Summary
Roof windows (Velux is the common trade name, but Fakro, Roto, Dakea, Keylite and others share the same construction) leak far less often than they are blamed for. The classic winter call is a customer who finds water on the glass, the frame and the plasterboard reveal every cold morning. That is condensation: a bedroom or bathroom generating moisture, a sloping glass surface that is the coldest thing in the room, and often a reveal that was never insulated or fitted with a vapour barrier. No flashing work will cure it.
The genuine leaks divide by where the water appears and when. Water at the top corners or the top rail during rain points to the head flashing and the underlay detail above the window: a missing drainage gutter, an underlay collar left off, or tiles cut so tight that the top apron cannot do its job. Water down one side points to the side flashings, side gutters blocked with moss or debris, or a flashing kit for the wrong roof covering. Water at the bottom rail is the sash seal, the glazing gasket, a sash not fully latched, or wind-driven rain through the ventilation flap. Misting between the panes is the sealed glazing unit, replaced as a cassette on most modern windows.
This article gives you a diagnostic sequence that separates these in one visit, a hose-test method, the repair for each cause, and the thresholds at which replacing the flashing kit or the window is better value than another tube of sealant. For prices see skylight repair pricing guide; for installing from new see roof window installation.
Key Facts
- Condensation first — if the wetness correlates with cold weather and not with rain, and the glass is wet inside, it is condensation. Check extract ventilation (Approved Document F Volume 1: 15 l/s intermittent in a bathroom, 30 l/s adjacent to a hob or 60 l/s elsewhere in a kitchen) and the reveal insulation before anything on the roof.
- Misted between panes — sealed-unit failure. The outer seal has failed and moisture has entered the cavity. Only a replacement glazing unit (cassette on most windows since the late 1990s) cures it.
- Flashing kits are covering-specific — Velux uses EDL for slate and flat coverings, EDW for profiled tiles up to 120 mm, EDZ for lower-profile tiles, and EDN or EDJ for recessed installation; other brands have equivalents. A profiled-tile kit on slate, or a slate kit on pantiles, leaks at the side and sill aprons.
- Underlay collar and drainage gutter — the collar (Velux BFX) seals the window to the roof underlay and the gutter diverts water running down the underlay around the window. Leaks that appear in the loft above the window during long rain, with dry flashings, are usually a missing collar or gutter.
- Minimum pitch — 15° for standard installation to most manufacturers' instructions and BS 5534:2014+A2:2018; some low-pitch flashing kits take this to 10°. Below the minimum, water sits on the sill apron and the sash seal and finds a way in.
- Tile and slate gaps — tiles and slates must be cut to the gap the flashing instructions specify at the sides and must overlap the head flashing by the manufacturer's stated amount. Tight cuts lift the aprons; wide gaps leave the side flashings exposed to splash.
- Insulation collar and vapour barrier — a window fitted without an insulation collar (Velux BDX) and vapour barrier (BBX) cold-bridges the frame and lets room moisture into the roof void. The result is condensation at the reveal corners that looks like a leak.
- Ventilation flap — the top-control flap admits air through a filter even when the sash is locked. In driving rain at low pitch it can admit water; it should be closed in storms.
- Sash latching — a sash that does not pull fully home against its gasket (misaligned keeper, worn gasket, debris) leaks at the bottom rail in wind-driven rain. Check by closing on a sheet of paper around the perimeter.
- Glazing gasket — the external gasket around the glass hardens and cracks after 15 to 25 years. Water tracks under it and emerges at the bottom corners of the sash.
- Replacement U-value — 1.4 W/m²K or better for replacement roof windows (measured in the vertical plane) in existing dwellings under Approved Document L Volume 1 (2021 edition); rooflights measured horizontally have a 2.2 W/m²K limit. The work is notifiable unless done by a competent person scheme member.
