Summary
Gas pressure testing is the final safety verification step in any gas installation, repair, or commissioning job. It establishes whether the gas supply pipework and fittings are leak-free before the system is energised. Every Gas Safe registered engineer must be competent in gas tightness testing — it is a mandatory requirement of the Gas Safety (Installation and Use) Regulations 1998.
In UK domestic practice, the procedures follow IGEM/UP/1B (Institution of Gas Engineers and Managers — Utilisation Procedure 1B), Tightness testing and direct purging of small LPG/Air, natural gas and LPG installations. This is the definitive specification for domestic-sized installations: pipework up to 35mm copper / 32mm steel with a maximum operating pressure not exceeding 2 bar at the ECV outlet. (IGEM/UP/1C is a different document — it covers strength testing, tightness testing and purging of meter installations, and IGEM/UP/1 and UP/1A cover industrial and commercial installations.)
Edition change: IGEM/UP/1B Edition 4 was published in March 2026 and becomes mandatory from 1 October 2026, superseding Edition 3. The headline change for natural gas is that permissible pressure drops are now determined by installation volume (IV) rather than meter size, and where a drop is within the whole-system limit you must now isolate the appliances and re-test the pipework alone, which must show no perceptible movement. Until 1 October 2026 both editions are technically valid.
A tightness test must be carried out:
- After any new gas pipework is installed
- After any existing pipework is disturbed (joint opened, extension added, meter changed)
- As part of a Landlord Gas Safety Check (LGSC) annual inspection
- On commission of any new gas appliance
Understanding the test procedures, pressure limits, pass/fail criteria, and what to do on failure is fundamental knowledge for any Gas Safe registered engineer.
Key Facts
- Test pressure — natural gas: 20–21 mbar for the domestic tightness test, after a 1-minute stabilisation period. IGEM/UP/1B does not require a strength test for domestic installation pipework
- Test pressure — LPG: propane tested against a valve (no regulator in the section) 36–37 mbar; propane tested through a regulator 30–31 mbar; butane depends on the regulator fitted — 20–21 mbar for a 28 mbar system, up to 36–37 mbar for a 37 mbar system. LPG testing requires different test equipment and procedures
- Manometer type: U-tube manometer (water-filled) or electronic digital manometer. The manometer must be calibrated to read in mbar. An electronic manometer is more accurate and readable at low pressures
- Test duration: 1 minute stabilisation, then 2 minutes test time — this applies to natural gas, LPG and LPG/Air alike
- Pass criterion: New pipework, or any installation with no appliances connected — no perceptible gauge movement ("perceptible" = 0.25 mbar on a water gauge or a digital manometer reading to two decimal places). Existing installations with appliances connected have a small permissible drop based on installation volume (see table below). Any perceptible movement must be investigated — it must not be written off as meter tolerance or temperature change
- Let-by test: Specifically tests whether the Emergency Control Valve (ECV) at the meter is seating correctly. Close the ECV, raise the pressure downstream to between 7 and 10 mbar, and observe for 1 minute — any pressure rise (gas letting by past the closed valve) indicates ECV failure. The same 7–10 mbar let-by pressure applies to natural gas, LPG and LPG/Air
- Working pressure check: With all appliances on, the working pressure should not drop more than 1 mbar below the standing pressure. A greater drop indicates under-sized pipework or a supply pressure problem
- Never use a naked flame — Using a lighter or match to detect a gas leak is extremely dangerous. Always use approved leak detection fluid (soapy solution or proprietary detector fluid) or an electronic gas detector
Quick Reference Table
Need to quote gas work? squote generates accurate, professional quotes fast.
Try squote free →| Gas Type | Standing Pressure | Working Pressure | Test Pressure (tightness) |
|---|---|---|---|
| Natural gas (mains) | 21 mbar | ≥20 mbar at the appliance | 20–21 mbar |
| LPG — Propane | 37 mbar (low pressure regulator) | 35–37 mbar | 36–37 mbar against a valve; 30–31 mbar through a regulator |
| LPG — Butane | 28 mbar | 27–28 mbar | 20–21 mbar (28 mbar system); 36–37 mbar (37 mbar system) |
Maximum permissible pressure drop over the 2-minute test — natural gas, existing installation with appliances connected (IGEM/UP/1B Edition 4, by installation volume):
| Installation Volume (IV) | Max permissible drop |
|---|---|
| ≤ 0.005 m³ | 8 mbar |
| > 0.005 – ≤ 0.010 m³ | 4 mbar |
| > 0.010 – ≤ 0.015 m³ | 2.5 mbar |
| > 0.015 – ≤ 0.035 m³ | 1 mbar |
New pipework, or any installation with no appliances connected: no perceptible movement. Under Edition 4, if the whole-system test shows a drop that is within the limit above, you must then isolate the appliances and re-test the pipework alone — that pipework-only test must show no perceptible movement. Under Edition 3 (valid until 1 October 2026) permissible drops were determined by meter type rather than installation volume — check which edition your training and paperwork reflect.
