Summary
Hypervolt is a British-designed charger that sells heavily through installer networks and on its app features: solar matching (Eco and Super Eco modes), scheduling against time-of-use tariffs, a software lock and load management via a CT clamp. Like every smart charger, most of its "it's broken" call-outs are the charger doing what it was told: waiting for a schedule, waiting for surplus solar, or holding the mandatory random delay before a session starts. Reading the glow colour correctly and opening the app before touching a screwdriver will clear the majority of jobs in minutes.
Where Hypervolt differs from zappi, Pod Point or Ohme is in how it tells you about a genuine fault. There is no two-digit code on a display, because there is no display. The unit goes red, the app shows a status, and the troubleshooting is driven from the app's status text and the installation. That makes it important to know what the red state covers (RCD, open-PEN, over-voltage, under-voltage, output fault and internal protection) and how to narrow it down with a meter.
This article covers the Hypervolt-specific LED language, the app statuses, the protective functions inside the unit and the installation checks that resolve each red-light scenario. For the brand-agnostic branch (supply, RCD type, Control Pilot, PME earthing) see ev charger faults and ev charger fault finding.
Key Facts
- Models in the field — Home 2.0 (2020 onward, 7 kW, Wi-Fi), Home 3.0 (2023 onward, 7.4 kW, tethered, Wi-Fi) and Home 3 Pro (2024 onward, 7.4 kW, tethered 7.5 m or 10 m, Wi-Fi plus wired Ethernet). All are Mode 3 AC chargers to BS EN IEC 61851-1 with a Type 2 connector to BS EN IEC 62196-2:2026.
- No numeric fault codes — faults are shown as a red LED and a status in the Hypervolt app. The app status text is the primary diagnostic.
- Red = safety system activated — the unit has stopped charging. Hypervolt's own reset is isolator off, wait about 5 seconds, isolator on. A unit that returns to red after reboot needs Hypervolt support, not repeated resets.
- Open-PEN protection — the charger monitors line-to-neutral voltage and trips when it is above 253 V or below 207 V for more than 5 seconds, disconnecting live, neutral and earth from the vehicle. This is the Regulation 722.411.4.1(iv) method and is why no earth rod is required on a PME supply.
- Internal 6 mA DC detection (RDC-DD) — detects the small DC leakage that would blind an upstream AC RCD. An external 30 mA Type A RCD or RCBO is still required by the manufacturer and by Regulation 722.531.3.101; the Hypervolt does not replace it.
- Pulsing white = offline — the charger has lost its internet connection. It will usually still charge locally in plug-and-charge mode, but schedules, solar matching and the app will not work until it reconnects.
- Flashing green = random delay — the Electric Vehicles (Smart Charge Points) Regulations 2021 require a randomised start delay (up to 600 seconds by default) on every session so thousands of chargers do not switch on at the same second. A customer watching the car "not start" for several minutes is seeing compliance, not a fault.
- Default off-peak schedule — the same Regulations require units sold from 30 June 2022 to ship with charging avoided in peak hours (typically 08:00 to 11:00 and 16:00 to 22:00 on weekdays) until the user changes it. Solid purple with a car plugged in and nothing happening is usually this.
- Lock — the Hypervolt Lock stops anyone starting a session without the app or a paired RFID card. Solid orange is locked; flashing orange is an attempt to use the unit while locked.
- Super Eco — charges only from surplus solar measured by the CT clamp. Flashing yellow with the car plugged in on a dull day is the unit waiting for export; it is not a fault. The minimum Control Pilot current is 6 A (about 1.4 kW), so export below that produces no charging in Super Eco.
- Maximum current set at commissioning — the installer sets the current limit in the app. A unit set to 16 A on a circuit designed for 32 A will "only charge at 3.6 kW"; check the setting before suspecting the car.
- Part P and Chapter 722 — a new charger circuit is notifiable work in England and Wales; the installation is to BS 7671:2018+A4:2026 Section 722 and the IET Code of Practice for Electric Vehicle Charging Equipment Installation (5th edition, 2023).
Quick Reference Table
Diagnosed the problem? Create a repair quote in minutes with squote.
Try squote free →| LED state | Meaning | Fault? | First action |
|---|---|---|---|
| No light | Plug-and-charge standby on some models (Home 3.0 quick-start guide), or no power | Maybe | Open the app: if it shows the charger online, standby; if offline and dark, check the RCBO and isolator |
| Solid blue | Standby, ready, no vehicle connected (Home 2.0 and app descriptions) | No | None |
| Solid green | Charging | No | None |
| Flashing green | Randomised start delay before charging (Smart Charge Points Regulations 2021) | No | Wait up to 10 minutes; explain to customer |
| Solid purple | Schedule set, no vehicle connected | No | Check schedule in app |
| Pulsing purple | Vehicle connected, waiting for scheduled start | No | Use Boost or edit the schedule to charge now |
| Flashing yellow | Super Eco waiting for surplus solar | No | Check CT clamp reading and export; switch to Eco or Boost to prove the unit charges |
| Solid orange | Charger locked | No | Unlock in app or with paired card |
| Flashing orange | Attempt to use a locked charger | No | Unlock; check who has access |
| Pulsing white | No internet connection | No (connectivity) | Check router, Wi-Fi signal at the unit, Ethernet on Home 3 Pro |
| Solid or pulsing red | Safety system activated; charging stopped | Yes | Isolator off 5 seconds, on; read app status; if red returns, test the installation (below) |
Colours have shifted slightly between Home 2.0, Home 3.0 and Home 3 Pro firmware. Treat the app status as authoritative and the colour as a prompt.
