Summary

Gas tightness testing is a mandatory check after any work on a gas installation — whether a new boiler installation, a pipe repair, or the reconnection of an appliance. The test verifies that no gas is escaping from the pipework or fittings. Unlike flue gas analysis (which checks combustion products), tightness testing checks the integrity of the physical pipe system itself — every joint, valve, fitting, and connection from the meter outlet to the appliance isolation valves.

The procedure uses the working gas pressure already in the system (typically around 20–21 mbar for natural gas on a standard domestic installation) as the test pressure. The engineer closes off the meter and notes the pressure, then waits. A pressure drop beyond the permissible limit for that installation's volume indicates a leak. This is different from higher-pressure purging tests used on new pipework, which use air or nitrogen at higher pressures.

Standard in transition (as of this review, August 2026): IGEM/UP/1B Edition 4 was published in March 2026 and becomes mandatory from 1 October 2026. Edition 3 remains valid until it is withdrawn on 30 September 2026 — both editions are technically live during this transition window, and Gas Safe expects engineers to move to Edition 4 as soon as practicable. The single biggest change: permissible pressure drop is no longer a flat figure tied to meter size — it is now calculated from the Installation Volume (IV) of the pipework under test, banded across several ranges (smaller IV = larger permissible drop, since a small leak represents a bigger proportional loss in a small volume of gas). Edition 4 also formally defines "perceptible movement" on the gauge (0.25 mbar on a water gauge, 0.2 mbar on a high-resolution electronic gauge) and adds a mandatory pipework-only retest step when appliances are connected. Do not rely on a single "1 mbar" or "4 mbar" rule of thumb under either edition — calculate the installation volume and check the current permissible-drop table.

The "let-by test" is a related but distinct check. It tests whether the meter governor (the regulator controlling pressure downstream of the meter) is seating correctly and not letting gas past when it should be closed. A let-by fault means gas is leaking through a closed governor — serious, and requiring a DNO call, not a DIY fix. Engineers must be familiar with both tests and when each is appropriate.

Key Facts

Quick Reference Table

Need to quote gas work? squote generates accurate, professional quotes fast.

Try squote free →
Test Type What It Checks Method Pass Criteria
Let-by test Meter/ECV seating Close ECV; monitor pressure rise No pressure rise in 2 min
Working pressure tightness Installation pipework integrity Pressurise; close meter; monitor Permissible drop set by Installation Volume (IGEM/UP/1B Edition 4, mandatory from 1 Oct 2026) — not a flat figure; see Detailed Guidance below
Strength test New pipework integrity Air/nitrogen at higher pressure Per IGEM/UP/1B for the pipe size and type — consult current edition
Standing pressure Supply adequacy Open appliance; measure pressure ≥17 mbar natural gas
Working pressure (gas rate) Appliance input Meter reading vs rated input Within ±5% of rated

Detailed Guidance

Pre-Test Checks

Before carrying out a tightness test:

  1. Confirm the property has a gas supply (meter present and connected)
  2. Identify the Emergency Control Valve (ECV) — typically a lever valve at the meter, turns 90° to close (lever across = off)
  3. Note any smell of gas — if strong smell is detected, do not operate switches, ventilate the property, and call the national gas emergency service on 0800 111 999 before proceeding
  4. Identify all appliances and their isolation valves; close all isolation valves
  5. Allow the system pressure to stabilise at working pressure before beginning

Let-By Test Procedure

The let-by test is carried out first. It checks whether the meter governor is seating (closing) correctly when the downstream pressure builds up to the governor set pressure. A governor that is "letting by" is allowing gas through even when it should be closed.