| Test Type | Purpose | When Used |
|---|---|---|
| Tightness test (let-by) | Verify pipework soundness; check ECV seats | After any new installation or disturbance |
| Working pressure test | Confirm adequate supply pressure under load | Commissioning any new appliance |
| Visual inspection | Identify visible defects before pressure test | As part of any service or installation |
| Electronic leak detection | Locate a detected leak in existing pipework | When tightness test fails |
Detailed Guidance
Equipment Required
Before any gas pressure test, ensure:
- Calibrated manometer — Electronic digital manometer (Pocketed or similar) preferred for domestic use. Must be calibrated and in date. U-tube water manometer acceptable but harder to read at low pressures
- Flexible connection hose — To connect the manometer to the test nipple at the gas meter or isolation valve. Must be gas-rated and in good condition
- Leak detection fluid — Approved soapy solution in a squeeze bottle, or proprietary leak detector spray (Snoop, EasySeal detector). Never use washing-up liquid neat — it can corrode brass fittings
- Gas detector (electronic) — Catalytic bead or infrared gas detector for pinpointing leaks. Calibrated and in date
- PTFE tape and jointing compound — For remaking any failed connections
The Domestic Tightness Test (IGEM/UP/1B Procedure)
This procedure applies to natural gas domestic installations:
Step 1 — Visual inspection: Before applying any test pressure, carry out a visual inspection:
- Check all pipework for corrosion, mechanical damage, incorrect installation, or unsafe materials
- Check that all appliances are turned off at their controls (but not isolated at meter)
- Check that the installation pipe does not pass through any unsafe route
Step 2 — Connect manometer:
- Connect the manometer to the test point on the meter. The test point is typically a 1/8 inch BSP plug on the outlet side of the meter
- Ensure the manometer is properly connected and the hose is not kinked or damaged
Step 3 — Purge test point nipple:
- Briefly open the test point to purge any air from the connection. Close the test point and allow the manometer to stabilise with gas pressure. The standing pressure should read approximately 21 mbar
Step 4 — Let-by test (ECV check):
- Close the Emergency Control Valve (ECV) at the gas meter
- Raise the pressure downstream of the ECV to between 7 and 10 mbar (using a pressure pump, or by cracking the ECV briefly and re-closing it)
- Observe the manometer for 1 minute
- If the pressure remains stable: the ECV is seating — continue
- If the pressure rises by any perceptible amount (0.25 mbar or more): gas is passing through the closed ECV (let-by). Do not proceed — the situation must be made safe and reported to the gas transporter (National Gas / Cadent / SGN / Northern Gas Networks depending on region)
Step 5 — Tightness test of installation pipework:
- With the ECV closed, raise the pressure to 20–21 mbar for natural gas
- Allow the pressure to stabilise for 1 minute, then time the test for 2 minutes
- Pass — new pipework or no appliances connected: no perceptible gauge movement (perceptible = 0.25 mbar) and no smell of gas
- Pass — existing installation with appliances connected: any drop is within the permissible limit for the installation volume (8 / 4 / 2.5 / 1 mbar — see the table above), and there is no smell of gas. Under Edition 4 you must then isolate the appliances and re-test the pipework alone, which must show no perceptible movement
- Fail: the drop exceeds the permissible limit, or there is a smell of gas — a leak exists
Step 6 — On failure:
- Open the ECV and restore gas supply
- Use leak detection fluid on all joints, connections, and fittings — start at the most recent work and work outward
- Use an electronic gas detector for concealed pipework (under floors, in voids)
- Once the leak is found, make the repair, then re-test from Step 2
Step 7 — Pass — working pressure test:
- Open the ECV and allow standing pressure to stabilise
- Turn on all gas appliances simultaneously (all hob burners, oven, boiler, etc.)
- Observe the manometer under working load — the working pressure should not drop below 20 mbar (i.e., no more than 1 mbar below standing pressure)
- Fail (pressure drops excessively): Insufficient gas supply. Check pipe sizing — refer to BS 6891 (the standard for domestic installation pipework up to 35mm, whose Annex A tables cover sizing) to confirm adequate capacity for the total load. Pipework above 35mm, or loads beyond the BS 6891 tables, falls under IGEM/UP/2. May indicate a meter/regulator fault or undersized pipework
Step 8 — Document results:
- Record the test results on the Benchmark commissioning sheet, the Landlord Gas Safety Record (LGSR), or on a job record sheet
- Record: standing pressure, working pressure, tightness test result (pass/fail), and any remedial actions taken
New Pipework Installation Testing
IGEM/UP/1B does not require a separate strength test for domestic installation pipework. New domestic pipework is proved by the tightness test at 20–21 mbar, with the stricter pass criterion: no perceptible gauge movement over the 2-minute test.
Strength testing at elevated pressure is a requirement of the other documents in the UP/1 family, and applies to different work:
- IGEM/UP/1C — strength, tightness testing and purging of natural gas and LPG meter installations
- IGEM/UP/1A — small low-pressure industrial and commercial installations
- IGEM/UP/1 — industrial and commercial installations generally
So for a new extension, a complete re-pipe, or a routine appliance change in a domestic property, the IGEM/UP/1B tightness test alone is the correct procedure. If the job involves the meter installation itself, or a commercial property, check which document applies before testing — the procedures and pressures are not interchangeable.