Detailed Guidance
Decision tree
HYPERVOLT WON'T CHARGE
======================
1. What colour is the glow?
Purple / yellow / orange / flashing green -> go to 2 (not a fault)
Pulsing white -> go to 3 (offline)
Red (solid or pulsing) -> go to 4 (safety trip)
No light at all -> go to 5 (supply)
2. MODE OR SCHEDULE
- Purple: schedule active. Press Boost in the app -> charges? Healthy.
- Flashing yellow: Super Eco. Check live export in app; switch to
Eco or Boost -> charges? Healthy; it's a solar question.
- Orange: locked. Unlock in app.
- Flashing green: random delay. Wait up to 10 min.
- Still nothing after override -> go to 4
3. OFFLINE
- Does the unit still charge in plug-and-charge? Yes -> connectivity only.
- Check Wi-Fi signal at the unit (garage walls, metal doors).
- Home 3 Pro: try Ethernet. Reboot router, then charger.
- Reconnect via app onboarding if the home network changed.
4. RED - SAFETY TRIP
a. Isolator OFF, wait 5 s, ON. Red clears and charging resumes?
-> transient (voltage excursion, DC leakage event). Note and monitor.
b. Red returns with NO car connected
-> supply problem. Measure L-N at the unit: outside 207-253 V = PEN
or DNO issue; inside range = internal fault, contact Hypervolt.
c. Red returns ONLY with a particular car connected
-> vehicle or cable: DC leakage from the on-board charger, damaged
cable, water in the inlet. Test the car on another charge point.
d. Upstream RCBO/RCD also tripped
-> earth fault on circuit or vehicle. Insulation-resistance test the
circuit with the charger disconnected; check RCD type (A minimum).
5. NO LIGHT, APP OFFLINE
- Check dedicated RCBO/RCD at the consumer unit and the external isolator.
- Confirm 230 V at the incoming terminals (safe isolation first).
- Power present, still dark -> internal fault, warranty.
Red light: what the safety system is actually checking
The Hypervolt's red state is one indicator covering several independent protective functions, which is why the app status matters. The functions you can provoke or measure are:
- Voltage window (open-PEN). Line-to-neutral above 253 V or below 207 V for more than 5 seconds trips the unit and isolates L, N and E to the vehicle. On a PME supply, a broken PEN conductor shows up as a neutral-to-earth voltage and a drifting L–N reading. Measure L–N and N–E at the charger terminals. N–E above a few volts with L–N wandering is a supply fault: stop, make the installation safe and report it to the DNO on 105. Do not keep resetting the charger to "get the customer going".
- Over-voltage without a PEN fault. Rural supplies and homes with large solar exports can sit above 253 V in the afternoon. The charger is correct to trip. The cure is with the DNO (tap change) or the PV inverter's export settings, not the charger.
- Residual DC current. The internal 6 mA RDC-DD trips when the vehicle's on-board charger leaks DC to earth. If red appears only when one particular car is plugged in and clears with another, the fault is in the vehicle or its cable. Charging that car elsewhere confirms it.
- Upstream RCD trip. If the charger is dark rather than red, the external RCD or RCBO has opened. Hypervolt's guidance is to reset it once; a device that will not stay on points to an earth fault on the circuit or vehicle, and the circuit needs insulation-resistance testing with the charger isolated.
- Output or contactor fault. Voltage detected on the output when it should be dead, or a contactor that will not close. This is internal and is a warranty claim. Record the app status text and the time.
Offline, but is it faulty?
Hypervolt's connectivity troubleshooting lists the usual suspects: a changed router or Wi-Fi password, a 2.4 GHz network that has been merged into a 5 GHz-only band, a mesh system that keeps dropping the unit, and signal that reads fine on a phone at head height but not behind a steel garage door. The Home 3 Pro has a wired Ethernet port, which is the robust answer for detached garages. An offline Hypervolt will still charge in plug-and-charge, so confirm whether the customer's complaint is "won't charge" or "the app shows offline"; they are different jobs.
Cable will not release from the car
A tethered cable that stays latched in the vehicle inlet is almost always the vehicle's lock, not the charger. Most cars release the latch when unlocked with the key fob or via a release in the boot or under the bonnet. Hypervolt's own guidance covers latching failures as a vehicle-side issue to try first; forcing the plug damages the inlet.
Solar matching that "doesn't work"
Super Eco needs a correctly fitted CT clamp on the meter tail reading export. A clamp fitted the wrong way round reads import as export, or vice versa; a clamp on the PV string instead of the grid tail cannot see household load. The app shows the live grid reading: with the house idle and the sun out, it should show negative (export). Also check that the car's own charge schedule is not blocking the session, and that export exceeds the 1.4 kW minimum. See ct clamp load management and ev charger solar integration.