- Loft conversions — a roof window used as an escape window must have an openable area of at least 0.33 m², at least 450 mm high and 450 mm wide, with the bottom of the opening 800 to 1,100 mm above floor level (Approved Document B Volume 1 2019, paragraph 2.10). Do not downsize when replacing.
Quick Reference Table
Diagnosed the problem? Create a repair quote in minutes with squote.
Try squote free →| Symptom | Timing | Most likely cause | Confirm by |
|---|---|---|---|
| Wet glass inside, drips off bottom of frame | Cold mornings, any weather | Condensation | Dry weather occurrence; hygrometer; extract fan check |
| Wet plasterboard at bottom reveal corners, stain spreading | Winter, no rain link | Cold bridge at reveal (no insulation collar or vapour barrier) | Open reveal; feel for cold, missing insulation |
| Milky or misted glass that will not wipe off | Any | Sealed-unit failure | Visual; cannot be reached from either side |
| Water at top corners or top rail inside | During or after rain | Head flashing, missing underlay collar or drainage gutter | Hose test on head only; inspect from loft |
| Water running down one side of frame | During rain, worse with wind from that side | Side flashing, blocked side gutter, wrong kit, tight tile cut | Hose test one side; lift tiles and inspect |
| Water at bottom rail or sill inside | Wind-driven rain | Sash gasket, latch misalignment, ventilation flap open | Paper test; close flap; hose test bottom only |
| Drips from frame some hours after rain stops | After rain | Water held in side gutters or on underlay, slow release | Inspect gutters for moss; check collar |
| Water in loft above window, flashings dry | Long rain | Underlay collar or drainage gutter missing | Inspect from loft during rain |
| Leak only in snow or after snow melts | Thaw | Snow bridging side gutters; meltwater backing up over aprons | History; check gutter depth and tile gap |
Detailed Guidance
Decision tree
ROOF WINDOW "LEAKING"
=====================
1. Does the water appear only with rain?
NO -> condensation or cold bridge. Go to 2.
YES -> go to 3.
Misted BETWEEN panes -> sealed unit. Replace glazing cassette.
2. CONDENSATION PATH
- Wet glass inside, dripping -> room humidity. Check extract fan
(15 l/s bathroom), trickle vents, heating pattern. Advise.
- Dry glass but wet plasterboard at reveal corners -> cold bridge.
Open reveal. No insulation collar / no vapour barrier -> fit
insulation around frame + vapour-control membrane, re-line.
- Bathroom window with no extract -> fan to Approved Document F
before anything else.
3. RAIN LEAK - WHERE does it show inside?
TOP rail or top corners -> go to 4
ONE SIDE -> go to 5
BOTTOM rail / sill -> go to 6
4. HEAD
- Lift tiles above window. Drainage gutter present? Underlay
collar lapped under underlay above and over at sides?
- Head flashing tucked under tiles by the specified overlap?
Tiles cut short / sitting on apron -> re-cut or re-dress.
- Mortar or sealant "repair" on the apron -> remove; find cause.
5. SIDE
- Side gutters full of moss/debris -> clear; advise annual clean.
- Tiles cut too tight (apron lifted) or too wide (flashing
exposed) -> re-cut to kit instructions.
- Kit type matches covering? Profiled kit on flat covering or
vice versa -> replace flashing kit.
- Slates: soakers or side flashings nailed through -> replace.
6. BOTTOM
- Ventilation flap open? Close; explain to customer.
- Paper test around sash: slips free at one point -> adjust
keepers / hinges; replace gasket if hard or cracked.
- Sill apron dressed onto tiles, not kinked upward -> re-dress.
- External glazing gasket perished -> replace gasket, or glazing
cassette if gasket is integral.
- Pitch below 15° without low-pitch kit -> no reliable repair;
replace with low-pitch kit or raise the window on a kerb.
