Summary

"It trips as soon as I switch it back on" is a different fault from "it trips at random". A random trip points to an intermittent fault or a leakage that builds over time; a startup trip means something is wrong at the moment current first flows. Startup trips cluster after power cuts, after a new appliance is plugged in, after a new consumer unit is fitted, and on cold damp mornings. Each of those clues narrows the cause before you lift a cover.

The first job is to identify which device is tripping. A main switch on a split-load or dual-RCD board is just a switch and does not trip; what customers call "the main switch" is often an RCD incomer (100mA or 30mA, common on TT installations), an RCBO, or an AFDD. Each device trips for a different reason: an MCB trips on overcurrent, an RCD on earth leakage, an RCBO on either, an AFDD on arcing signatures as well as both. Knowing which device went tells you which measurement to take.

This article gives a decision tree, the startup-specific causes that general tripping guides miss, and the testing sequence. For the broader half-split method on RCDs and MCBs see rcd tripping and tripping breaker.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Device that trips On startup with no load On startup when loads reconnect On switching a particular item on Most likely cause
MCB (single circuit) Yes – – Dead short on the circuit or a faulty MCB
MCB (single circuit) No Yes Yes, same item Inrush exceeding Type B magnetic trip
RCD or RCD incomer Yes – – Line-to-earth fault on an RCD-protected circuit, or faulty RCD
RCD or RCD incomer No Yes Any load Neutral-to-earth fault, or cumulative leakage
RCD No No One specific circuit Borrowed neutral or that circuit's appliance
RCBO Yes – – Hard fault on that circuit only; half-split within it
AFDD No Yes Motors, dimmers, brushed tools Arc signature from an appliance; check for genuine loose connection first
"Everything" (RCD incomer on TT) No Yes Any load Cumulative leakage across the whole installation; consider RCBO board

Detailed Guidance

Decision tree: startup trips

START: Device trips immediately on energising or on reset
│
├─ Which device trips?  (MCB / RCD / RCBO / AFDD / RCD incomer)
│
├─ MCB trips ───────────────────────────────────────────────────────┐
│    ├─ Trips with ALL loads unplugged and switched off?           │
│    │     YES → Dead short L–N or L–E on fixed wiring.            │
│    │           Isolate, IR test L–N, L–E, N–E at 500V.           │
│    │           <1MΩ → locate by half-split at JBs/accessories.   │
│    │           ≥1MΩ → swap MCB (faulty device).                  │
│    │     NO ↓                                                     │
│    └─ Trips when one appliance starts?                           │
│          YES → Inrush. Clamp the start current.                  │
│                > 5×In → correct circuit design: Type C MCB       │
│                (check Zs still meets Table 41.3), soft-start,     │
│                or split loads.                                    │
│          NO  → Cumulative start on reconnection: stagger loads,  │
│                check circuit loading, consider dedicated circuits │
│
├─ RCD / RCBO / RCD incomer trips ───────────────────────────────────┐
│    ├─ Trips with all MCBs on that RCD switched OFF?               │
│    │     YES → Faulty RCD, or fault between RCD and MCBs          │
│    │           (crossed neutral, damaged busbar). Test RCD;       │
│    │           inspect board wiring.                              │
│    │     NO ↓                                                      │
│    ├─ Trips with MCBs on but NO loads connected?                   │
│    │     YES → L–E fault on fixed wiring. IR test each circuit    │
│    │           L–E at 500V with neutrals disconnected.            │
│    │     NO ↓                                                      │
│    ├─ Holds with no load, trips as soon as ANY load is applied?    │
│    │     YES → N–E fault. IR test N–E on each circuit with the    │
│    │           neutral lifted from the bar. Also check for a      │
│    │           borrowed neutral between RCD groups.               │
│    │     NO ↓                                                      │
│    └─ Trips only when several loads start together?               │
│          YES → Cumulative leakage. Earth leakage clamp on each    │
│                circuit's L+N together at power-up. Sum > 9mA →    │
│                re-distribute circuits, fit RCBOs, replace leaky   │
│                appliances. Check for Type AC RCD on inverter/     │
│                EV/PV circuits.                                     │
│
├─ AFDD trips ───────────────────────────────────────────────────────┐
│    └─ Isolate, inspect every termination on the circuit for a     │
│       loose connection FIRST. Then test with suspect appliance    │
│       removed. See [afdd nuisance tripping](/knowledge/fault-finder/electrical/afdd-nuisance-tripping)
│
└─ After the fix: full RCD test (x0.5, x1, x5), IR, Zs, record on
   Minor Works or EIC; replace any device that has been tripped
   repeatedly under fault.

