Summary
"The bathroom fan never turns off" is one of the few extractor complaints where the first job is to decide whether there is a fault at all. Since the 2010 edition of Part F, and far more since 2021, new and refurbished homes have been fitted with continuous-running fans: dMEV units in each wet room that run quietly all day at 6–13 l/s and boost when the light or humidistat calls, or a central MEV unit in the loft running continuously. A tenant moving into one of these, or a homeowner whose builder did not explain the system, hears a fan that never stops and calls someone to fix it. Switching it off at the isolator is the worst outcome: the house loses its only ventilation and the mould arrives within a winter.
When the fan is an intermittent type — the standard axial fan with a timer overrun that runs on the light and stops 5–25 minutes later — continuous running is a fault, and it is almost always in the control: a humidistat whose sensor has drifted or is set at 60% RH in a bathroom that is always at 65%, a timer relay that has welded, or wiring where the switched live from the light and the permanent live have been swapped so the timer sees a demand all the time. This guide gives the tests to tell the two situations apart, the decision tree for the intermittent fan, the Part F rates that decide whether the continuous fan is doing its job, and what to charge. For the dead-fan version of this call see extractor fan not working; for the noisy version see extractor fan noisy vibrating.
Key Facts
- Continuous by design — dMEV fans (Part F System 3, decentralised) run 24/7 at a trickle rate, typically 6–13 l/s, and boost to 15–30 l/s on a trigger; centralised MEV runs continuously in the loft serving several rooms; MVHR runs continuously supplying and extracting. None of these should be switched off
- Intermittent by design — the standard axial or centrifugal fan (Part F System 1) that runs only when triggered by the light switch, a pull cord, a humidistat or a PIR, with a timer overrun of 5–25 minutes; continuous running is a fault
- How to tell — a dMEV unit is usually labelled as continuous on the data plate, has a trickle/boost rating (e.g. "6/13 l/s" or "continuous"), and is often a larger, quieter unit; an intermittent fan has a single rate and a timer or humidistat adjuster. The installation certificate or EPC may say "System 3"
- Part F extract rates, intermittent — bathroom 15 l/s, kitchen 30 l/s with a cooker hood or 60 l/s without, utility 30 l/s, WC 6 l/s (Approved Document F 2021, Table 1.2); earlier editions gave 8 l/s for bathrooms, which is why older fans are smaller
- Part F extract rates, continuous (dMEV/MEV) — minimum high rate per wet room (bathroom 8 l/s, kitchen 13 l/s, utility 8 l/s, WC 6 l/s) and a whole-dwelling minimum rate by bedrooms (19 l/s for a 1-bed, 25 l/s for a 2-bed, 31 l/s for a 3-bed, rising 6 l/s per further bedroom)
- Humidistat — triggers above a set relative humidity, adjustable typically 50–90% RH; set too low, or with a sensor fouled by dust or steam residue, it calls permanently in a bathroom whose ambient RH is 60–70% in winter
- Timer module — a small relay board that holds the fan on after the switched live drops; a welded relay or a failed timing capacitor leaves the fan running
- Wiring — an intermittent timer fan needs permanent live (L), switched live (SL) from the light and neutral (N); if L and SL are swapped at the fan terminals or at the isolator, the timer input is permanently live and the fan never stops; a fan wired with only a permanent live to both terminals does the same
- Triple-pole isolator — the means of isolation for a bathroom fan (L, SL, N all switched); outside the zones, usually above the door or in the loft; the first thing to check and the first thing to lock off
- PIR fans — trigger on movement or heat; a PIR facing a towel radiator, a heated mirror or a sunlit window can retrigger continuously
- DIP switches — many modern fans have a "trickle" or "24-hour" mode selectable by DIP switch or jumper inside the cover; a fan set to trickle by the installer is running continuously by configuration, not fault
- Part P — like-for-like replacement of the fan, or of a module inside it, on the existing circuit is not notifiable; a new circuit is
- BS 7671 Section 701 — bathroom zones; the fan must be suitable for its zone (IPX4 in zones 1 and 2, SELV in zone 1 if within reach of the bath/shower unless the manufacturer rates it otherwise)
- Running cost — a dMEV fan at 3–6 W continuous costs £6–£13 a year at 25p/kWh; an intermittent 20 W axial fan stuck on costs £40–£45 a year and wears out in 1–2 years
- Repair cost — diagnosis and adjust/rewire 30–60 minutes, £60–£110; module replacement £60–£140; fan replacement £150–£300 fitted (see extractor fan installation pricing guide)
Quick Reference Table
Diagnosed the problem? Create a repair quote in minutes with squote.