LET-BY TEST PROCEDURE

1. Ensure all appliances and isolation valves are CLOSED
2. Connect manometer to test point (test nipple after meter)
3. Note working pressure (should be ~20 mbar)
4. Close the Emergency Control Valve (ECV) at the meter
5. Watch the manometer for 2 minutes

RESULT:
├── Pressure RISES → Let-by detected
│   ├── Gas is leaking past the meter governor
│   ├── DO NOT proceed with installation work
│   ├── Call the gas emergency service: 0800 111 999
│   └── Advise customer; vacate if significant
│
└── Pressure STABLE (no rise) → Let-by test PASSED
    └── Proceed to working pressure tightness test

Working Pressure Tightness Test Procedure

TIGHTNESS TEST PROCEDURE

1. Re-open ECV; confirm pressure at working level (~20 mbar)
2. All appliance isolation valves remain CLOSED
3. Close ECV again to isolate the system
4. Note the starting pressure on the manometer
5. Wait 1–2 minutes (observe clock — be precise)
6. Note the final pressure

RESULT:
├── Pressure DROP exceeds the permissible limit for this
│   installation's calculated volume (IGEM/UP/1B table) → FAIL — LEAK PRESENT
│   ├── Open ECV to restore pressure
│   ├── Use calibrated gas detector on all joints
│   ├── Apply soap solution to suspected joints
│   ├── Locate, repair, and retest
│   └── Do NOT commission appliance until pass is achieved
│
└── Pressure DROP within the permissible limit → PASS
    ├── Under IGEM/UP/1B Edition 4, also carry out the mandatory
    │   pipework-only retest — any perceptible movement fails
    ├── Record test result with start pressure, end pressure,
    │   duration, calculated installation volume, and outcome
    └── Proceed to purging before commissioning appliance

Do not use a flat "1 mbar" or "4 mbar" pass/fail figure. The permissible drop depends on the calculated Installation Volume (IV) of the pipework under test — see the transition note above.

Locating Leaks After a Failed Test

When a tightness test fails, the leak must be located before proceeding. Methods in order of preference:

  1. Calibrated gas detector — electronic combustible gas detector (CGI); sweep all accessible pipework joints, valves, and fittings; start at the meter and work downstream. A detector gives a percentage of lower explosive limit (%LEL) reading; any reading above background indicates gas presence.

  2. Soap solution — apply a soap-based detection fluid (purpose-made leak detection spray, or washing-up liquid diluted with water) to each joint. Bubbles form where gas is escaping. Use this to confirm individual joints after the CGI has indicated the area.

  3. Isolation method — for large installations or where leaks are not quickly found, isolate sections of pipework by closing intermediate valves and retesting each section. This narrows the leak to a specific section.

Do not use a naked flame to detect gas leaks.

Purging After Tightness Test

After a successful tightness test, the installation pipework must be purged to remove any air introduced during the test or repairs. Purging is carried out per IGEM/UP/1B:

Recording and Reporting

A written record of the tightness test must be made at every visit and must include:

This record should be retained by the engineer and a copy provided to the customer (or landlord/agent as appropriate).

Frequently Asked Questions

How is a tightness test different from a gas safety check?

A gas safety check (CP12 for landlords) includes a tightness test as one of its components, but also covers appliance inspection, flue check, and combustion testing. A standalone tightness test is simply the pipework pressure check — it's required after any work on gas pipework before an appliance is reconnected.

Can a small pressure drop (e.g. 0.5 mbar) be accepted?

Whether it's acceptable depends on the permissible drop for the calculated Installation Volume of the pipework being tested (IGEM/UP/1B) — there is no single flat figure across all installations. Under Edition 4, "perceptible movement" itself is now formally defined (0.25 mbar on a water gauge, 0.2 mbar on a high-resolution electronic gauge), so a genuinely tiny reading may not even count as movement. Separately, temperature change in the test environment can affect pressure readings — a warm room cooling slightly can cause an apparent pressure drop. Allow for this by testing in stable conditions and repeating if results are borderline. Do not accept a borderline result without investigating.

What do I do if I find a leak I cannot reach (pipework under concrete)?

If the leak is in embedded pipework that cannot be accessed, the options are: rerouting the pipework to an accessible route, or (with appropriate specialist advice) using a corrosion-resistant approved gas pipe sleeve system. The appliance must not be recommissioned until the leak is rectified.

When is a strength test required instead of a working pressure test?

A strength test (at higher pressure, typically with air or nitrogen) is required for new pipework before it is connected to the gas supply. Once installed and pressure-tested at higher pressure, a working pressure tightness test is carried out before the gas is turned on. The working pressure test is the routine check after any reconnection or repair work.

Regulations & Standards