Step 1: Interview before you test

Three questions save an hour:

  1. When did it start? After a power cut, a storm, a new appliance, new lighting, a new board, or heavy rain. Each points somewhere different.
  2. What exactly do you reset, and what happens? "The big switch on the left" on a dual-RCD board is an RCD, not the main switch. Ask them to photograph the board with the tripped device.
  3. Does it hold if you switch everything off first, then reset, then switch things back on one at a time? If yes, the fault is a load or cumulative leakage, not the fixed wiring, and the customer may already have found the circuit for you.

Step 2: Identify the device and isolate

Photograph the board. Note the make and whether the RCDs are Type AC, A or F, and their rated residual current. Isolate at the main switch, lock off, prove dead to GS38 on all line and neutral terminals. If the board is a TT installation with a 100mA time-delayed incomer and 30mA RCDs downstream, note which tripped: an incomer tripping with the 30mA devices holding suggests leakage spread across several circuits or a fault upstream of the 30mA devices.

Step 3: Dead tests by half-split

With the supply isolated:

Halve the circuit at a convenient point (a junction box, an accessory mid-run, the first downlight) and test each half until the fault is in one leg. See test and inspection procedures.

Step 4: Live tests for inrush and leakage

Where dead tests pass, the fault is dynamic and must be measured live, with the customer's agreement and appropriate precautions:

Step 5: Fixes by cause

Cause Fix Notes
Dead short on fixed wiring Repair or rewire the damaged section Common after drilling, rodent damage, screw through cable
N–E fault Repair the termination or replace the water-damaged fitting Check outdoor accessories for IP rating, see ip ratings explained
Borrowed neutral Rewire so each circuit has its own neutral, or move both circuits onto the same RCD/RCBO Do not "fix" by removing RCD protection
Inrush on Type B Type C MCB where Zs permits (Table 41.3 maximum Zs is lower for Type C), soft-start unit, or dedicated circuit Re-calculate Zs; a Type C on a long circuit may not disconnect in time
Cumulative leakage Redistribute circuits across RCDs, convert to an all-RCBO board, replace the leaky appliance An RCBO board also stops one fault taking out half the house
Type AC RCD with DC-leaking loads Replace with Type A (or Type F/B where the equipment requires) Type A minimum under BS 7671:2018+A4:2026 for most new domestic circuits
Faulty RCD or MCB Replace like for like, matching breaking capacity and type Check busbar fit and the manufacturer's board compatibility
Reconnection surge after outage Stagger restart with timers or smart plugs on heavy loads; consider dedicated circuits for compressor loads Explain to the customer; this is not a wiring fault
AFDD arc signature Find and fix the loose connection; if genuinely a benign appliance signature, dedicated circuit without AFDD only where the regulations allow See afdd nuisance tripping

Step 6: Certification and the device itself

Fault repair on an existing circuit is not notifiable under Part P in England, but a replacement consumer unit or a new circuit is. Record the repair on a Minor Electrical Installation Works Certificate with the test results. Where an RCD or MCB has cleared a dead short, inspect it: BS EN 60898 devices are rated for a limited number of short-circuit operations and a device that has cleared several faults should be replaced. See part p notifiable work.

Frequently Asked Questions

Why does it hold when everything is off but trip as soon as I switch a light on?

That is the signature of a neutral-to-earth fault. With no load there is no current in the neutral, so nothing diverts to earth and the RCD sees no imbalance. The moment current flows, some of it returns via the fault to earth instead of through the RCD, and it trips. Test N–E at 500V with the neutral disconnected from the bar.

Can I change the Type B MCB for a Type C to stop a motor tripping it?

Only if the earth fault loop impedance still meets the lower maximum Zs for a Type C device in BS 7671 Table 41.3, so that the device still disconnects within 0.4s on an earth fault. Measure Zs, compare, and record it. If Zs is too high, use a soft-start or a dedicated circuit instead.

The consumer unit was fitted last week and has tripped every morning since. Is it faulty?

More likely a wiring error during the changeover: a neutral on the wrong RCD's neutral bar, or a pre-existing borrowed neutral that the old non-RCD board tolerated. Faulty new devices are rare. Ask the installer to return, test and correct it under their guarantee.

Does an RCBO board stop startup trips?

It stops one circuit's fault or leakage tripping other circuits, and it makes diagnosis far easier because the tripped device identifies the circuit. It does not cure a fault on that circuit. It is the right recommendation where cumulative leakage across many circuits is the cause.

Is it safe to keep resetting it until it holds?

No. Each reset under a genuine fault passes fault current and stresses the device, and if the cause is a damaged cable the repeated energising can start a fire. Isolate and test.

Regulations & Standards