Boiler to Heat Pump Migration Checklist: Radiator Survey, Pipe Sizing, Cylinder and Grant Eligibility

Quick Answer: Migrating from a gas/oil boiler to an air source heat pump is not a like-for-like swap — because heat pumps run at lower flow temperatures (typically 35-50°C vs a boiler's 60-80°C), the existing emitters and pipework often need upsizing. The migration checklist is: room-by-room heat loss calculation (to MCS/BS EN 12831), radiator survey against the new low flow temperature, pipework sizing check, hot water cylinder sizing (heat pumps need a cylinder, even replacing a combi), electrical supply capacity, and grant eligibility under the Boiler Upgrade Scheme (BUS, £7,500 in England & Wales) which requires MCS certification and EPC with no outstanding insulation recommendations. Skip the heat loss calc and the system will underperform — the single biggest cause of unhappy heat pump customers.

Summary

The most expensive mistake in heat pump installation is treating it like a boiler swap. A boiler delivers heat at 60-80°C, so small radiators sized for that high temperature work fine. A heat pump is most efficient at low flow temperatures (35-50°C), and a radiator's output falls sharply as flow temperature drops — a radiator giving 1,500W at 70°C might only give 700-800W at 45°C. If you bolt a heat pump onto a system designed for a boiler without checking the emitters, the house won't heat in cold weather, the heat pump runs hard and inefficiently, and the customer is left cold and angry. Every credible migration starts with a heat loss calculation, not a heat pump model number.

This is fundamentally a system design job, not a product swap. You're redesigning the heat distribution: recalculating heat loss room by room, surveying every radiator against the new flow temperature, checking the pipework can carry the required flow, sizing a hot water cylinder (heat pumps almost always need one — they can't do instantaneous DHW like a combi), and confirming the electrical supply and the property fabric. Get the design right and a heat pump delivers comfortable, efficient, low-carbon heat for decades; get it wrong and it's a noisy, expensive disappointment.

This checklist walks through each migration step, the standards and the grant framework (Boiler Upgrade Scheme, MCS certification, MCS 3005/MCS 007). It's a cross-reference hub linking the detailed articles on each topic. For the heat loss method see heat pump sizing heat loss; for radiators see radiator sizing for heat pumps; for cylinders see heat pump cylinder sizing; for the grant see bus grant scheme guide.

Key Facts

Migration Checklist (Quick Reference)

Spending too long on quotes? squote turns a 2-minute voice recording into a professional quote.

Try squote free →
Step What to Check Standard / Reference
1. Heat loss calc Room-by-room heat demand at design conditions BS EN 12831 / MCS
2. Radiator survey Output of each emitter at the new flow temp radiator sizing for heat pumps
3. Pipework Primary/branch sizes carry required flow MCS 3005 / MIS 3005
4. Cylinder Add/upsize cylinder with large coil heat pump cylinder sizing
5. Electrical Dedicated circuit, main fuse, DNO if needed BS 7671
6. Fabric / EPC Insulation level; EPC for BUS epc ratings
7. Siting & noise Location, clearances, MCS 020 noise Permitted development conditions
8. Grant & MCS BUS eligibility, MCS certification bus grant scheme guide

Detailed Guidance

Step 1 — Heat Loss Calculation (Do This First, Always)

Everything flows from the heat loss calculation. You measure each room (dimensions, fabric, windows, exposure) and calculate the heat loss at the design external temperature (typically -2 to -3°C depending on region) and the desired internal temperatures, to BS EN 12831 as required by MCS. This gives:

A "rule of thumb" or boiler-size match is not acceptable and won't pass MCS. See heat pump sizing heat loss.

Step 2 — Radiator Survey

This is where boiler-to-heat-pump migrations live or die. A radiator's heat output is quoted at a standard temperature difference (often Δ50, i.e. 70°C mean water temp into a 20°C room). Drop the flow temperature to 45°C and the mean water temperature falls, the Δ falls, and output drops dramatically — often to around half.

For each room, compare the required output (from the heat loss calc) against the actual output of the existing radiator at the new flow temperature. Radiators that fall short must be:

Many migrations need 30-60% of radiators upgraded. Underfloor heating is ideal for heat pumps (large surface area, very low flow temp) where it can be installed. See radiator sizing for heat pumps and radiator heat pump compatibility.

The honest customer conversation: "To run efficiently and keep you warm, the heat pump runs cooler than your boiler, so some radiators need to be bigger. Here's which ones and why." Customers who understand this up front are happy; those surprised by it mid-job are not.