Try squote free →| What you find | Fan type | Verdict | Action |
|---|---|---|---|
| Quiet fan, runs always, louder when light is on, labelled continuous or trickle/boost | dMEV | Not a fault | Explain; check boost works; check filter if fitted |
| Fan in loft ducted to several rooms, runs always | MEV | Not a fault | Explain; check it is on the right speed setting |
| Standard axial fan, runs always, no change with light | Intermittent | Fault | L/SL crossed, or timer relay welded |
| Runs always in winter, stops in summer | Intermittent with humidistat | Fault (setting) | Raise setpoint to 70–80% RH; clean sensor |
| Runs always, stops when humidistat turned fully up | Humidistat | Fault (drift or setting) | Reset; replace module if drift returns |
| Runs always, stops only at isolator; timer adjuster has no effect | Timer module | Fault | Replace module or fan |
| Runs always after a new light fitting or switch was installed | Wiring | Fault | Switched live has been made permanent — correct at the switch |
| Runs always after a new fan was fitted | Wiring or DIP switch | Fault / config | Check L vs SL at the terminals; check trickle mode switch |
| PIR fan runs always, stops when sensor covered | PIR | Fault (siting) | Move the fan or shield the sensor; reduce sensitivity |
| Runs always and is noisy or hot | Motor or bearing | Fault | Replace the fan |
Detailed Guidance
Safety first — isolation
The fan is on the lighting circuit through a triple-pole isolator. Isolate at the isolator, remove the fan cover and verify dead on L, SL and N with an approved voltage indicator. If the isolator does not kill the fan, the isolator is wired wrongly (switching N only, or bypassed) and that is the first fault to put right — a single-pole isolation on a bathroom fan leaves a live switched conductor at the unit. Lock off at the consumer unit if the isolator cannot be trusted.
Decision tree
Fan runs continuously — start here
│
├── Is the fan designed to run continuously?
│ ├── Data plate says "continuous", "dMEV", "trickle/boost", or gives two
│ │ rates (e.g. 6/13 l/s); or it is a central unit in the loft
│ │ └── NOT A FAULT → explain to the customer; check:
│ │ ├── Boost works on light / humidistat / pull cord?
│ │ ├── Trickle rate still audible but not loud (bearings OK)?
│ │ ├── Filter (if fitted) clean?
│ │ └── Running at the commissioned speed (DIP/jumper)?
│ └── Single-rate axial fan with timer or humidistat → continue
│
├── Does the fan stop when the light has been off for 30 minutes?
│ ├── Yes → it is the overrun; adjust the timer pot down (5–30 min)
│ └── No → continue
│
├── Is there a humidistat?
│ ├── Yes
│ │ ├── Turn the setpoint to maximum (90% RH or "off"). Fan stops?
│ │ │ ├── Yes → setpoint was below ambient; set to 70–80%;
│ │ │ │ clean the sensor grille; advise on ventilation
│ │ │ └── No → humidistat module or timer relay failed → continue
│ └── No → continue
│
├── Isolate, open the fan. With the light OFF and the isolator back ON:
│ is there 230 V on the SL terminal?
│ ├── Yes → the "switched" live is permanently live:
│ │ ├── L and SL swapped at the fan or the isolator → correct
│ │ ├── Fan fed from a permanent live on both L and SL → correct
│ │ └── Light switch bypassed / new fitting wired wrongly →
│ │ correct at the switch or the loop-in
│ └── No, SL is dead and the fan still runs → control module fault:
│ ├── Timer relay welded or timing circuit failed → replace module
│ ├── Humidistat relay failed → replace module
│ └── Module not available for this fan → replace fan
│
├── Is there a PIR?
│ └── Cover the sensor. Fan stops after the overrun?