Landlord Gas Safety Check (LGSC)
The annual gas safety check required under the Gas Safety (Installation and Use) Regulations 1998 for rented properties includes a tightness test of the installation pipework. The procedure is the same as above.
The Landlord Gas Safety Record (LGSR) must be completed for each appliance checked, and the tightness test result recorded. Copies must be:
- Provided to the existing tenant within 28 days of the check
- Provided to a new tenant before they move in
- Retained by the landlord for 2 years
Unsafe Situations and GIUSP Classifications
The Gas Industry Unsafe Situations Procedure (GIUSP) is set out in IGEM/G/11 Edition 2 (with amendments July 2022, June 2024 and July 2025), published for registered engineers as Gas Safe Technical Bulletin TB 001. It defines three classifications — note these are letter codes, not numbered ID codes:
| Code | Situation | Action |
|---|---|---|
| ID — Immediately Dangerous | Fault presents an immediate danger to life or property | With the customer's permission, disconnect and make safe; label and warn — do not use |
| AR — At Risk | Fault not immediately dangerous, but a risk exists if use continues | With the customer's permission, turn off and label; warn and advise immediate repair |
| NCS — Not to Current Standards | Does not meet the current standard but is not ID or AR | Advisory only — record and recommend upgrade; the appliance may continue in use |
IGEM/G/11 Table 1 gives worked examples of ID and AR situations, but it is not exhaustive — the engineer must exercise engineering judgement and be able to justify the classification.
A failed tightness test with a confirmed, unlocated gas escape is an ID situation. The engineer must:
- Turn off the gas at the ECV
- Issue the GIUSP Warning/Advice Notice to the customer (and to the landlord where the property is let)
- Label the installation with the classification and the engineer's details
- Record on the job sheet and, on a landlord check, the LGSR
- Report to the gas emergency service / transporter where required by the GIUSP
The engineer must not leave a property with a confirmed gas leak unless the gas is off at the meter and the customer has been warned.
Frequently Asked Questions
My gas meter has no test point. How do I carry out a tightness test?
Older meters may not have a test point nipple fitted. Alternatives: (a) fit a temporary test point adaptor to the outlet union of the meter; (b) use a test point on the first isolation valve downstream of the meter. The test must be carried out downstream of the ECV — testing upstream is testing the incoming supply, which is the gas transporter's responsibility, not yours.
Can I carry out a tightness test for a tenant?
Yes — if you are Gas Safe registered in the appropriate category (Domestic Natural Gas). You must complete the Landlord Gas Safety Record and provide copies to the landlord and tenant as described. If you are not Gas Safe registered, you cannot carry out any gas work, including testing.
A joint I've just made is bubbling on the leak detection test. What do I do?
Turn off gas at the meter. Remake the joint: for compression fittings, this means disassembling and replacing the olive if possible, or tightening further (one quarter-turn at a time). For threaded joints, remove and re-apply PTFE tape or jointing compound. For soldered joints, resolder (drain and dry the pipe first). Re-test the joint after any repair.
How do I test for gas leaks in concealed pipework?
An electronic gas detector is the most effective tool for locating leaks in inaccessible pipework. Run the probe along the suspected route of the pipe (along skirting boards, through inspection hatches). The detector will alarm as it approaches the source. Once the general area is identified, if access is needed, open up carefully — do not use power tools near a suspected gas leak (spark risk).
Regulations & Standards
Gas Safety (Installation and Use) Regulations 1998 (GSIUR) — Legal framework for all gas work in the UK
IGEM/UP/1B — Tightness testing and direct purging of small LPG/Air, natural gas and LPG installations. This is the governing document for domestic tightness testing. Edition 4 published March 2026, mandatory from 1 October 2026
IGEM/UP/1C — Strength testing, tightness testing and direct purging of natural gas and LPG meter installations (not domestic installation pipework)
IGEM/G/11 Edition 2 — Gas Industry Unsafe Situations Procedure (GIUSP), with amendments July 2022, June 2024 and July 2025
Gas Safe TB 001 — Technical bulletin publishing the GIUSP for registered businesses
BS 6891:2015 — Installation and maintenance of low pressure gas installation pipework up to 35mm on premises (domestic pipe sizing tables, Annex A)
IGEM/UP/2 — Installation pipework on industrial and commercial premises (for pipework above 35mm or loads beyond BS 6891)
Gas Safe Register — Technical Bulletins — TB 001 (GIUSP) and all current technical guidance for registered engineers
IGEM Publications — UP/1B, G/11 and UP/2 — Definitive procedures for gas installation testing and unsafe situations
HSE — Gas Safety — Regulatory framework and enforcement guidance
cooker connection — Gas cooker bayonet fitting and commissioning
boiler servicing — Annual service including gas pressure checks
gas safe registration — Gas Safe registration categories and requirements
smell of gas — Responding to suspected gas leak call-outs