → it is the overrun; adjust the timer pot down (5–30 min)
│   └── No → continue
│
├── Is there a humidistat?
│   ├── Yes
│   │     ├── Turn the setpoint to maximum (90% RH or "off"). Fan stops?
│   │     │     ├── Yes → setpoint was below ambient; set to 70–80%;
│   │     │     │         clean the sensor grille; advise on ventilation
│   │     │     └── No  → humidistat module or timer relay failed → continue
│   └── No → continue
│
├── Isolate, open the fan. With the light OFF and the isolator back ON:
│   is there 230 V on the SL terminal?
│   ├── Yes → the "switched" live is permanently live:
│   │         ├── L and SL swapped at the fan or the isolator → correct
│   │         ├── Fan fed from a permanent live on both L and SL → correct
│   │         └── Light switch bypassed / new fitting wired wrongly →
│   │             correct at the switch or the loop-in
│   └── No, SL is dead and the fan still runs → control module fault:
│         ├── Timer relay welded or timing circuit failed → replace module
│         ├── Humidistat relay failed → replace module
│         └── Module not available for this fan → replace fan
│
├── Is there a PIR?
│   └── Cover the sensor. Fan stops after the overrun?
│         ├── Yes → PIR retriggering on heat/movement → re-site or
│         │         reduce sensitivity; shield from the towel rail
│         └── No → module fault → replace
│
└── Inside the cover, is there a DIP switch or jumper marked "trickle",
    "24 h", "continuous" or "T"?
      └── Set to continuous → change to intermittent if that is what the
          room needs — or leave it and explain, if the room has no other
          background ventilation

Permanent live and switched live: the wiring fault

A timer fan needs three conductors plus earth. The permanent live powers the timer; the switched live tells the timer that the light is on. When the installer — or the electrician who fitted the new downlights last month — connects the permanent live to the SL terminal, or connects the fan's SL to the lighting circuit's permanent live at the loop-in instead of the switched live, the fan sees a demand all the time. The test is simple: with the light off, the SL terminal should be dead; if it reads 230 V, it is not switched. Trace back to the light switch or the loop-in ceiling rose and correct it. The same fault appears when a smart switch or a dimmer with a neutral is fitted and the fan's switched live has been picked up from the wrong side.

The triple-pole isolator can cause it too: the three conductors are not always in the same order on both sides, and a careless rewire of the isolator crosses L and SL.

Humidistats: setting, drift and the winter bathroom

A humidistat fan has a sensor that triggers above a set relative humidity. Two problems:

A humidistat fan also needs a permanent live and, usually, a switched live; a fan wired with a permanent live only runs on humidity alone and has no light-switch boost, which customers sometimes report as "it comes on by itself and won't stop" — it is doing what it was wired to do.

Timer modules and welded relays

The timer board holds a relay closed for the overrun. When the relay welds — more likely on fans that have been switching a motor with a failing capacitor, which draws more current — the fan runs until isolated. The timing capacitor can also fail short, which has the same effect. Some manufacturers sell the module as a spare (£20–£50); on most budget fans the fan is replaced. If the motor has started to hum or run slow, replace the fan rather than the module, or the new module welds too.

The continuous fan that the customer wants stopped

When the fan is a dMEV or MEV unit, the job is to explain: the fan is the house's ventilation, it runs at a few watts, and switching it off will bring condensation and mould within weeks. Check the three things that make a continuous fan annoying and fixable: that the trickle speed has not been set to boost permanently (DIP switch), that the bearings are not starting to whine (replacement unit if so, £150–£300), and that a filter or grille is not blocked and making it work harder. If the customer insists on an intermittent fan instead, the room then needs background ventilation (trickle vents) to replace the continuous extract, and the whole-dwelling ventilation strategy changes; that is a Part F decision, not a fan swap — see ventilation strategy and trickle vent installation pricing guide.

Replacement and Part F / Part P

A like-for-like fan replacement on the existing circuit is not notifiable under Part P. The replacement must meet the Part F rate for the room: an intermittent bathroom fan at 15 l/s under the 2021 edition (8 l/s under the 2010 edition still applies to the fan that was there, but fit the current rate), kitchen 30 l/s with a hood. A continuous unit replaces a continuous unit at the same trickle and boost rates. In zones 1 and 2 of the bathroom the fan must be IPX4 or better; a mains fan within reach of the shower in zone 1 needs the manufacturer's confirmation that it is suitable, or a SELV unit with a remote transformer — see bathroom fan wiring and bathroom extractor fan guide.

Charging the job

Job Time Typical charge
Diagnose; explain a dMEV; adjust humidistat or timer 30 min £60–£100 call-out / minimum
Correct L/SL wiring at fan, isolator or switch 30–60 min £70–£130
Replace timer or humidistat module 30–45 min £60–£140 inc. part
Replace intermittent fan like-for-like 1–1.5 h £150–£250 inc. fan
Replace dMEV unit like-for-like 1–1.5 h £200–£320 inc. unit
Re-site PIR fan or shield sensor 1 h £80–£150

Say in advance that the visit may end with an explanation and an adjustment, and charge the minimum for it; the customer who has been told their fan is fine and why is a repeat customer.

Frequently Asked Questions

Is it normal for an extractor fan to run all the time?

Yes, if it is a continuous-running type — a dMEV unit in the wet room or a central MEV fan in the loft — which is how most homes built or refurbished since around 2010 are ventilated. It runs at a quiet trickle rate using 3–6 W and boosts when the light or humidity triggers it. If it is a standard fan that used to stop after the light went off, continuous running is a fault.

Why does my bathroom fan not switch off after the light?

Either the timer overrun is set long (up to 30 minutes on some units — adjust it), the humidistat is set below the room's normal humidity, the timer relay has welded, or the switched live has been made permanently live by a wiring error — often after a new light or switch was fitted. Testing the switched-live terminal with the light off tells you which.

Can I just turn the fan off at the isolator?

If it is an intermittent fan with a fault, yes until it is repaired. If it is a continuous dMEV or MEV unit, no — it is the room's only ventilation, and switching it off brings condensation and mould within weeks and may put a landlord in breach of the ventilation requirements the property was built to.

How much does it cost to fix a fan that won't turn off?

£60–£130 for a diagnosis and an adjustment or wiring correction, £60–£140 to replace a timer or humidistat module, and £150–£300 to replace the fan. None of it is notifiable under Part P as a like-for-like job on the existing circuit.

Does a continuous fan cost a lot to run?

No. A dMEV unit at 3–6 W uses 26–53 kWh a year, about £6–£13 at 25p/kWh. An intermittent 20 W fan stuck on continuously is £40–£45 a year and will burn out its bearings in a year or two, which is the better argument for getting it fixed.

Regulations & Standards