Step 3 — Pipework Sizing

Heat pumps move more water at a lower temperature than boilers, so they need higher flow rates and adequately sized pipework. Common findings:

Undersized pipework starves the system of flow, causing poor heat distribution and high pump energy. The pipework check is part of MCS-compliant design. See pipe materials and pipe compatibility.

Step 4 — Hot Water Cylinder

A heat pump cannot produce instantaneous hot water like a combi boiler, so:

Heat pump cylinders have a large heat exchanger coil (commonly ~3m² or more) so they can transfer heat into the water at the heat pump's low flow temperature, and are sized on the household's hot water demand (number of occupants/bathrooms). Reheat times are longer than a boiler, so sizing for peak demand matters. See heat pump cylinder sizing and cylinder selection.

Step 5 — Electrical Supply

A heat pump is an electrical appliance drawing significant current. Check:

This is electrician's work and must be designed to BS 7671:2018+A2:2022. See heat pump wiring.

Step 6 — Fabric and EPC

Heat pumps work best in reasonably insulated homes (they deliver gentle, continuous heat). Before migration, assess the fabric — loft insulation, cavity/solid wall insulation, draught-proofing — both for performance and for grant eligibility:

See epc ratings, loft insulation, and cavity wall.

Step 7 — Siting, Noise and Permitted Development

The outdoor unit needs a location with airflow clearance, a stable base, condensate drainage (with frost protection), and acceptable noise. Most domestic ASHPs are permitted development but subject to conditions: a single unit, sited to minimise visual/noise impact, not on a flat roof/within set distances of boundaries in some cases, and (key) an MCS 020 noise assessment demonstrating the noise at the neighbour's window is within limits. Listed buildings, conservation areas, and flats often fall outside PD and need planning permission. See heat pump noise planning.

Step 8 — Grant Eligibility and MCS

The Boiler Upgrade Scheme (BUS) pays £7,500 toward an air source heat pump in England & Wales (ground source higher; Scotland uses Home Energy Scotland grant + loan). Requirements:

MCS certification is the gateway — without it, no BUS grant. The installer must be MCS registered for the technology. See bus grant scheme guide, mcs 007 heat pump standard, and mcs certification explained.

Commissioning and Controls

A heat pump is commissioned and runs differently from a boiler: continuous operation with weather compensation (the flow temperature adjusts to outdoor temperature) rather than on/off cycling to a thermostat. Setting it to mimic a boiler (high flow temp, on/off) destroys efficiency. Proper commissioning sets the weather compensation curve, balances the radiators for even flow, and educates the customer that "low and slow" is correct. See heat pump commissioning checklist and heat pump controls setup.

Frequently Asked Questions

Can I just swap a boiler for a heat pump on the same radiators?

Almost never without checking. Heat pumps run at lower flow temperatures (35-50°C vs a boiler's 60-80°C), and radiator output drops sharply at lower temperatures — a radiator may give only ~half its boiler-temperature output. You must do a room-by-room heat loss calculation and a radiator survey; typically 30-60% of radiators need upsizing or supplementing. Skipping this is the number one cause of cold houses and unhappy heat pump customers.

Do I need a hot water cylinder with a heat pump?

Yes, in almost all cases. A heat pump can't produce instantaneous hot water like a combi boiler, so it heats a cylinder. If you're replacing a combi you must add a cylinder (needing space and adding cost); if replacing a system boiler you usually replace the cylinder with a heat-pump-specific one that has a large coil (~3m²+) to transfer heat at the low flow temperature. Cylinder sizing is based on the household's hot water demand.

How much is the heat pump grant and what are the conditions?

The Boiler Upgrade Scheme (BUS) gives £7,500 toward an air source heat pump in England & Wales (Scotland uses Home Energy Scotland grant + loan). Conditions: an MCS-certified installer designing/installing to MCS 3005, a valid EPC with any loft/cavity wall insulation recommendations addressed, and replacing a fossil fuel system. The installer applies and discounts the grant from the price. Without MCS certification there's no grant.

Will the existing pipework be big enough?

Often not. Heat pumps need higher flow rates than boilers, so microbore (8/10mm) is frequently inadequate and primaries often need to be 22mm or 28mm. The pipework must be checked as part of MCS-compliant design — undersized pipe starves the system, causing poor heat distribution and high pump energy. Plan for some pipework upgrading on most older systems.

Does a heat pump need planning permission?

Most domestic air source heat pumps are permitted development, but subject to conditions: siting/clearance, only one unit, and an MCS 020 noise assessment showing acceptable noise at neighbouring windows. Listed buildings, conservation areas, and flats frequently fall outside permitted development and need planning permission. Always check the specific siting and the local planning position before committing.

Regulations & Standards