Summary

A customer ringing to say water is coming out of the light is frightened, and rightly: water in a ceiling rose or a downlight sits across the live and neutral terminals and the earth of the fitting, and the first person to reach up and touch it is standing on a wet floor. The call-out is therefore two jobs in one. The electrician's job is to make the installation safe and, later, prove it is safe to re-energise. The plumber's or roofer's job is to find where the water is coming from and stop it. A single multi-skilled tradesperson can do both, but the order matters: safe first, trace second, repair third, test and reinstate last.

The trace is where most time is lost. The fitting is the exit point, not the source. Water that reaches the back of a plasterboard ceiling runs along the top of the board until it finds a hole, and the hole it finds is the cable entry at the rose or the cut-out for a downlight. A bath waste leaking at the far corner of a bathroom can appear at a landing light three metres away. The leak is upstream of the light in the direction of fall of the joists, the cables or the pipes, and the quickest way to find it is to work out what is directly above and nearby, then run water tests one source at a time.

This guide covers the make-safe steps, a decision tree for the trace, the common sources by what is above the ceiling, the ceiling and electrical repairs, the test before re-energising, and what to charge.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
When it drips What is above Most likely source First check
Only when the shower or bath is used Bathroom Sealant at the tray or bath edge, tray waste, shower screen seal Run the shower onto the wall and floor separately for 5 minutes each with a dry sheet below
After a bath empties Bathroom Bath waste or overflow, trap joint, waste pipe joint Fill and empty with the bath panel off and a torch on the waste
After the WC is flushed Bathroom or cloakroom Pan connector, cistern-to-pan doughnut, flush pipe Flush with dry tissue around the connector and under the cistern
In heavy rain only Roof Slipped tile, flashing, valley, roof window Inspect from the loft during rain with a torch
In cold clear weather Loft Condensation on the underside of the felt or on a cold-water tank Look for drip marks on the insulation in the loft
Heating on, especially first thing Pipework Radiator valve or tail, compression joint in the floor void Dry tissue on every joint on the radiators above
Constant slow drip, all conditions Mains or cold-feed pipework, tank overflow Pinhole, joint, passing float valve Check the loft tank level and overflow; listen at the stopcock with everything off
Only when an appliance runs Washing machine, dishwasher, boiler Hose, filter, condensate, pressure relief Run the appliance and watch it

Detailed Guidance

Step 1 — make it safe

Go to the consumer unit before you go to the light. Identify the lighting circuit; if the labelling is poor, switch off the main switch and accept that the house will be dark for a while. Lock off if you can; at the least, tape the MCB and tell everyone in the house not to touch it. Then, and only then, go to the room.

Do not operate the light switch; a wet switch drop is as dangerous as the rose. Put a bucket under the drip. Look at the ceiling for a bulge: a plasterboard ceiling will hold several litres before it sags, and when it fails it goes all at once. If there is a bulge, pierce it at its lowest point, well away from the fitting and the cable route, and let it drain into the bucket.

If the fitting is a downlight, do not try to remove it with water still coming through. If it is a pendant, do not pull the flex. Leave it until the circuit is proven dead with a voltage indicator tested on a proving unit before and after.

Water from a light fitting
        |
Switch off lighting circuit at the CU (main switch if unsure)
        |
Prove dead at the fitting with a tested voltage indicator
        |
Catch the water; relieve any ceiling bulge away from the fitting
        |
Is the drip continuous?
        |
   YES ---------> Mains, cold feed, tank or heating pipework.
        |         Turn off the stopcock: does it stop within an hour?
        |           YES -> mains-fed pipe or fitting above
        |           NO  -> heating system, stored water, or roof
        |
   NO (intermittent)
        |
What is directly above and one room each way?
        |
   Bathroom ------> Run each fixture in turn for 5 minutes,
        |           dry sheet below, 20 minutes between tests
   Roof/loft -----> Torch inspection in the loft, in rain if possible;
        |           look for wet felt, tide marks, drips on insulation
   Bedroom -------> Radiators and heating pipes in the floor void
        |
Found it ---------> Repair, dry, test circuit, reinstate
Not found --------> Lift boards or cut an inspection hole in the
                    ceiling upstream of the fitting, in line with
                    the cable or pipe run

Step 2 — trace from what is above

Stand under the fitting and work out what is above it and within about two metres in each direction. Then test one source at a time with a dry towel or sheet laid on the floor below the ceiling patch and twenty minutes between tests so you can attribute the water.

Bathroom above. Start with the shower, because it is the commonest source and the one customers do not suspect. Run it onto the walls only, then onto the tray only. A failed silicone bead at the wall-to-tray or wall-to-bath junction lets water behind the tray every shower; the tray waste leaks only when the tray fills; the screen seal leaks only where the water hits it. Then the bath: fill it, check the overflow by filling to the overflow, empty it and watch the waste and trap with the panel off. Then the WC: flush and check the pan connector and the close-coupling. Then the basin. A leak that appears only with a particular fixture is found in half an hour this way; a leak that appears with all of them is a waste-pipe joint downstream of them.

Bedroom or landing above. The floor void carries heating pipes, and the radiators in the room above are the first suspects. Dry tissue on each valve gland, each tail and each union; look for the green crust on copper and the white crust on brass. If the pipes run under the floor in notches, a compression joint in a notch that has been stood on will weep. Lift a board at the joist bay above the light.

