Summary

The zappi is the most common solar-aware EV charger on UK driveways because it was designed around diverting surplus PV generation into the car. That design is also why it generates more "my charger is broken" calls per unit than a plain 7 kW charger: in Eco and Eco+ modes the zappi deliberately waits for export before it charges, so a car that sits all afternoon at 0 kW on a cloudy day is the unit doing exactly what it was set to do. Before any electrical diagnosis, check which mode the customer has selected and what the grid CT is reading.

When a genuine fault occurs, the zappi gives you a plain-English message and a numeric code rather than a cryptic E-number. The numbering has shifted slightly between manual revisions (the v2.1 Rev 2.1.5 install manual and the Rev 1.7 UK user manual list the same faults with the same numbers for 23 to 26, but later codes such as 29 to 32 were added as firmware gained PEN-fault and voltage-range detection), so always read the message text, not just the number, and confirm against the manual revision that matches the unit's firmware.

Underneath the solar logic the zappi is a Mode 3 AC EVSE, and every protective-device trip, earth fault or Control Pilot problem is diagnosed exactly as for any other brand under BS 7671:2018+A2:2022 Section 722. For the brand-agnostic branch see ev charger faults; this article covers what is specific to the zappi.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Display message Code Meaning First action
Waiting for export — Eco+ mode, surplus below 1.4 kW Check mode; check grid CT reading; switch to Fast or use Boost to confirm the unit can charge
Charge Delayed — Charger ready, EV has not accepted charge Check vehicle charge limit, timer and lock state; unlock/relock car; 2021 Regs default schedule
EV Disconnected — No Control Pilot handshake Reseat cable at both ends; try a known-good cable; check charge-port flap sensor on the car
Charge Blocked — EV keeps re-requesting after Charge Complete Unplug and re-plug; check vehicle charge-limit setting
Pilot Problem — Control Pilot signal fault; retests after 5 s Clean plug pins; test EV on another charge point to isolate car vs cable vs zappi
Lock Failure 23 Untethered socket actuator could not lock/unlock Push plug fully home; hold the button to reset; inspect actuator
Output Fault 24 Wrong output voltage detected (e.g. live when it should be off) Unplug EV, hold button to reset; persistent = contactor/relay fault, escalate
PE Fault 25 Earth disconnected or impedance too high Unplug EV; test earth continuity at the zappi terminals (R2) and Zs; reset
Comms Fault 26 Internal protection-board communication failure Power-cycle at the isolator; persistent = internal fault, warranty claim
PEN Fault 29 Open-PEN condition detected on supply Do not reset repeatedly; measure L-N and N-E voltages; call DNO if neutral is suspect
Overload 30 EV drawing more current than permitted Check Max Current setting vs circuit OCPD; check vehicle on-board charger behaviour
Over/Under Voltage 31 Supply outside permitted range Measure supply voltage at the unit; check for loose terminations; DNO if persistent
Overheating / Voltage Mismatch 32 Internal temperature too high, or phase/voltage inconsistency Check ventilation and direct sun; for 3-phase check all phases present and balanced

Detailed Guidance

Decision tree

ZAPPI WON'T CHARGE
===================
1. What is on the zappi display / in the app?
   "Waiting for export" / "Waiting for surplus" -> go to 2
   "Charge Delayed" / "EV Disconnected" / "Charge Blocked" -> go to 3
   Numbered fault (23–32) -> go to 4
   Blank screen, no lights -> go to 5

2. MODE / SOLAR LOGIC (not a fault)
   - Which mode? Eco+ only charges from surplus >= 1.4 kW
   - Press Boost (or switch to Fast): does it charge?
       YES -> unit is healthy; it is a mode/CT/export question
             - Check grid CT: display Import/Export must change
               sign when a kettle is switched on
             - CT on wrong cable, backwards, or harvi not paired
               -> fix CT (see CT section)
             - Min Green Level set too high for the season
       NO  -> go to 3

3. VEHICLE-SIDE STATUS
   - "Charge Delayed": car has not accepted. Check vehicle
     timer, charge limit (%), car locked/unlocked, and the
     2021 Regs default off-peak schedule on the zappi
   - "EV Disconnected": no pilot. Reseat both plugs; try a
     known-good cable; check the car's port flap microswitch
   - "Charge Blocked": car reached Charge Complete and keeps
     retrying. Unplug/replug; raise the car's charge limit
   - Car charges at a public post but not here -> go to 4
   - Car charges nowhere -> vehicle fault; refer to dealer

4. NUMBERED FAULT
   23 Lock Failure  -> push plug fully in; hold button to reset;
                       check for debris in socket actuator
   24 Output Fault  -> unplug, reset once; persistent = internal
                       contactor/relay, do not keep resetting
   25 PE Fault      -> unplug; test earth continuity to the unit;
                       check CPC termination and main earth
   26 Comms Fault   -> power-cycle 60 s; persistent = internal
   29 PEN Fault     -> measure N-E voltage; >~10 V or L-N
                       outside 207–253 V = supply problem, DNO
   30 Overload      -> compare Max Current setting with vehicle
                       draw; check OCPD rating
   31 Voltage       -> measure at unit terminals under load;
                       loose terminal = heat damage, repair
   32 Overheat/Mismatch -> ventilation/sun; 3-phase: check
                       all phases present and rotation

5. DEAD UNIT
   - Check dedicated MCB/RCBO or RCBO at the CU (reset once)
   - Check external rotary isolator if fitted
   - Confirm 230 V at the zappi incoming terminals
   - Live in, no display -> internal PSU fault, warranty

"Waiting for export" and the grid CT

The single most common zappi call-out is a unit in Eco+ that never starts. Start by watching the Import/Export figure on the home screen while someone switches a 3 kW load on and off. If the figure does not swing by roughly 3 kW, the zappi cannot see the grid and will never find surplus.

