Summary

Solis inverters are among the most widely installed on UK domestic solar PV systems because of their price point and the broad range of single-phase string models (Mini 4G, S5, S6) and hybrid models (RHI, S5-EH1P, S6-EH1P, S6-EH3P) used with battery storage. The alarm scheme is shared across the range: a plain text label on the display and in SolisCloud, backed by a numeric code (1010, 1011 and so on) that is useful for support tickets but is not consistent between firmware versions or regional documentation. Diagnose from the text label and treat the number as a secondary reference.

Most Solis call-outs in the UK are grid-side. The UK statutory voltage range is 230 V +10 % / −6 % (216 to 253 V), and on a sunny afternoon in a street with several PV systems exporting, the local voltage at the inverter terminals can exceed 253 V. The inverter is required under G98 and G99 to disconnect at the stage-1 overvoltage setting of 262.2 V for 1 s (stage 2 at 273.7 V for 0.5 s), wait the reconnection delay, then reconnect. The customer sees lost generation and an OV-G-V01 alarm; the installation is behaving exactly as the grid code demands. Measuring and logging the AC voltage at the inverter, then reporting to the DNO, is the fix; raising the trip threshold is not permitted without DNO agreement.

The DC-side family is where safety lives. PV ISO-PRO means the inverter's pre-connection insulation test found the array's resistance to earth below the threshold (nominally 1 MΩ, in line with the BS EN 62446-1 commissioning minimum), and ILeak-PRO means the integrated residual-current monitor has seen leakage current above its limit while running. Early-morning dew, rain and condensation in a rooftop DC isolator cause both, and the alarm often clears by midday. When it does not, there is a damaged cable, a wet connector or a failing module junction box, and the array must be string-tested before the inverter is restarted. For the brand-agnostic version of this logic see solar inverter error codes.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Alarm (display text) Typical ID Family Likely cause in UK installs First action
OV-G-V01 1010 Grid Local voltage rise above 262.2 V stage-1 limit Log AC voltage at inverter; report to DNO if above 253 V regularly
OV-G-V02 to 04 1011–1013 (varies) Grid Short, higher overvoltage spikes As above; check for loose AC terminations
UN-G-V01/02 1014–1015 (varies) Grid Undervoltage below 184 V, loose AC terminal, long run Measure AC under load; check terminations and cable size
OV-G-F / UN-G-F varies Grid Wrong grid standard; rare real frequency event Confirm G98/G99 selected
NO-Grid varies Grid AC isolator off, MCB tripped, lost neutral Check AC path from cut-out to inverter
G-IMP varies Grid High AC loop impedance Measure Zs at inverter AC terminals
GRID-INTF 1030 Grid AC transient / power board Restart once; recurring = warranty
PV ISO-PRO01/02 1033 DC safety Insulation < 1 MΩ; moisture, damaged cable Do not restart; string insulation test when dry
ILeak-PRO01–04 1034 DC safety Leakage > ~30 mA; wet isolator or connector Do not restart; isolate strings one at a time
OV-DC01/02 varies DC String Voc above inverter max on cold morning Check string design against max input voltage
OV-TEM 1032 Internal Over-temperature; ventilation, sun, fan Clearances, shade, clean heatsink; sensor if persistent
RelayChk-FAIL 1035 Internal Output relay self-test failed Restart; warranty if it returns
DSP-B-FAULT 1036 Internal Processor communication or firmware mismatch Firmware check; warranty
OV-Vbatt / UN-Vbatt varies Hybrid Battery outside voltage window Check BMS, battery DC isolator, SOC limits
CAN-FAIL varies Hybrid BMS comms lost CAN cable pinout and termination; battery model selected

Numeric IDs are shown as reported in current Solis service documentation; they differ between firmware versions and regional guides, so quote the text label in any support ticket.

Detailed Guidance

Decision tree

SOLIS INVERTER ALARM
=====================
1. Read the text alarm on the LCD or SolisCloud and open the
   alarm history. One event, or a daily pattern?