Top floor, roof above. Go into the loft with a torch, in rain if the leak is rain-related. Look for daylight through the tiles, a wet patch on the felt, water running down a rafter, a blocked or overflowing valley, and the flashing at any chimney or abutment. Follow the drip marks on the top of the insulation back to where they start. If the felt is uniformly damp on the underside with droplets and there is no daylight, it is condensation, not a leak, and the fix is ventilation (see condensation in loft). Check the cold-water storage cistern: a passing float valve that overflows onto the loft floor instead of through the overflow pipe is a classic source of a landing-light drip.

Cupboards and utility spaces above. A boiler's condensate pipe, pressure relief discharge or a leaking filling loop; an unvented cylinder tundish that has started to discharge; a washing machine hose. These show up at the kitchen or hall light below.

Step 3 — repair the source and dry the void

Repair the leak, then give the ceiling void time to dry before closing anything up. Plasterboard that has been soaked once will usually dry flat if it is allowed to; board that has been wet for days sags and is replaced. Loft insulation that is saturated is removed and replaced, because it does not dry and it carries the damp to the board. Timber joists dry on their own; check them with a moisture meter after a week if there is any sign of rot.

If an inspection hole was cut, leave it open until the void has dried, then patch it with a piece of board on noggins, tape and fill.

Step 4 — electrical inspection and test before re-energising

With the circuit still isolated, remove the fitting. A plastic ceiling rose or a lamp holder that has held water is replaced, not dried; the terminals corrode and loosen later. A downlight is replaced with the same fire rating as the original. Dry the cable ends, re-strip any conductor that shows green or black corrosion, and check the junction box or the loop-in rose above for the same.

Then test. With lamps out and any electronic drivers, smart switches or transformers disconnected, carry out an insulation-resistance test at 500 V d.c. between line and neutral joined together and earth, and between line and neutral. BS 7671:2018+A2:2022 Table 61 gives 1 MΩ as the minimum for a 230 V circuit; a sound dry lighting circuit reads well above 100 MΩ, and anything below about 2 MΩ says there is still water somewhere in the circuit, usually in a switch drop or a junction box you have not found yet. A continuity test on the protective conductor and a polarity check complete the picture. Record the results on a Minor Electrical Installation Works Certificate, which the customer's insurer will want to see.

Only then re-energise, and only the lighting circuit first, watching for an RCD trip.

Step 5 — the ceiling

A stain that has dried flat is sealed with a stain-blocking primer (an ordinary emulsion will let the brown bleed through) and painted. A patch that has sagged, or a board that is soft when pressed, is cut back to the centre line of the adjacent joists and replaced; tape, fill, sand, prime, paint. If the ceiling is lath and plaster, the plaster around a wetted area loses its key and comes away later; press it and cut back to sound keys.

Pricing

Item Typical charge (ex VAT, 2026)
Emergency electrical make-safe, isolate and prove dead, daytime £80–£150
Same, out of hours £150–£250
Leak trace, up to 2 hours including water tests £120–£250
Replace ceiling rose or pendant and test circuit, certificate £90–£160
Replace a downlight, like for like, and test £60–£110
Insulation-resistance test and Minor Works Certificate (standalone) £60–£100
Reseal a bath or shower tray £80–£150
Replace a bath waste and trap £90–£160
Repair a radiator valve or tail £70–£130
Refit a slipped tile or patch a flashing from a ladder £120–£250
Patch a plasterboard ceiling (up to 600 × 600 mm), fill and paint £150–£300
Replace a full ceiling in a bathroom (up to 6 m²) £500–£900

Keep the make-safe and the trace as separate lines and give the customer a written note of where the water came from. The insurer pays for trace and access and for reinstatement, but only with a report that says what was found.

Frequently Asked Questions

The RCD tripped and the light went off by itself. Is it safe now?

Safer, but not safe. The RCD has disconnected the circuit, but it will reset if someone pushes it, and if the RCD covers more than the lighting circuit the household will be tempted to. Switch the lighting MCB off as well, label it, and treat the circuit as live until it is proven dead at the fitting. An RCD trip in these circumstances also tells you water has reached the earth path, so the fitting and probably the rose will need replacing.

The customer wants the light back on tonight. Can I just dry it with a hairdryer?

Not without the test. A fitting that has been wet may look dry and still read a few hundred kilohms to earth, which is a shock risk and, on a non-RCD circuit, an eventual fire risk as the tracking carbonises. If the insulation-resistance test passes after drying and the terminals are clean, the circuit can go back on with the fitting replaced; if it does not pass, the circuit stays off and the customer uses a lamp on a socket circuit until it does.

The leak only happens when it rains, but the loft is dry. Where is it?

Look at the walls, not the roof. Water entering through a cracked render band, a defective window head or a cavity tray can run down inside the wall and along the ceiling board from the perimeter, appearing at the first fitting in from the wall. Check the top of the external wall above the room in rain, and look for a wet patch at the top of the inside wall before you condemn the roof.

Do I need to replace all the loft insulation that got wet?

Replace any mineral wool that is saturated, because it holds water against the board and the joists for weeks and it loses most of its thermal performance when it has been wet. Insulation that is slightly damp on the surface from a single short leak dries if it is lifted and the loft is ventilated. Do not put the new insulation back until the board below is dry.