Earthing & Bonding: Main Equipotential Bonding, Supplementary Bonding & BS 7671

Quick Answer: All domestic electrical installations must have a main earthing terminal connected to the supply earth (PME or TN-S), with main equipotential bonding cables (10mm² for PME, 6mm² for TN-S) connecting all incoming metallic services — gas, water, oil — to that terminal within 600mm of entry. Supplementary bonding in bathrooms is only required where continuity cannot be confirmed through the main bonding.

Summary

Earthing and bonding are the two most misunderstood safety concepts in domestic electrical work. They are related but distinct: earthing provides a fault current path back to the source so protective devices operate; bonding connects metallic parts together to prevent dangerous potential differences appearing between them.

Every installation in the UK must comply with BS 7671:2018+A2:2022 (the 18th Edition Wiring Regulations) on both counts. The specific requirements depend on your supply system type — PME (Protective Multiple Earthing, also called TN-C-S), TN-S (separate neutral and earth), or TT (transformer with separate earth electrode). The vast majority of UK domestic properties are PME.

Failures in earthing and bonding are responsible for a significant proportion of electric shock incidents and electrical fires. Getting this right is non-negotiable — it's also one of the most commonly cited failures on EICR inspections (Electrical Installation Condition Reports), particularly supplementary bonding omissions in older bathrooms.

Key Facts

Quick Reference Table

Quoting an electrical job? Describe the work and squote handles the pricing.

Try squote free →
Parameter PME (TN-C-S) TN-S TT
Main bonding cable size 10mm² 6mm² 6mm²
Main earthing conductor 16mm² min 16mm² min 16mm² min
Typical Ze 0.1–0.35Ω 0.4–0.8Ω Variable
Earth electrode required? No (unless exporting PME) No Yes
RCD disconnection required? Circuits over 32A Circuits over 32A All circuits
Supplementary bonding bathroom Usually not required Usually not required May be required

Detailed Guidance

Supply System Identification

Before any earthing work, identify your supply system type:

  1. Inspect the incoming cable at the meter position. If the earth terminal at the cut-out is connected to the neutral terminal, it's PME. If there's a separate lead cable sheath earth, it's TN-S.
  2. The DNO (Distribution Network Operator) can confirm on request.
  3. TT systems typically have a local earth rod visible near the property; no connection between neutral and earth at the cut-out.

For PME supplies, exporting PME earth to outbuildings requires careful consideration — BS 7671 Regulation 411.4.1 and Appendix 4 restrict this where the outbuilding contains a bath or shower.

Main Equipotential Bonding — What Needs Connecting

The incoming services that must be bonded:

Gas supply pipe: Bond within 600mm of the gas meter. The bond should be applied to the installation pipework, not the meter itself (the meter may be changed). A 10mm² green/yellow sleeved conductor from the gas pipe to the MET using a BS 951 pipe clamp.

Water supply pipe: Bond the incoming cold water main within 600mm of entry. If the incoming pipe is plastic (MDPE blue pipe), there may be no need to bond — but if there are metal fittings downstream, assess whether bonding is still required. Some installers bond at the first metallic stop valve.

Oil supply pipe: Any incoming oil supply pipe must be bonded as a metallic service.

Structural steel: Large exposed metallic structures (steelwork, reinforced concrete frames) may need bonding per Regulation 411.3.1.2 — assess on a project-by-project basis.

What does NOT require main bonding:

Supplementary Bonding in Bathrooms

Amendment 2 to the 17th Edition (2015) significantly relaxed supplementary bonding requirements. Under the current 18th Edition BS 7671:2018+A2:2022:

Supplementary bonding is NOT required in a bathroom if:

Supplementary bonding IS still required if:

In practice: for new bathroom installations with all circuits on RCBO or RCD-protected ways, supplementary bonding is not needed. For older properties where you cannot confirm main bonding is present and in good order, supplementary bonding remains good practice.

When supplementary bonding IS installed, all simultaneously accessible metal parts in zone 1 and 2 must be interconnected: bath, shower tray, towel rail, waste pipe, supply pipes, radiator. Minimum 4mm² conductors.

Earthing Electrode Systems (TT)

TT systems require a local earth electrode. Common types:

Electrode resistance must be low enough that the earth fault loop impedance allows the RCD to operate. For a 30mA RCD, Zs ≤ 1667Ω — achievable with most soil conditions. For fuse protection, electrode resistance must be much lower.

Test electrode resistance using a proprietary earth electrode tester (4-terminal method) or clamp meter method on existing electrodes.

CPC Sizing

Circuit protective conductors within wiring systems:

Frequently Asked Questions

Do I need to re-bond if the gas pipe has been replaced with plastic?

If the incoming gas service pipe is now plastic (as many are after replacement), there may be no metallic path to bond. However, if the internal installation pipework is copper or steel with a metallic connection to the meter, you must bond at that metallic point within 600mm. If the entire installation including meter connection has been converted to plastic push-fit, bonding at that service may no longer be applicable — but document your assessment. Other services (water, oil) still require bonding.

Is bonding required on plastic incoming water pipes?

MDPE blue plastic incoming mains need no bonding themselves, but if the first fitting inside is metallic (brass stop valve), the bonding should still be applied to that fitting. The purpose is to prevent potential differences on accessible metalwork — so any exposed metal downstream of plastic still warrants consideration.

What happens if main bonding is missing on an EICR?

Missing main bonding is a C2 (potentially dangerous) code on an EICR — meaning it should be investigated and rectified urgently. It does not mean the building is immediately dangerous, but it significantly reduces protection against step potential and touch voltage in fault conditions. Landlords with C2 codes must remediate within 28 days.

Can I use the gas or water pipe as an earth for socket circuits?

No. This was sometimes done in older installations but is dangerous and non-compliant. Bonding conductors are connected TO the MET FROM the pipes — not using the pipe as an earthing conductor for circuits. Using a service pipe as an earth can cause corrosion, introduce dangerous currents into the pipework, and fails to provide a proper low-impedance fault path.

Regulations & Standards