2. Which family?
   OV-G-V / UN-G-V / OV-G-F / UN-G-F / NO-Grid / G-IMP -> 3
   PV ISO-PRO / ILeak-PRO                              -> 4
   OV-DC / OV-BUS / UN-BUS                             -> 5
   OV-TEM / Relay / DSP / IGBT / DC-INTF / Fan         -> 6
   Vbatt / CAN-FAIL / Meter                             -> 7

3. GRID
   - Grid standard set to G98 or G99? (Advanced Settings)
       NO  -> set it; most frequency alarms vanish here
   - Measure AC voltage at the inverter terminals, inverter
     running, around midday:
       > 253 V repeatedly   -> DNO voltage-rise report
       Big drop under load  -> loose terminal, undersized or
                               long AC cable, high Zs (G-IMP)
       0 V                  -> NO-Grid: isolator, MCB, fuse,
                               neutral
   - Alarm only at peak sun on sunny days -> voltage rise,
     not an inverter fault; export limitation may help

4. DC SAFETY (do not simply reset)
   - Does it clear by late morning on a dry day?
       YES -> moisture; find the entry point (roof DC isolator,
              MC4s, module junction box) and reseal/replace
       NO  -> array fault
   - Isolate DC. Test each string: Voc, then insulation
     resistance PV+ to earth and PV- to earth at 1000 V
     (>= 1 MΩ; a reading that falls while the test holds =
     moisture). ISO-PRO01 points to the negative side,
     ISO-PRO02 to the positive
   - Inspect: rodent damage, abrasion on tile edges, cable
     ties cut into insulation, water in the DC isolator
   - Fix the cause, retest, then restart

5. DC VOLTAGE
   - OV-DC: string Voc (modules x Voc at -10 °C) vs inverter
     max input (commonly 600 V single-phase). Re-string if
     the design is marginal
   - OV-BUS / UN-BUS at dawn/dusk only -> usually benign;
     persistent during the day -> internal, warranty

6. INTERNAL
   - OV-TEM: 300 mm clearance each side, 500 mm above/below,
     out of direct sun, heatsink clear; fan running?
   - Others: power down AC then DC, wait 5 minutes, restart
     once. Returns -> log serial number and firmware,
     warranty claim via installer/distributor

7. HYBRID / BATTERY
   - CAN-FAIL: correct battery model selected; CAN lead
     pinout (Solis uses specific pins for different battery
     brands); termination resistor
   - OV/UN-Vbatt: battery BMS limits vs inverter settings;
     battery DC isolator on; SOC and voltage in the app
   - Meter-FAIL: RS485 wiring, meter address, CT direction

OV-G-V01 and UK voltage rise

This is the Solis alarm every UK solar installer sees most. The UK statutory limit at the customer's terminals is 253 V, and the G98/G99 stage-1 overvoltage protection the inverter must implement trips at 262.2 V after 1 s. Between those values the inverter keeps running but may see OV-G-V alarms as the voltage at its own terminals is higher than at the cut-out, because the inverter's export current raises voltage along the AC cable run. Check three things in order:

  1. Measure the AC voltage at the inverter AC terminals with the inverter exporting, and at the cut-out at the same time. A large difference means AC cable volt drop; shorten the run, increase the CSA, or tighten terminations.
  2. Log the voltage over several sunny days. SolisCloud records grid voltage; a pattern of alarms between 11:00 and 15:00 on clear days is network voltage rise.
  3. Report to the DNO. The DNO is obliged to keep the supply within statutory limits and can retap the local transformer. Export limitation via a meter and the inverter's export-power setting is a workaround, not a fix, and should be agreed with the customer because it loses them generation. The inverter's own overvoltage thresholds must not be raised without written DNO consent. See dno g98 g99 applications.