│ ├── Yes → PIR retriggering on heat/movement → re-site or
│ │ reduce sensitivity; shield from the towel rail
│ └── No → module fault → replace
│
└── Inside the cover, is there a DIP switch or jumper marked "trickle",
"24 h", "continuous" or "T"?
└── Set to continuous → change to intermittent if that is what the
room needs — or leave it and explain, if the room has no other
background ventilation
Permanent live and switched live: the wiring fault
A timer fan needs three conductors plus earth. The permanent live powers the timer; the switched live tells the timer that the light is on. When the installer — or the electrician who fitted the new downlights last month — connects the permanent live to the SL terminal, or connects the fan's SL to the lighting circuit's permanent live at the loop-in instead of the switched live, the fan sees a demand all the time. The test is simple: with the light off, the SL terminal should be dead; if it reads 230 V, it is not switched. Trace back to the light switch or the loop-in ceiling rose and correct it. The same fault appears when a smart switch or a dimmer with a neutral is fitted and the fan's switched live has been picked up from the wrong side.
The triple-pole isolator can cause it too: the three conductors are not always in the same order on both sides, and a careless rewire of the isolator crosses L and SL.
Humidistats: setting, drift and the winter bathroom
A humidistat fan has a sensor that triggers above a set relative humidity. Two problems:
- Setpoint below ambient. A UK bathroom in winter sits at 60–70% RH after a shower and takes an hour to fall; a humidistat set to 60% calls permanently. Set it to 70–80% so it responds to the shower peak, not the background. The adjuster is a small pot under the cover.
- Sensor drift or fouling. Cheap capacitive sensors drift upwards with age and steam residue; after five years a sensor may read 10–15 points high. Cleaning the grille helps; if the fan only stops with the pot at maximum, the sensor has drifted and the module or fan should be replaced.
A humidistat fan also needs a permanent live and, usually, a switched live; a fan wired with a permanent live only runs on humidity alone and has no light-switch boost, which customers sometimes report as "it comes on by itself and won't stop" — it is doing what it was wired to do.
Timer modules and welded relays
The timer board holds a relay closed for the overrun. When the relay welds — more likely on fans that have been switching a motor with a failing capacitor, which draws more current — the fan runs until isolated. The timing capacitor can also fail short, which has the same effect. Some manufacturers sell the module as a spare (£20–£50); on most budget fans the fan is replaced. If the motor has started to hum or run slow, replace the fan rather than the module, or the new module welds too.
The continuous fan that the customer wants stopped
When the fan is a dMEV or MEV unit, the job is to explain: the fan is the house's ventilation, it runs at a few watts, and switching it off will bring condensation and mould within weeks. Check the three things that make a continuous fan annoying and fixable: that the trickle speed has not been set to boost permanently (DIP switch), that the bearings are not starting to whine (replacement unit if so, £150–£300), and that a filter or grille is not blocked and making it work harder. If the customer insists on an intermittent fan instead, the room then needs background ventilation (trickle vents) to replace the continuous extract, and the whole-dwelling ventilation strategy changes; that is a Part F decision, not a fan swap — see ventilation strategy and trickle vent installation pricing guide.
Replacement and Part F / Part P
A like-for-like fan replacement on the existing circuit is not notifiable under Part P. The replacement must meet the Part F rate for the room: an intermittent bathroom fan at 15 l/s under the 2021 edition (8 l/s under the 2010 edition still applies to the fan that was there, but fit the current rate), kitchen 30 l/s with a hood. A continuous unit replaces a continuous unit at the same trickle and boost rates. In zones 1 and 2 of the bathroom the fan must be IPX4 or better; a mains fan within reach of the shower in zone 1 needs the manufacturer's confirmation that it is suitable, or a SELV unit with a remote transformer — see bathroom fan wiring and bathroom extractor fan guide.
