Summary
The zappi is the most common solar-aware EV charger on UK driveways because it was designed around diverting surplus PV generation into the car. That design is also why it generates more "my charger is broken" calls per unit than a plain 7 kW charger: in Eco and Eco+ modes the zappi deliberately waits for export before it charges, so a car that sits all afternoon at 0 kW on a cloudy day is the unit doing exactly what it was set to do. Before any electrical diagnosis, check which mode the customer has selected and what the grid CT is reading.
When a genuine fault occurs, the zappi gives you a plain-English message and a numeric code rather than a cryptic E-number. The numbering has shifted slightly between manual revisions (the v2.1 Rev 2.1.5 install manual and the Rev 1.7 UK user manual list the same faults with the same numbers for 23 to 26, but later codes such as 29 to 32 were added as firmware gained PEN-fault and voltage-range detection), so always read the message text, not just the number, and confirm against the manual revision that matches the unit's firmware.
Underneath the solar logic the zappi is a Mode 3 AC EVSE, and every protective-device trip, earth fault or Control Pilot problem is diagnosed exactly as for any other brand under BS 7671:2018+A2:2022 Section 722. For the brand-agnostic branch see ev charger faults; this article covers what is specific to the zappi.
Key Facts
- Models in the field — zappi v2 (2019 onward) and zappi v2.1 (2022 onward, with built-in wifi and Ethernet so no separate hub is needed); 7 kW single-phase (32 A) and 22 kW three-phase (32 A per phase); tethered (6.5 m cable) or untethered Type 2 socket.
- UK "-G" vs "-T" variants — UK-market "-G" units include integrated PEN-fault (open-PEN) detection that disconnects the protective earth from the vehicle when a broken PEN is detected; "-T" units sold in some other markets keep the earth connected. Only the "-G" version satisfies BS 7671:2018+A2:2022 Regulation 722.411.4.1 on a PME supply without a separate earth electrode or open-PEN device.
- Three charging modes — Fast (full 7 kW regardless of export), Eco (charges continuously at a minimum of 1.4 kW, topping up from the grid if surplus falls short) and Eco+ (charges only from surplus; pauses when export drops below the minimum).
- Minimum charge rate 1.4 kW — the IEC 61851-1 Control Pilot protocol cannot command a vehicle to draw less than 6 A, which is roughly 1.4 kW at 230 V single-phase. In Eco+ the zappi waits until surplus export reaches that level before it starts; the "Min Green Level" setting (default 100 %) controls how much of that 1.4 kW must be surplus.
- Grid CT is mandatory for Eco modes — the zappi needs a current transformer on the incoming supply tail (arrow towards the consumer unit) wired to its CT terminals, or a wireless harvi carrying that CT. No grid CT or a mis-set CT means the unit cannot see export and will never charge in Eco+.
- Fault code family — 23 Lock Failure (untethered socket actuator), 24 Output Fault (voltage present when output should be off), 25 PE Fault (earth disconnected or high impedance), 26 Comms Fault (internal protection-board communication), 29 PEN Fault (loss of supply neutral/earth), 30 Overload (EV drawing more than the set limit), 31 Over/Under/Bad Voltage Range, 32 Overheating or Voltage Mismatch.
- Built-in 6 mA DC fault detection — the zappi includes residual DC detection (RDC-DD), so a Type A RCD upstream satisfies Regulation 722.531.3; a Type B RCD is not required for the zappi itself.
- Smart Charge Points Regulations 2021 — units sold from 30 June 2022 ship with a default off-peak schedule (typically avoiding 08:00 to 11:00 and 16:00 to 22:00 on weekdays); a customer who has not changed this will see "Charge Delayed" or a scheduled start rather than immediate charging.
- Boost and Smart Boost — Boost forces a Fast-mode charge of a set kWh amount from any mode; Smart Boost adds a set kWh by a set time using the cheapest window. A customer "stuck in Eco+" can use Boost as the manual override.
- Firmware updates — pushed over the hub (v2) or built-in wifi/Ethernet (v2.1); a zappi that has been offline for months may be running firmware that mis-reports newer status messages. Confirm firmware version in the Other Settings menu before escalating.
