Summary
A retaining wall holds back soil whose natural angle of repose would otherwise slump. The forces on the wall are larger than most tradespeople intuitively realise — even 1m of saturated soil exerts several tonnes per linear metre of horizontal pressure on the wall face. This is why retaining walls fail unexpectedly: a wall that "looks fine" in summer collapses after a wet winter because hydrostatic pressure was never relieved.
UK practice categorises walls by construction type: gravity walls (mass concrete, gabion, stone), reinforced concrete walls, masonry cantilever walls (engineering brick or block on a concrete base), sheet pile walls, and segmental block walls (e.g. Kee block, Allan block, Marshalls Croft). Each has a height range and ground condition where it makes economic sense.
The typical domestic retaining wall — 600 to 1500mm high, holding back garden ground — is built either in engineering brick on a strip footing, or in dense concrete block rendered to finish, with a perforated drainage pipe behind. Walls above 1.2–1.5m start to need reinforcement and a designed footing, and unless the tradesperson has a structural design they should not build above this height.
Key Facts
- Permitted development limit — boundary retaining walls up to 1m next to a highway, 2m elsewhere (England/Wales)
- Building Regulations applicability — walls retaining ground that supports a building or roadway require structural design
- BS EN 1997-1 — Eurocode 7: Geotechnical design (replaces BS 8002 partial; both still cited)
- BS 8002:2015 — Code of practice for earth retaining structures
- BS 8004:2015 — Code of practice for foundations
- Active earth pressure — typical Ka (Rankine) 0.25–0.40 depending on soil and wall friction
- Hydrostatic pressure — saturated soil can double the pressure on the wall face
- Soil unit weight (γ) — typical dry sand 16 kN/m³, wet clay 20 kN/m³
- Mortar designation for retaining walls — Designation (iii) (1:1:6) or stronger; M6 mortar
- Bricks for retaining walls — Class B engineering bricks per BS EN 771-1 (frost resistance F2, low water absorption)
- Concrete grade — RC32/40 for reinforced walls per BS 8500
- Reinforcement cover — 50mm to face exposed to soil; 40mm to opposite face (XC2/XC4 exposure)
- Land drain behind wall — 100mm perforated PVC-u wrapped in non-woven geotextile
- Weep holes — every 800–1000mm horizontally, 150–200mm above ground level
- Coping — required to stop water entry at the top; brick on edge, stone or precast concrete coping with throat detail
Quick Reference Table
Spending too long on quotes? squote turns a 2-minute voice recording into a professional quote.
Try squote free →| Wall Type | Practical Height | Footing | Notes |
|---|---|---|---|
| Single-skin brick (102mm) | <600mm | Concrete strip 450 × 150mm | Retains light garden soil only |
| Double-skin brick (215mm) | 600–1000mm | Concrete strip 600 × 200mm | Class B engineering brick + M6 mortar |
| Engineering brick cavity wall | 1000–1500mm | Designed footing | Cavity filled with concrete + reinforcement |
| Mass concrete gravity | 1000–2000mm | Toe + heel concrete base | Width = ~1/3 height (rule of thumb) |
| Reinforced concrete cantilever | 1500–4000mm | Designed reinforced base | Engineer's calculations required |
| Gabion | 1000–4000mm | Compacted hardcore base | Stone 100–200mm, mesh BS EN 10223 |
| Segmental block (Allan/Kee) | 1000–2500mm | Compacted granular base + geogrid reinforcement | Manufacturer's design tables |
| Sheet pile | 1500–6000m+ | Driven below excavation level | Specialist plant — out of scope of typical groundworker |
| Sleeper wall (timber) | <800mm | Concrete posts or driven posts | Temporary or low-grade application |
Detailed Guidance
Designing the foundation
The footing of a retaining wall is engineered to resist three modes of failure:
Failure Modes (BS 8002 / EC7)
1. Overturning — wall rotates about toe
Resistance moment ≥ 2.0 × overturning moment
2. Sliding — wall slides on its base
Friction + passive resistance ≥ 1.5 × horizontal force
3. Bearing — soil under toe fails in compression
Ultimate bearing ≥ 3.0 × maximum toe pressure
For a domestic wall up to 1m, NHBC Standards Chapter 7.1 gives nominal dimensions: footing width approximately 2/3 wall height, footing depth at least 200mm into firm ground, founded below frost line (450mm in southern England, 600mm in north).
Concrete strip footing for 1m wall (example)
For a 1m double-skin engineering brick wall holding back garden soil:
- Excavate footing trench 600mm wide × 400mm deep (or to firm strata)
- Lay 50mm GEN 1 binding (optional but tidier)
- Pour GEN 3 (C20/25) concrete to 200mm depth
- Cure 24 hours before laying bricks
- Lay DPC at 150mm above ground level on the soil-retaining face
- Build wall in Class B engineering brick, English bond or Flemish bond
- Mortar designation (iii) — 1:1:6 cement:lime:sand
Drainage behind the wall
This is the single biggest failure mode in domestic retaining walls. Saturated soil exerts hydrostatic pressure on top of normal soil pressure, often doubling the force on the wall. Drainage rules:
- Perforated land drain — 100mm PVC-u perforated pipe along the back of the footing, falling 1:200 minimum to an outlet
- Outlet — soakaway, surface water drain, or daylight to lower ground
- Drainage stone — 20–40mm clean angular stone, 200–300mm wide column behind the wall
- Geotextile wrap — non-woven membrane around the stone to prevent fines migration
- Weep holes — 75–100mm pipe through the wall every 800–1000mm, 150mm above finished ground level
- Backfill in lifts — compact granular backfill in 200mm lifts (don't dump and trample)
Coping and top detail
Water penetration at the top of the wall causes frost damage in winter. Always:
- Project the coping 25mm minimum either side of the wall (drip)
- Cut a throat (groove) underneath the projecting coping
- Bed coping in (iii) mortar
- Seal coping joints with flexible sealant if exposed
Movement joints
Retaining walls expand and contract with temperature. BS 5628 / BS EN 1996 specifies movement joints in clay brick at 10–12m and in concrete block at 6m. For shorter walls, build the wall in single bays without joints — for longer walls, plan joints at architectural break points.