Charging the job
| Job | Time | Typical charge |
|---|---|---|
| Diagnose; explain a dMEV; adjust humidistat or timer | 30 min | £60–£100 call-out / minimum |
| Correct L/SL wiring at fan, isolator or switch | 30–60 min | £70–£130 |
| Replace timer or humidistat module | 30–45 min | £60–£140 inc. part |
| Replace intermittent fan like-for-like | 1–1.5 h | £150–£250 inc. fan |
| Replace dMEV unit like-for-like | 1–1.5 h | £200–£320 inc. unit |
| Re-site PIR fan or shield sensor | 1 h | £80–£150 |
Say in advance that the visit may end with an explanation and an adjustment, and charge the minimum for it; the customer who has been told their fan is fine and why is a repeat customer.
Frequently Asked Questions
Is it normal for an extractor fan to run all the time?
Yes, if it is a continuous-running type — a dMEV unit in the wet room or a central MEV fan in the loft — which is how most homes built or refurbished since around 2010 are ventilated. It runs at a quiet trickle rate using 3–6 W and boosts when the light or humidity triggers it. If it is a standard fan that used to stop after the light went off, continuous running is a fault.
Why does my bathroom fan not switch off after the light?
Either the timer overrun is set long (up to 30 minutes on some units — adjust it), the humidistat is set below the room's normal humidity, the timer relay has welded, or the switched live has been made permanently live by a wiring error — often after a new light or switch was fitted. Testing the switched-live terminal with the light off tells you which.
Can I just turn the fan off at the isolator?
If it is an intermittent fan with a fault, yes until it is repaired. If it is a continuous dMEV or MEV unit, no — it is the room's only ventilation, and switching it off brings condensation and mould within weeks and may put a landlord in breach of the ventilation requirements the property was built to.
How much does it cost to fix a fan that won't turn off?
£60–£130 for a diagnosis and an adjustment or wiring correction, £60–£140 to replace a timer or humidistat module, and £150–£300 to replace the fan. None of it is notifiable under Part P as a like-for-like job on the existing circuit.
Does a continuous fan cost a lot to run?
No. A dMEV unit at 3–6 W uses 26–53 kWh a year, about £6–£13 at 25p/kWh. An intermittent 20 W fan stuck on continuously is £40–£45 a year and will burn out its bearings in a year or two, which is the better argument for getting it fixed.
Regulations & Standards
Building Regulations 2010, Approved Document F, Volume 1: Dwellings (2021 edition) — extract rates for intermittent (System 1) and continuous (System 3) ventilation; whole-dwelling rates; background ventilation
Building Regulations 2010, Approved Document P (2013 edition) — electrical safety; replacement of a fan on an existing circuit not notifiable
Building Regulations 2010, Approved Document L, Volume 1 (2021) — specific fan power limits for replacement fans
BS 7671:2018+A2:2022 — Section 701 (locations containing a bath or shower): zones, IP ratings, SELV; Chapter 46 and Section 537 isolation
BS EN 60335-2-80:2003+A2:2010 — household electrical appliances; particular requirements for fans
BS EN 13141-4:2021 — performance testing of components for residential ventilation; fans used in residential ventilation systems
Domestic Ventilation Compliance Guide (2021) — installation and commissioning of domestic ventilation systems, including commissioning sheets for continuous systems
Electricity at Work Regulations 1989 (SI 1989/635) — safe isolation
Housing Act 2004 (HHSRS) — damp and mould hazards where ventilation is disabled in rented homes
Approved Document F: Ventilation, Volume 1 (2021) — gov.uk; extract rates and system types
Domestic Ventilation Compliance Guide — gov.uk; commissioning of continuous systems
IET — BS 7671 Wiring Regulations — Section 701 bathroom requirements
HSE — Electricity at Work Regulations guidance (HSR25) — safe isolation
BEAMA — Residential ventilation guidance — manufacturers' guidance on dMEV and MEV
extractor fan not working — the dead-fan version of this diagnosis, with the wiring detail
extractor fan noisy vibrating — bearing and mounting faults
bathroom fan wiring — permanent live, switched live and the triple-pole isolator
bathroom extractor fan guide — selecting intermittent vs continuous fans
part f extract rates — the rates by room and system type
ventilation strategy — System 1, 3 and 4 explained
condensation on windows — what happens when the fan is switched off
extractor fan installation pricing guide — replacement pricing
trickle vent installation pricing guide — background ventilation if a continuous fan is changed to intermittent