Work through the CT in this order:

  1. Position — the grid CT must be on the meter tail between the meter and the consumer unit (or on the incoming side of the Henley block), not on the solar circuit or a sub-main. On a three-phase supply a 7 kW zappi still needs a CT on every phase, which means a harvi.
  2. Direction — the arrow on the CT points towards the consumer unit. A reversed CT shows export as import; the unit will "charge from surplus" at night and never during the day.
  3. Termination and resistance — the CT connects to the zappi's CT1/CT2 terminals (or a harvi input). A healthy myenergi CT reads roughly 200 Ω across its leads when disconnected.
  4. Assignment — in Advanced Settings the CT input must be set to Grid, not Generation or None. A harvi input must be assigned to Grid in Linked Devices.
  5. harvi placement — a harvi in a steel meter cabinet, or sitting next to a smart meter, frequently loses signal. Relocate it into an enclosure near the consumer unit and re-pair.

See ct clamp load management for CT placement rules and ev charger solar integration for how the solar diversion logic works.

PEN Fault (29) and PE Fault (25)

These two are often confused. PE Fault (25) means the zappi has measured its own protective-earth connection as missing or high-impedance: typically a loose CPC at the unit, a corroded main earth terminal or a damaged SWA armour termination. Test R1+R2 and Zs at the zappi terminals and fix the termination.

PEN Fault (29) means the integrated open-PEN detection has seen a supply condition consistent with a broken combined neutral/earth on a TN-C-S (PME) network: L-N voltage drifting outside limits or a rising N-E voltage. The zappi responds by disconnecting the vehicle earth, which is what Regulation 722.411.4.1 requires. A one-off trip during a supply disturbance can be reset; repeated PEN Faults on a healthy installation point to a network problem and should be reported to the Distribution Network Operator, not cleared by lowering the detection threshold. See pme earthing ev charging and tncs earthing pme.

Overload (30) and the Max Current setting

The zappi's output limit is set in the installation menu (Supply Grid > Device Limit / Max Current). On a 32 A circuit the limit should be 32 A; a limit set below the car's draw on a hot day, or a cable rating setting that does not match the tethered lead, raises Overload. Equally, an installer who set 32 A on a circuit protected by a 20 A device will see MCB trips rather than code 30. Match the setting to the OCPD and the cable per ev charger cable sizing calculator.

If the zappi is on a load-limited supply (Grid Limit set to protect a 60 A or 80 A cut-out fuse), the unit will throttle rather than fault, and the display shows a reduced charge rate: this is normal behaviour and not an Overload.

Lock Failure (23) on untethered units

The Type 2 socket on untethered zappis has a motorised lock pin. Code 23 appears when the pin cannot drive home or release, almost always because the plug is not fully inserted, has been twisted while locked, or grit has entered the socket. Push the plug fully in, hold the front button to reset, and inspect the socket face. A pin that jams with a clean, fully seated plug needs the socket assembly replaced under warranty. Tethered units cannot raise 23.

Firmware, app and connectivity

A zappi v2 needs a hub (Ethernet to the router) for app control and firmware updates; a v2.1 has wifi and Ethernet built in. Offline units still charge normally, but the app shows stale data and schedule changes do not reach the unit. Before changing any charging setting remotely, check the unit's last-seen time in the app. A unit that has not updated firmware for a long period can show status messages that differ from current documentation, so update firmware first when the message on screen does not match the manual.

What to charge for a zappi diagnosis

Job Typical UK price (ex VAT)
Diagnostic visit, CT check, mode and settings correction £60–£120
Relocate or replace grid CT / harvi, re-pair and commission £90–£180
Earth termination repair and retest (R1+R2, Zs, RCD) £80–£150
Warranty swap of unit (labour only, unit supplied by myenergi) £120–£220
Full charger replacement supplied and fitted (like-for-like) £800–£1,200

Prices are indicative for a single-phase domestic installation. See ev charging cost to install for new-install pricing.

Frequently Asked Questions

Why does the zappi sit at 0 kW all day in Eco+ mode?

Because Eco+ charges only from surplus, and the minimum a Type 2 vehicle will accept is about 1.4 kW (6 A). On an overcast day a 4 kWp array rarely exports that much once the house base load is subtracted, so the unit waits. It is working correctly. Lower the Min Green Level so the zappi tops up from the grid, use Eco mode, or schedule a Boost.

Can I just reset a PEN Fault (29) and carry on?

Once, to see if it recurs. A repeated PEN Fault on a correctly wired "-G" zappi means the supply has shown open-PEN characteristics. The detection is a safety function required by BS 7671:2018+A2:2022 Regulation 722.411.4.1 on PME supplies; the fix is to investigate the supply with the DNO, not to override the unit.

Does the zappi need a Type B RCD?

No. The zappi has integrated 6 mA residual DC detection (RDC-DD), so an upstream Type A RCD or RCBO satisfies Regulation 722.531.3. A Type AC device is not acceptable for any EV circuit.

The customer says "the app shows a fault but the charger screen is fine". Which is right?

The unit. The app can hold a cached fault from hours earlier if the hub or wifi link has dropped. Read the display on the unit, then check the app's last-seen timestamp. If the two disagree persistently, the connectivity is the problem, not the charger.

My customer's zappi only charges at night even in Fast mode. Why?

Check two schedules: the zappi's own Boost timer, and the default off-peak schedule the Smart Charge Points Regulations 2021 require to be preset on units sold from 30 June 2022. Either can block daytime charging until the customer edits or disables it in the app.