Heat Pump Cylinder Sizing: Unvented DHW Cylinders, Buffer Tanks, Coil Size and Legionella Pasteurisation

Quick Answer: A heat pump DHW cylinder must be sized for the household's daily hot water demand plus the heat pump's recovery characteristics. A typical 3–4 person household requires a 200–250 litre unvented cylinder with a large heat exchanger coil (to allow effective heat transfer at heat pump flow temperatures of 50–55°C). An immersion heater provides the weekly 60°C legionella pasteurisation cycle. Buffer tanks (50–200 litres) are sometimes added to prevent short-cycling and smooth heat pump operation.

Summary

Domestic hot water (DHW) is one of two primary demands on a heat pump (the other being space heating). Heat pump DHW cylinders differ from conventional indirect cylinders in two critical ways: the heat exchanger coil must be large enough to transfer adequate heat at low flow temperatures (50–55°C rather than the 70–80°C of a boiler), and an immersion heater is required for legionella pasteurisation.

Correct cylinder sizing is a required element of MCS 007 design documentation. Undersized cylinders lead to morning DHW recovery failures; incorrectly sized coils lead to poor heat pump efficiency or an inability to heat the cylinder to the required temperature.

Key Facts

Quick Reference Table: Cylinder Sizing by Household

Spending too long on quotes? squote turns a 2-minute voice recording into a professional quote.

Try squote free →
Household Size Minimum Cylinder Size Heat Pump Coil Area (typical) Notes
1–2 persons 150 litres 1.5–2.0 m² Showers only typical
3 persons 200 litres 2.0–2.5 m² Allow 250L if bath primary
4 persons 250 litres 2.5–3.0 m² Standard family home
5+ persons 300+ litres 3.0 m²+ May require twin-coil or larger unit
High demand (large baths, multiple bathrooms) 300–400 litres 3.0 m²+ Consider twin coil or electric boost

Detailed Guidance

Heat Pump Cylinder Selection

Coil size and heat transfer: A conventional boiler-heated indirect cylinder typically has a coil surface area of 0.8–1.2 m². At boiler flow temperatures of 70–80°C, this is adequate for rapid heat transfer. At heat pump flow temperatures of 50–55°C, the log mean temperature difference (LMTD) across the coil is much smaller — heat transfer is proportional to coil area × LMTD. A coil that is too small cannot transfer enough heat at heat pump temperatures, resulting in:

Heat pump compatible cylinders have coil surface areas of 2.0–3.0 m² — typically 2–3× the area of a standard indirect cylinder. This larger coil allows effective heat transfer at 50–55°C flow temperature.

Standing heat loss: Well-insulated cylinders (factory-fitted foam insulation, minimum 50mm) minimise standing heat loss. For heat pumps operating on tight running cost margins, a cylinder with a low daily heat loss figure (≤1.0 kWh/day for a 200L cylinder) is preferable.

Common heat pump cylinders:

Buffer Tank Application

When a buffer tank is NOT required: For most correctly designed heat pump systems with weather compensation and either:

... a buffer tank is not required. The heating circuit provides sufficient water volume to prevent short-cycling.

When a buffer tank IS required:

Buffer tank sizing: A buffer tank is typically 50–150 litres for a domestic ASHP installation. The buffer adds thermal mass to the circuit, allowing the heat pump to run for longer continuous periods before stopping.

Hydraulic separation: Some buffer tanks are installed as hydraulic separators (low-loss headers) between the heat pump primary circuit and the heating distribution circuit. This allows the heat pump and heating circuit pump to operate at different flow rates without hydraulic interference.

Legionella Pasteurisation

Why heat pump DHW needs special attention: Legionella bacteria proliferate between 20–45°C. A conventional boiler cylinder stored at 65°C is lethal to Legionella. A heat pump cylinder stored at 50°C is at the upper limit of the proliferation range — not ideal.

HSE L8 compliance for heat pump DHW:

  1. Store at 50–55°C daily (acceptable: limits proliferation but not elimination)
  2. Weekly pasteurisation to 60°C for 1 hour minimum — kills Legionella throughout the cylinder
  3. The pasteurisation cycle is performed by the immersion heater (the heat pump cannot reliably reach 60°C at a useful COP — most heat pumps' COP falls sharply above 55°C)
  4. Programme the pasteurisation to occur overnight or during off-peak electricity tariff hours to minimise running cost impact

Practical setup: Most heat pump controllers include a "legionella protection" schedule. Set to:

DHW Priority and COP Impact

Efficiency impact of DHW heating: Heating DHW to 50–55°C is less efficient than heating space heating circuits to 40–45°C. The additional temperature lift reduces the ASHP's COP:

For accurate SCOP (Seasonal COP) calculation, the DHW contribution must be included. The proportion of the heat pump's annual output used for DHW typically represents 20–30% of total demand for a well-insulated property.

Minimising DHW running cost:

Frequently Asked Questions

Can the heat pump heat the DHW and the space heating simultaneously?

Most domestic ASHP controllers run in DHW priority mode — the heat pump dedicates its full output to DHW heating, then switches to space heating once the cylinder is satisfied. Simultaneous operation is possible on some models but less common. DHW priority heating for a 200L cylinder typically takes 2–3 hours; during this time, space heating is paused. On a well-insulated property, this is rarely noticeable.

Do I need a buffer tank if I have underfloor heating?

Usually not. Underfloor heating provides a large volume of water in the circuit (the UFH loops act as a thermal buffer) and operates continuously at low load. Short-cycling is rarely a problem with UFH systems. Buffer tanks are primarily needed in systems with small hydraulic volumes and aggressive zone control (multiple room thermostats shutting down the circuit).

Is a vented (open-vented) cylinder acceptable with a heat pump?

Technically yes, but open-vented cylinders operate at low pressure (gravity-fed), giving poor flow rates in multi-story properties. Unvented cylinders at mains pressure are the standard for heat pump DHW — they provide consistent pressure throughout the property and are compatible with modern showers and bathrooms. Open-vented systems are only specified where the building prohibits mains pressure (listed building restrictions, very old pipework) or where an existing vented system is being retained temporarily.

What is a "twin coil" cylinder and when is it needed?

A twin-coil cylinder has two heat exchanger coils: one connected to the heat pump, one connected to a secondary source (typically solar thermal panels or a solid fuel stove). For combined solar thermal + heat pump systems, a twin-coil cylinder allows both sources to heat the DHW without complex valving. The lower coil is connected to the solar thermal circuit (prioritised when solar is available); the upper coil is connected to the heat pump (tops up when solar output is insufficient).

Regulations & Standards