Installation checks when the unit keeps going red
- Safe isolation and proving dead to GS38 before opening anything. See safe isolation procedure.
- Terminals: loose incoming L or N produces voltage excursions under load, and the unit trips on its voltage window. Check torque.
- Supply voltage under load: run a 3 kW load and watch L–N. A drop of more than 10 V suggests a high-impedance supply or poor termination.
- Earthing arrangement: on PME, confirm no earth rod has been fitted that bypasses the charger's PEN detection logic, and that the earthing is as the manufacturer specifies. See pme earthing ev charging.
- Upstream protection: 30 mA Type A RCD or RCBO (Type AC is not acceptable for a charger). Test trip time at 1× and 5× IΔn.
- Insulation resistance of the circuit with the charger disconnected: 1 MΩ minimum at 500 V DC, expect far higher.
- Record Zs and prospective fault current and compare with the commissioning certificate; see ev charger testing commissioning.
If every reading is healthy and red returns with no car connected, the fault is internal. Hypervolt's support line handles warranty; installers should not open the sealed unit.
Frequently Asked Questions
Why does my Hypervolt flash green for ten minutes before it starts charging?
Because the Electric Vehicles (Smart Charge Points) Regulations 2021 require a randomised delay of up to 600 seconds before each charging session begins, so that millions of chargers do not switch on in the same second after a tariff window opens. The user can disable the random delay in the app, but it is on by default and the flashing green is the charger counting it down.
Does a Hypervolt need an earth rod?
Not on a PME (TN-C-S) supply in the UK: the built-in voltage-monitoring open-PEN protection meets BS 7671:2018+A4:2026 Regulation 722.411.4.1 without a separate earth electrode. The installer still needs to confirm the supply type, fit a 30 mA Type A RCD or RCBO upstream and record the earthing arrangement on the certificate. A TT installation needs its own electrode as for any other circuit.
Can I just reset it when it goes red?
Once. Hypervolt's own advice is one reboot at the isolator. If red returns, the unit is telling you about a supply, vehicle or internal problem that resetting will not fix and may be masking. Repeated resets on a PEN-fault trip in particular put the user at risk of a live car body.
The app says offline but the car is charging. Is that a fault?
No. Local plug-and-charge works without the cloud. The customer loses schedules, solar matching and remote control until the connection is restored, so it is worth fixing, but it is a network job not an electrical one.
Does the Hypervolt replace the RCD on the circuit?
No. It contains 6 mA DC detection, which is what allows a Type A RCD to be used instead of a Type B, but the 30 mA AC RCD or RCBO is still required upstream. Hypervolt's technical sheet states this explicitly.
Regulations & Standards
BS 7671:2018+A4:2026 — IET Wiring Regulations; Section 722 (electric vehicle charging installations), Regulation 722.411.4.1 (PME supplies and open-PEN protection), Regulation 722.531.3.101 (RCD type and DC fault current detection).
IET Code of Practice for Electric Vehicle Charging Equipment Installation (5th edition, 2023) — installation and commissioning guidance.
Electric Vehicles (Smart Charge Points) Regulations 2021 — default off-peak schedule, randomised delay, security and data requirements for private chargers sold from 30 June 2022.
BS EN IEC 61851-1 — electric vehicle conductive charging systems; Mode 3 Control Pilot behaviour and minimum 6 A current signal.
BS EN IEC 62196-2:2026 — Type 2 plugs, sockets and vehicle connectors.
BS EN 62955 — residual direct current detecting devices (RDC-DD) for Mode 3 charging.
Building Regulations 2010, Approved Document P — notifiable electrical work in England and Wales.
Electricity Safety, Quality and Continuity Regulations 2002 — DNO duties on supply voltage (230 V +10 % / −6 %) and PEN integrity.
Hypervolt Help Center: LED Statuses — manufacturer's colour meanings.
Hypervolt Help Center: Fault Mode (pulsing red) — reset procedure and escalation.
Hypervolt Help Center: Home 3 Pro Installation Guide — PEN protection, RCD requirements, commissioning.
Hypervolt Help Center: External AC RCD Protection — dark unit and upstream RCD guidance.
Hypervolt Help Center: My Hypervolt is Offline — connectivity troubleshooting.
The Electric Vehicles (Smart Charge Points) Regulations 2021 — default schedule and randomised delay.
ev charger faults — brand-agnostic EV charger fault diagnosis and decision tree.
ev charger fault codes zappi — equivalent guide for myenergi zappi, which does use numeric codes.
ev charger fault codes ohme — Ohme fault diagnosis and smart-tariff scheduling conflicts.
ev charger fault codes pod point — Pod Point LED ring and app status diagnosis.
pme earthing ev charging — open-PEN protection options and when an earth rod is needed.
ev charger testing commissioning — commissioning values to compare against.
ev charger smart charging regulations 2022 — the Smart Charge Points Regulations in detail.