Reinforced retaining walls
For walls above 1.2–1.5m the bricklayer/builder will be working from an engineer's drawing showing:
- Footing dimensions and reinforcement (typically T10 / T12 bars top and bottom)
- Vertical wall starter bars cast into the footing
- Vertical reinforcement up the wall (often A142 mesh on the back face or vertical T10s at 200mm centres)
- Cover requirements (typically 50mm to soil face)
- Concrete grade (RC32/40)
- Drainage detail
Critical points on these walls:
- Starter bars must be the full lap length (typically 35× bar diameter) before any vertical bar can be lapped
- Reinforcement must not be cut to make the wall easier to build
- Cover must be maintained with proprietary spacers, not lumps of brick
- Cube samples may be required by the engineer or Building Control
Gabion walls
A gabion wall is a stack of rock-filled wire baskets. Useful for low-grade retaining (highway embankments, garden walls) where the look is acceptable. Key points:
- Use galvanised or PVC-coated mesh to BS EN 10223-3 (galvanised wire BS EN 10218-2)
- Stone fill 100–200mm angular, hand-placed against the visible face
- Tie baskets together with helical lacing wire
- Base course on 200mm compacted Type 1 sub-base
- Step back successive courses 100mm per 1m height for stability
- Gabions are heavy — 1m³ ≈ 1.7 tonnes; consider crane access
Frequently Asked Questions
Do I need Building Regs for a 1m garden retaining wall?
Probably not if it is a freestanding garden boundary wall not supporting a building or roadway, but planning consent may still be needed if higher than 1m fronting a highway or 2m elsewhere, or in conservation areas / listed building curtilage. Always check with the local planning authority.
Can I build a retaining wall in concrete block?
Yes — dense concrete blocks to BS EN 771-3 (compressive strength 7.3 N/mm² or higher) bedded in (iii) mortar are widely used for retaining walls up to 1.2m. Finish with cement render or a slip-on brick face for appearance. Cellular blocks and lightweight aircrete blocks are not suitable.
What's the minimum cover for reinforcement in a retaining wall?
For exposure class XC2 (buried concrete), minimum cover is 25mm; for XC4 (exposed to wetting and drying), 35mm. UK practice usually specifies 40–50mm on the soil face for retaining walls — the engineer's drawing will state the figure.
Do I need weep holes if I have a land drain?
Yes — they back up the land drain. If the drain blocks (silt, root intrusion), weep holes give a secondary route for water to escape rather than building up behind the wall. They should be 75mm minimum, fitted with a small grille if rodent ingress is a concern, and located at the level of the drainage stone behind.
How long after the footing can I build on it?
Concrete strip footings reach approximately 65–75% of strength at 7 days. For domestic retaining walls, 24 hours is the minimum before laying bricks, but if the wall is heavy or the ground is soft, waiting 3 days reduces the risk of differential settlement showing in the wall above.
Regulations & Standards
BS EN 1997-1:2004+A1:2013 — Eurocode 7: Geotechnical design (general rules)
BS EN 1997-2:2007+A1:2010 — Eurocode 7: Ground investigation and testing
BS 8002:2015 — Code of practice for earth retaining structures
BS 8004:2015 — Code of practice for foundations
BS 8500-1 / 2:2023 — Concrete: specification (incl. cover, exposure classes)
BS EN 1996 (Eurocode 6) — Design of masonry structures
BS EN 771-1 — Specification for masonry units: clay (brick frost resistance class F2)
Building Regulations Approved Document A — Structure
NHBC Standards Chapter 7.1 — Retaining walls
CDM Regulations 2015 — Excavation, support, manual handling
Construction Plant-hire Association (CPA) guidance — Use of mini-excavators in proximity to retained ground
Institution of Structural Engineers — Manual for the design of plain masonry — Domestic retaining wall design
The Brick Development Association — Brickwork retaining wall details
Concrete Centre — Retaining Walls — Reinforced concrete cantilever wall design
NHBC Standards Chapter 7.1 — Retaining walls in new-build warranty
British Standards Institution — BS 8002 — Earth retaining structures
HSE — Excavation safety — Trench and footing safety
foundations — Footing types and depths
trench safety guide — Working safely in retaining wall excavations
soil types and bearing capacity — Bearing capacity input to wall design
concrete mix ratios guide — Specifying GEN 3 / RC25/30 mixes for footings
engineering bricks — Class B engineering brick specification