Quick Reference Table
Diagnosed the problem? Create a repair quote in minutes with squote.
Try squote free →| Display message | Code | Meaning | First action |
|---|---|---|---|
| Waiting for export | — | Eco+ mode, surplus below 1.4 kW | Check mode; check grid CT reading; switch to Fast or use Boost to confirm the unit can charge |
| Charge Delayed | — | Charger ready, EV has not accepted charge | Check vehicle charge limit, timer and lock state; unlock/relock car; 2021 Regs default schedule |
| EV Disconnected | — | No Control Pilot handshake | Reseat cable at both ends; try a known-good cable; check charge-port flap sensor on the car |
| Charge Blocked | — | EV keeps re-requesting after Charge Complete | Unplug and re-plug; check vehicle charge-limit setting |
| Pilot Problem | — | Control Pilot signal fault; retests after 5 s | Clean plug pins; test EV on another charge point to isolate car vs cable vs zappi |
| Lock Failure | 23 | Untethered socket actuator could not lock/unlock | Push plug fully home; hold the button to reset; inspect actuator |
| Output Fault | 24 | Wrong output voltage detected (e.g. live when it should be off) | Unplug EV, hold button to reset; persistent = contactor/relay fault, escalate |
| PE Fault | 25 | Earth disconnected or impedance too high | Unplug EV; test earth continuity at the zappi terminals (R2) and Zs; reset |
| Comms Fault | 26 | Internal protection-board communication failure | Power-cycle at the isolator; persistent = internal fault, warranty claim |
| PEN Fault | 29 | Open-PEN condition detected on supply | Do not reset repeatedly; measure L-N and N-E voltages; call DNO if neutral is suspect |
| Overload | 30 | EV drawing more current than permitted | Check Max Current setting vs circuit OCPD; check vehicle on-board charger behaviour |
| Over/Under Voltage | 31 | Supply outside permitted range | Measure supply voltage at the unit; check for loose terminations; DNO if persistent |
| Overheating / Voltage Mismatch | 32 | Internal temperature too high, or phase/voltage inconsistency | Check ventilation and direct sun; for 3-phase check all phases present and balanced |
Detailed Guidance
Decision tree
ZAPPI WON'T CHARGE
===================
1. What is on the zappi display / in the app?
"Waiting for export" / "Waiting for surplus" -> go to 2
"Charge Delayed" / "EV Disconnected" / "Charge Blocked" -> go to 3
Numbered fault (23–32) -> go to 4
Blank screen, no lights -> go to 5
2. MODE / SOLAR LOGIC (not a fault)
- Which mode? Eco+ only charges from surplus >= 1.4 kW
- Press Boost (or switch to Fast): does it charge?
YES -> unit is healthy; it is a mode/CT/export question
- Check grid CT: display Import/Export must change
sign when a kettle is switched on
- CT on wrong cable, backwards, or harvi not paired
-> fix CT (see CT section)
- Min Green Level set too high for the season
NO -> go to 3
3. VEHICLE-SIDE STATUS
- "Charge Delayed": car has not accepted. Check vehicle
timer, charge limit (%), car locked/unlocked, and the
2021 Regs default off-peak schedule on the zappi
- "EV Disconnected": no pilot. Reseat both plugs; try a
known-good cable; check the car's port flap microswitch
- "Charge Blocked": car reached Charge Complete and keeps
retrying. Unplug/replug; raise the car's charge limit
- Car charges at a public post but not here -> go to 4
- Car charges nowhere -> vehicle fault; refer to dealer
4. NUMBERED FAULT
23 Lock Failure -> push plug fully in; hold button to reset;
check for debris in socket actuator
24 Output Fault -> unplug, reset once; persistent = internal
contactor/relay, do not keep resetting
25 PE Fault -> unplug; test earth continuity to the unit;
check CPC termination and main earth
26 Comms Fault -> power-cycle 60 s; persistent = internal
29 PEN Fault -> measure N-E voltage; >~10 V or L-N
outside 207–253 V = supply problem, DNO
30 Overload -> compare Max Current setting with vehicle
draw; check OCPD rating
31 Voltage -> measure at unit terminals under load;
loose terminal = heat damage, repair
32 Overheat/Mismatch -> ventilation/sun; 3-phase: check
all phases present and rotation
5. DEAD UNIT
- Check dedicated MCB/RCBO or RCBO at the CU (reset once)
- Check external rotary isolator if fitted
- Confirm 230 V at the zappi incoming terminals
- Live in, no display -> internal PSU fault, warranty
"Waiting for export" and the grid CT
The single most common zappi call-out is a unit in Eco+ that never starts. Start by watching the Import/Export figure on the home screen while someone switches a 3 kW load on and off. If the figure does not swing by roughly 3 kW, the zappi cannot see the grid and will never find surplus.
