PME Earthing and EV Charging: PEN Fault Risk, TT Earthing Solutions and Approved Protection Devices

Quick Answer: PME (Protective Multiple Earthing, also called TN-C-S) presents a specific risk for EV charging: if the PEN conductor fails, the vehicle chassis can become energised to dangerous voltage. BS 7671:2018+A2:2022 Regulation 722.411.4.1 requires that where PME earthing is used, additional protection is provided — either by earthing the EV circuit via a TT (separate earth electrode) arrangement, or by a OZEV/BS 7671-approved PEN fault detection device.

Summary

PME earthing is used by most UK Distribution Network Operators (DNOs) for residential supplies. It is generally safe and reliable. However, it has a specific vulnerability: if the combined neutral/earth (PEN) conductor in the distribution network develops a fault (break, corrosion, connection failure), the earth terminal at the consumer's premises can be raised to a dangerous potential — potentially approaching the full supply voltage.

For most household equipment, this PME fault scenario is a low-probability, short-duration event that causes nuisance rather than serious harm. For EV charging, it is different: the EV's conductive chassis is connected to the chargepoint earth, and therefore to the PME earth terminal. In a PME fault, the EV would be energised. A person simultaneously touching the EV (or the chargepoint) while standing on wet ground or a metal structure connected to true earth could receive a potentially fatal electric shock.

This risk was identified in the EV charging context during the development of Chapter 722 and is addressed specifically by Regulation 722.411.4.1. Every domestic EV installation must either isolate the EV circuit from the PME earth or include an approved protection device.

Key Facts

Quick Reference Table: Earthing System Identification and EV Solution

Spending too long on quotes? squote turns a 2-minute voice recording into a professional quote.

Try squote free →
Earthing System Identification PME Risk? EV Solution
TN-S Separate neutral (blue) and earth (green/yellow) incoming conductors at cut-out No Standard chargepoint connection to earth terminal
TN-C-S (PME) Combined neutral/earth (PEN) at cut-out; separate thereafter Yes TT earth electrode for EV circuit OR approved PEN detection device
TT Consumer's own earth electrode; no earth connection from DNO No Earth via consumer's electrode
IT Isolated supply; rare in UK domestic No Specialist — consult engineer

Detailed Guidance

Identifying the Earthing System

Before designing an EV installation, identify the earthing system. Methods:

1. Inspect the meter and cut-out:

2. Contact the DNO: Ring the DNO's technical helpline with the address. They can confirm the earthing arrangement. This is the most reliable method and creates a documented record.

3. Check for the earth terminal type: PME supplies have a combined neutral/earth that is separated at the service fuse assembly. If the earth terminal is a clip or bar connected directly to the neutral bar, this indicates PME.

Solution 1: TT Earthing for EV Circuit

The TT solution involves providing a separate earth electrode (typically a copper-bonded steel earth rod) for the EV chargepoint circuit. The EV circuit is connected to this electrode, not to the premises' PME earth terminal.

Implementation:

  1. Drive a 1.2m or 2.4m earth rod at the chargepoint location (or in the garden, connected by earth cable)
  2. Connect the protective conductor (earth wire) of the EV circuit to the earth rod, NOT to the main earth terminal
  3. Do not connect the EV circuit earth to any other part of the premises earthing system
  4. Install an RCD on the EV circuit (the RCD must operate on a TT earthed circuit — earth fault loop impedance on TT is typically higher than TN-S)

Earth fault loop impedance on TT: For a TT circuit, earth fault loop impedance (Ze) depends on the earth rod resistance. A good earth rod in typical soil achieves 50–100Ω. With a 30mA RCD, this is sufficient to cause RCD operation (voltage = 0.03 × 50 = 1.5V → below shock threshold for RCD operation). Check that Ze × I_a (the RCD trip current × 2, per BS 7671) ≤ Uo/2 (115V).

Earth rod installation considerations:

Solution 2: PEN Fault Detection Device

A PEN fault detection device monitors the PME PEN conductor and disconnects the EV chargepoint if it detects a fault condition that would raise the earth potential.

How it works:

Approved devices (check current approvals with OZEV and manufacturer):

Installation: PEN detection devices are typically installed at or near the consumer unit. They require a connection to the incoming supply in addition to the circuit supply. Follow the manufacturer's specific installation instructions precisely.

Limitations:

Which Solution to Use?

Use TT earthing when:

Use PEN fault detection when:

Both solutions require:

Testing and Documentation

After installing the TT earth electrode:

  1. Earth rod resistance test — using a dedicated earth resistance tester (stakeable instrument or 2-terminal method per BS 7671); confirm resistance is adequate for the RCD protection chosen
  2. Earth fault loop impedance — measure Ze at the chargepoint terminals; confirm RCD will operate
  3. RCD test — test the RCD (30mA, trip within 200ms); confirm operation
  4. Record on EIC — document earthing system type, solution chosen, test results

Frequently Asked Questions

Is all UK domestic electricity supply on PME?

No, but the vast majority is. TN-S (separate neutral and earth throughout) is found on some older properties, particularly in London and other areas where the underground distribution network has remained unchanged for decades. TT earthing is found in rural areas and some other situations where the DNO has not provided a PME supply. Always check before assuming.

Can I just use a Type B RCD instead of TT earthing for PME?

No. A Type B RCD addresses the issue of DC fault current components from EV chargepoints, but it does NOT address the PME PEN conductor fault risk. A Type B RCD will still have its earth connected to the PME terminal; if the PEN conductor fails, the RCD earth and the EV chassis will still be at dangerous potential. The RCD will not see a fault current in this scenario (because the fault is upstream of the consumer's installation) and will not trip. TT earthing or a PEN fault detection device is required in addition to the Type B RCD.

How deep should the earth rod be?

The minimum recommended length is 1.2m. A standard single-piece copper-bonded steel earth rod is typically 1.2m long. For better performance, a 2.4m rod (or two 1.2m rods connected in series with a rod coupler) achieves lower resistance in most UK soils. Test after installation to confirm resistance is adequate.

What if the earth rod resistance is too high?

If the measured earth rod resistance is too high (typically >200Ω), consider:

Regulations & Standards