PV ISO-PRO and ILeak-PRO: the safety branch

Both alarms mean the DC side has lost its separation from earth. On a dry day with the inverter isolated, perform the BS EN 62446-1 insulation test string by string: positive to earth and negative to earth at 1000 V DC, held for one minute; the pass figure is 1 MΩ. A reading that starts high and falls during the test indicates moisture tracking rather than a hard fault. Common UK findings are water inside a rooftop DC isolator (the most frequent), MC4 connectors left unmated or mated to a different manufacturer's part, cable insulation cut by a tile edge or a cable tie, and a cracked module junction box. Repair, retest and only then restart. Record the readings on the test certificate; see solar pv fault finding for the wider array fault-finding method and solar pv earthing and bonding for the earthing arrangement the test assumes.

OV-TEM and installation clearances

Solis specifies free air clearance around the inverter and derates output above its rated ambient. An inverter in a south-facing loft at 45 °C, a cupboard with no airflow, or mounted directly above a hot-water cylinder will throttle and eventually raise OV-TEM. Keep roughly 300 mm clear each side and 500 mm above and below, out of direct sun, with the heatsink fins vertical and clean. Fan-cooled models should be audible under load; a silent fan on a hot unit is a Fan-FAIL even if that alarm has not yet appeared. If clearances and airflow are correct and the unit still reports OV-TEM at modest load, the temperature sensor or its connection is suspect.

Hybrid-specific alarms

On RHI and S5/S6-EH hybrids the battery communicates over CAN. CAN-FAIL after a firmware update, a battery swap or a new installation is almost always the battery model setting or the CAN lead: Solis uses different RJ45 pin pairs depending on the battery brand selected, and a lead made for one brand will not talk to another. OV-Vbatt and UN-Vbatt indicate the battery pack voltage is outside the inverter's configured window, which can be a genuine BMS protection event (cold battery, cell imbalance) or a mismatch between the inverter's battery settings and the pack. Meter-FAIL on an export-limited system stops generation on some firmware, so check the RS485 meter wiring and the CT direction first. See solar battery storage installation.

What to charge

Job Typical UK price (ex VAT)
Diagnostic visit, alarm history review, AC/DC measurements £80–£150
Grid standard correction and recommissioning £80–£120
String insulation test, DC isolator replacement, reseal £150–£300
AC cable termination repair and Zs test £90–£160
Inverter warranty swap (labour only) £150–£250
Replacement 3.6 kW single-phase string inverter, supplied and fitted £650–£1,000
Replacement 5 kW hybrid inverter, supplied and fitted £1,200–£1,900

See solar pv installation pricing guide for whole-system pricing.

Frequently Asked Questions

The alarm says OV-G-V01 every sunny afternoon but the system works in the morning. Is the inverter faulty?

Almost certainly not. The inverter is disconnecting because the local grid voltage exceeds the G98/G99 overvoltage limit when several nearby systems export at once. Measure and log the voltage, then report to the DNO. Do not raise the trip threshold.

Can I just reset a PV ISO-PRO alarm?

The inverter will retest insulation on every start-up, so resetting does nothing harmful in itself, but the alarm means the array has a path to earth. If it does not clear once the roof is dry, isolate and test each string before anyone works near the DC side. Leaving an array with low insulation resistance live is a shock risk under BS 7671:2018+A2:2022 Section 712.

Which grid standard should a UK Solis be set to?

G98 for systems up to 16 A per phase (3.68 kW single-phase) and G99 for larger systems, matching the DNO notification or application made for the installation. The setting is in Advanced Settings behind the installer password. A wrong standard causes nuisance voltage and frequency trips.

Why does the numeric code in SolisCloud not match the list in the manual?

Solis has changed the numeric mapping between firmware generations and regional documents, so 1011 may be UN-G-V01 in one list and OV-G-V02 in another. The text label is stable; use it for diagnosis and quote it, with the serial number and firmware version, in any support ticket.

Does an OV-DC alarm mean the inverter is damaged?

Not necessarily. It means the string open-circuit voltage exceeded the inverter's maximum input, which happens on cold, bright mornings when module Voc rises. Recalculate the string at −10 °C; if it exceeds the inverter maximum, the string must be shortened. Repeated OV-DC events can eventually damage the input stage.