Hose testing in the right order
Hose testing finds the entry point in one visit if it is done bottom-up and one zone at a time. Start with the sash closed and the ventilation flap shut. Run a gentle hose (not a jet) on the sill apron and bottom of the sash for ten minutes with someone inside watching. If dry, move to one side flashing, then the other, then the head flashing and the tiles above. Allow ten minutes per zone, because water takes time to track. Testing the head first soaks everything and tells you nothing. Record which zone produced water inside; that is the repair.
Condensation and the cold-bridged reveal
A roof window in a bathroom or bedroom is the coldest surface in the room. On a 2°C morning with the room at 60 % relative humidity, the inner pane of an old double-glazed unit falls below the dew point and runs. The fix is ventilation and heat, not roofing: an extract fan to Approved Document F Volume 1 running on a humidistat or overrun, trickle ventilation, and a constant low background heat rather than short blasts. See condensation on windows.
The more damaging variant is the uninsulated reveal. Many windows fitted in the 1990s and 2000s went in without an insulation collar or a vapour barrier. The timber frame and the gap between it and the rafters run cold, warm moist air gets into the roof void around the frame, and condensation forms on the plasterboard at the bottom corners of the reveal and inside the lining. It stains, blisters paint and grows mould, and it looks exactly like a leak. Opening the reveal shows dry roofing and a cold, often damp, gap around the frame. The repair is to pack the gap with insulation (mineral wool or the manufacturer's collar), fit a vapour-control membrane lapped onto the frame and the ceiling membrane, and re-line. BS 5250:2021 covers the principle of keeping the warm, moist side sealed.
Head flashings and the underlay detail
Water running down the roof underlay above the window has to be diverted around it. The flashing kit's drainage gutter sits on the battens above the window and does this; the underlay collar seals the frame to the underlay so water cannot run behind the frame. Both are routinely left out by installers in a hurry, and the window works for years until the underlay ages or a tile slips above and more water starts running on the underlay. The symptom is water appearing at the top corners inside, or dripping in the loft above the window, while the visible flashings are bone dry. Lifting three or four tiles above the window shows whether the gutter and collar are present. Fitting them retrospectively is a half-day job with the tiles above removed.
The head apron must also be tucked under the tiles by the kit's stated overlap and the tiles must not be cut so short that they sit on the apron and lift it. Mortar fillets or mastic along the head apron are a sign someone has already guessed.
Side flashings, gutters and the wrong kit
The side pieces of a flashing kit form a gutter between the frame and the cut tiles. Moss, leaves and grit collect here, water backs up above the lip and finds the frame. Clearing the gutters is the cheapest repair there is and should be an annual item for a window under trees. Tiles cut too tight lift the apron lip and let wind-driven rain over it; cut too wide they expose the flashing to splash and look wrong. The kit instructions give the gap for each range.
A kit for the wrong covering is a replacement, not a repair. Profiled-tile kits have a deep foam or lead-replacement sill apron and wide side pieces to dress into the tile profile; slate kits are flat and rely on soakers. Each leaks on the other covering. On slate roofs check also that the side flashings or soakers have not been nailed through by a well-meaning repair.
Sash, gasket and ventilation flap
Water at the bottom rail inside, worse when the wind is on that elevation, is the sash. Close the sash on a strip of paper at several points around the perimeter: it should grip everywhere. A point where it slips means the sash is not pulling home, usually because the keepers have moved, the hinges are worn, or the gasket has hardened. Adjust keepers first, then replace the gasket. Check the external glazing gasket for cracks; on older windows it is a separate rubber that can be replaced, on newer ones it is part of the glazing cassette.
The ventilation flap is designed to pass air through a filter with the sash locked. At low pitches and in horizontal rain it can pass water. If the customer's leak happens only in storms with the flap open, the cure is a closed flap and a conversation, not a roofer.
Repair or replace?
- Clear side gutters, re-dress aprons, adjust keepers: an hour or two, no materials.
- Replace gasket or glazing cassette: cassette supplied to the window code on the data plate; a half day.
- Fit a missing drainage gutter and underlay collar: half a day with tiles above removed.