Work through the CT in this order:
- Position — the grid CT must be on the meter tail between the meter and the consumer unit (or on the incoming side of the Henley block), not on the solar circuit or a sub-main. On a three-phase supply a 7 kW zappi still needs a CT on every phase, which means a harvi.
- Direction — the arrow on the CT points towards the consumer unit. A reversed CT shows export as import; the unit will "charge from surplus" at night and never during the day.
- Termination and resistance — the CT connects to the zappi's CT1/CT2 terminals (or a harvi input). A healthy myenergi CT reads roughly 200 Ω across its leads when disconnected.
- Assignment — in Advanced Settings the CT input must be set to Grid, not Generation or None. A harvi input must be assigned to Grid in Linked Devices.
- harvi placement — a harvi in a steel meter cabinet, or sitting next to a smart meter, frequently loses signal. Relocate it into an enclosure near the consumer unit and re-pair.
See ct clamp load management for CT placement rules and ev charger solar integration for how the solar diversion logic works.
PEN Fault (29) and PE Fault (25)
These two are often confused. PE Fault (25) means the zappi has measured its own protective-earth connection as missing or high-impedance: typically a loose CPC at the unit, a corroded main earth terminal or a damaged SWA armour termination. Test R1+R2 and Zs at the zappi terminals and fix the termination.
PEN Fault (29) means the integrated open-PEN detection has seen a supply condition consistent with a broken combined neutral/earth on a TN-C-S (PME) network: L-N voltage drifting outside limits or a rising N-E voltage. The zappi responds by disconnecting the vehicle earth, which is what Regulation 722.411.4.1 requires. A one-off trip during a supply disturbance can be reset; repeated PEN Faults on a healthy installation point to a network problem and should be reported to the Distribution Network Operator, not cleared by lowering the detection threshold. See pme earthing ev charging and tncs earthing pme.
Overload (30) and the Max Current setting
The zappi's output limit is set in the installation menu (Supply Grid > Device Limit / Max Current). On a 32 A circuit the limit should be 32 A; a limit set below the car's draw on a hot day, or a cable rating setting that does not match the tethered lead, raises Overload. Equally, an installer who set 32 A on a circuit protected by a 20 A device will see MCB trips rather than code 30. Match the setting to the OCPD and the cable per ev charger cable sizing calculator.
If the zappi is on a load-limited supply (Grid Limit set to protect a 60 A or 80 A cut-out fuse), the unit will throttle rather than fault, and the display shows a reduced charge rate: this is normal behaviour and not an Overload.
Lock Failure (23) on untethered units
The Type 2 socket on untethered zappis has a motorised lock pin. Code 23 appears when the pin cannot drive home or release, almost always because the plug is not fully inserted, has been twisted while locked, or grit has entered the socket. Push the plug fully in, hold the front button to reset, and inspect the socket face. A pin that jams with a clean, fully seated plug needs the socket assembly replaced under warranty. Tethered units cannot raise 23.
Firmware, app and connectivity
A zappi v2 needs a hub (Ethernet to the router) for app control and firmware updates; a v2.1 has wifi and Ethernet built in. Offline units still charge normally, but the app shows stale data and schedule changes do not reach the unit. Before changing any charging setting remotely, check the unit's last-seen time in the app. A unit that has not updated firmware for a long period can show status messages that differ from current documentation, so update firmware first when the message on screen does not match the manual.