- Replace the flashing kit: the right kit for the covering plus re-cutting tiles; most of a day.
- Replace the window: when the frame is rotten at the bottom rail, the pitch is below the kit's minimum, or the window is more than about 25 years old and both the glazing and the flashings are failing. A new window must meet the 1.4 W/m²K U-value and, in a loft conversion, keep the escape-window dimensions.
Frequently Asked Questions
Is the water on my roof window a leak or condensation?
If it happens on cold mornings regardless of rain and the glass itself is wet inside, it is condensation. If it appears during or just after rain and the glass is dry inside but water is running down the frame or the reveal, it is a leak. Misting between the panes is a failed sealed unit, which is neither.
Can I just seal around the flashing with mastic or lead sealant?
No. Flashing kits are designed to shed water by overlap, not by adhesion, and sealant across a lap traps water behind it. Mastic on a head apron almost always marks a leak that was never diagnosed. Find the entry point with a hose test and correct the detail.
Does a leaking roof window mean the whole thing has to come out?
Rarely. Most leaks are a blocked side gutter, a tile cut wrongly, a missing drainage gutter or collar, a worn gasket or a latch that needs adjusting. The window itself comes out when the frame is rotten, the pitch is below the kit's minimum, or it is old enough that glazing and flashings are failing together.
Why does it only leak when it snows?
Snow sits in the side gutters and against the aprons, then melts from below as the house warms the roof. Meltwater backs up above the lip of the side gutter or the head apron and finds the frame. A deeper gutter profile, correct tile gaps and an insulated reveal (so the roof around the window stays cold and snow melts evenly) reduce it.
Do I need Building Control to replace a roof window?
Yes in England and Wales, because a replacement roof window is a controlled fitting under Approved Document L Volume 1 and must achieve 1.4 W/m²K or better. A competent person scheme member can self-certify; otherwise a building notice is needed. In a loft conversion the window may also be the escape route and must keep its minimum opening size under Approved Document B Volume 1.
Regulations & Standards
Building Regulations 2010, Approved Document L Volume 1 (2021 edition) — replacement roof windows 1.4 W/m²K; rooflights 2.2 W/m²K; controlled fittings.
Approved Document B Volume 1 (2019 edition incorporating 2020 and 2022 amendments) — paragraph 2.10 escape window dimensions.
Approved Document F Volume 1 (2021 edition) — extract ventilation rates for bathrooms and kitchens.
Approved Document C (2004 edition incorporating 2010 and 2013 amendments) — resistance to moisture; condensation in roofs.
BS 5534:2014+A2:2018 — slating and tiling for pitched roofs; minimum pitches and fixing.
BS 8000-6:2013 — workmanship on construction sites: slating and tiling of roofs and claddings.
BS 5250:2021 — management of moisture in buildings; condensation control.
BS EN 14351-1:2006+A2:2016 — windows and external pedestrian doorsets: product standard (roof windows are within scope).
BS EN 13859-1:2014 — underlays for discontinuous roofing.
Approved Document L Volume 1: Dwellings (2021 edition) — replacement window and rooflight U-values.
Approved Document B Volume 1: Dwellings — escape window requirements.
Approved Document F Volume 1: Dwellings — extract ventilation rates.
VELUX UK: flashing selector and installation instructions — kit types by roof covering.
NHBC Standards Chapter 7.2: Pitched roofs — roof window and underlay detailing.
BSI Knowledge: BS 5534:2014+A2:2018 — code of practice for slating and tiling.
roof window installation — installing a roof window correctly: flashing, trimmers, collars and Part L.
skylight repair pricing guide — prices for reseal, reflash, glazing cassette and replacement.
condensation on windows — separating condensation from leaks on any window.
roof leak only in heavy rain — roof leaks by trigger; abutments and valleys.
pitched roof leak tracing — tracing water across a pitched roof from the loft.
rooflights skylights — flat-roof rooflights and kerb details.
velux skylight pricing guide — new roof window pricing.