What to charge for a zappi diagnosis
| Job | Typical UK price (ex VAT) |
|---|---|
| Diagnostic visit, CT check, mode and settings correction | £60–£120 |
| Relocate or replace grid CT / harvi, re-pair and commission | £90–£180 |
| Earth termination repair and retest (R1+R2, Zs, RCD) | £80–£150 |
| Warranty swap of unit (labour only, unit supplied by myenergi) | £120–£220 |
| Full charger replacement supplied and fitted (like-for-like) | £800–£1,200 |
Prices are indicative for a single-phase domestic installation. See ev charging cost to install for new-install pricing.
Frequently Asked Questions
Why does the zappi sit at 0 kW all day in Eco+ mode?
Because Eco+ charges only from surplus, and the minimum a Type 2 vehicle will accept is about 1.4 kW (6 A). On an overcast day a 4 kWp array rarely exports that much once the house base load is subtracted, so the unit waits. It is working correctly. Lower the Min Green Level so the zappi tops up from the grid, use Eco mode, or schedule a Boost.
Can I just reset a PEN Fault (29) and carry on?
Once, to see if it recurs. A repeated PEN Fault on a correctly wired "-G" zappi means the supply has shown open-PEN characteristics. The detection is a safety function required by BS 7671:2018+A2:2022 Regulation 722.411.4.1 on PME supplies; the fix is to investigate the supply with the DNO, not to override the unit.
Does the zappi need a Type B RCD?
No. The zappi has integrated 6 mA residual DC detection (RDC-DD), so an upstream Type A RCD or RCBO satisfies Regulation 722.531.3. A Type AC device is not acceptable for any EV circuit.
The customer says "the app shows a fault but the charger screen is fine". Which is right?
The unit. The app can hold a cached fault from hours earlier if the hub or wifi link has dropped. Read the display on the unit, then check the app's last-seen timestamp. If the two disagree persistently, the connectivity is the problem, not the charger.
My customer's zappi only charges at night even in Fast mode. Why?
Check two schedules: the zappi's own Boost timer, and the default off-peak schedule the Smart Charge Points Regulations 2021 require to be preset on units sold from 30 June 2022. Either can block daytime charging until the customer edits or disables it in the app.
Regulations & Standards
BS 7671:2018+A2:2022, Section 722 — electric vehicle charging installations: Regulation 722.411.4.1 (PME supplies and open-PEN protection), 722.531.3 (RCD type and 6 mA DC detection), 722.533 (overcurrent protection).
BS EN 61851-1 — conductive charging of electric vehicles: defines Mode 3 charging and the Control Pilot states behind "Charge Delayed" and "EV Disconnected".
Electric Vehicles (Smart Charge Points) Regulations 2021 — default off-peak charging schedule, randomised delay and data requirements for domestic chargers sold from 30 June 2022.
Building Regulations Part P — the charger circuit is notifiable electrical work in England and Wales.
Building Regulations Part S — EV charge point requirements for new dwellings and major renovations with parking.
IET Code of Practice for Electric Vehicle Charging Equipment Installation (5th Edition) — industry guidance on earthing arrangements, open-PEN devices and commissioning tests.
myenergi Help Centre — Fixing Problems — official zappi troubleshooting articles including Lock Failure 23, Pilot Problem, Charge Delayed and EV Disconnected.
myenergi — zappi eco-smart EV charge point User Manual (Rev 1.7, July 2023) — fault code table for the UK "-G" model.
myenergi — zappi versions and PEN Fault detection — the difference between "-G" and "-T" units.
IET — Electric Vehicle Charging Equipment Installation Code of Practice — Section 722 application guidance.
GOV.UK — Electric Vehicles (Smart Charge Points) Regulations 2021 — default off-peak schedule requirement.
ev charger faults — brand-agnostic EV charger fault diagnosis and earth-fault branch.
ev charger fault codes ohme — equivalent brand-specific guide for Ohme chargers.
ev charger fault codes pod point — equivalent brand-specific guide for Pod Point chargers.
ct clamp load management — grid CT placement and load-management settings.
ev charger solar integration — how solar-diverting chargers decide when to charge.
pme earthing ev charging — open-PEN protection on PME supplies.