Summary

Roof windows (Velux is the common trade name, but Fakro, Roto, Dakea, Keylite and others share the same construction) leak far less often than they are blamed for. The classic winter call is a customer who finds water on the glass, the frame and the plasterboard reveal every cold morning. That is condensation: a bedroom or bathroom generating moisture, a sloping glass surface that is the coldest thing in the room, and often a reveal that was never insulated or fitted with a vapour barrier. No flashing work will cure it.

The genuine leaks divide by where the water appears and when. Water at the top corners or the top rail during rain points to the head flashing and the underlay detail above the window: a missing drainage gutter, an underlay collar left off, or tiles cut so tight that the top apron cannot do its job. Water down one side points to the side flashings, side gutters blocked with moss or debris, or a flashing kit for the wrong roof covering. Water at the bottom rail is the sash seal, the glazing gasket, a sash not fully latched, or wind-driven rain through the ventilation flap. Misting between the panes is the sealed glazing unit, replaced as a cassette on most modern windows.

This article gives you a diagnostic sequence that separates these in one visit, a hose-test method, the repair for each cause, and the thresholds at which replacing the flashing kit or the window is better value than another tube of sealant. For prices see skylight repair pricing guide; for installing from new see roof window installation.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Symptom Timing Most likely cause Confirm by
Wet glass inside, drips off bottom of frame Cold mornings, any weather Condensation Dry weather occurrence; hygrometer; extract fan check
Wet plasterboard at bottom reveal corners, stain spreading Winter, no rain link Cold bridge at reveal (no insulation collar or vapour barrier) Open reveal; feel for cold, missing insulation
Milky or misted glass that will not wipe off Any Sealed-unit failure Visual; cannot be reached from either side
Water at top corners or top rail inside During or after rain Head flashing, missing underlay collar or drainage gutter Hose test on head only; inspect from loft
Water running down one side of frame During rain, worse with wind from that side Side flashing, blocked side gutter, wrong kit, tight tile cut Hose test one side; lift tiles and inspect
Water at bottom rail or sill inside Wind-driven rain Sash gasket, latch misalignment, ventilation flap open Paper test; close flap; hose test bottom only
Drips from frame some hours after rain stops After rain Water held in side gutters or on underlay, slow release Inspect gutters for moss; check collar
Water in loft above window, flashings dry Long rain Underlay collar or drainage gutter missing Inspect from loft during rain
Leak only in snow or after snow melts Thaw Snow bridging side gutters; meltwater backing up over aprons History; check gutter depth and tile gap

Detailed Guidance

Decision tree

ROOF WINDOW "LEAKING"
=====================
1. Does the water appear only with rain?
   NO  -> condensation or cold bridge. Go to 2.
   YES -> go to 3.
   Misted BETWEEN panes -> sealed unit. Replace glazing cassette.

2. CONDENSATION PATH
   - Wet glass inside, dripping -> room humidity. Check extract fan
     (15 l/s bathroom), trickle vents, heating pattern. Advise.
   - Dry glass but wet plasterboard at reveal corners -> cold bridge.
     Open reveal. No insulation collar / no vapour barrier -> fit
     insulation around frame + vapour-control membrane, re-line.
   - Bathroom window with no extract -> fan to Approved Document F
     before anything else.

3. RAIN LEAK - WHERE does it show inside?
   TOP rail or top corners -> go to 4
   ONE SIDE -> go to 5
   BOTTOM rail / sill -> go to 6

4. HEAD
   - Lift tiles above window. Drainage gutter present? Underlay
     collar lapped under underlay above and over at sides?
   - Head flashing tucked under tiles by the specified overlap?
     Tiles cut short / sitting on apron -> re-cut or re-dress.
   - Mortar or sealant "repair" on the apron -> remove; find cause.

5. SIDE
   - Side gutters full of moss/debris -> clear; advise annual clean.
   - Tiles cut too tight (apron lifted) or too wide (flashing
     exposed) -> re-cut to kit instructions.
   - Kit type matches covering? Profiled kit on flat covering or
     vice versa -> replace flashing kit.
   - Slates: soakers or side flashings nailed through -> replace.

6. BOTTOM
   - Ventilation flap open? Close; explain to customer.
   - Paper test around sash: slips free at one point -> adjust
     keepers / hinges; replace gasket if hard or cracked.
   - Sill apron dressed onto tiles, not kinked upward -> re-dress.
   - External glazing gasket perished -> replace gasket, or glazing
     cassette if gasket is integral.
   - Pitch below 15° without low-pitch kit -> no reliable repair;
     replace with low-pitch kit or raise the window on a kerb.

Hose testing in the right order

Hose testing finds the entry point in one visit if it is done bottom-up and one zone at a time. Start with the sash closed and the ventilation flap shut. Run a gentle hose (not a jet) on the sill apron and bottom of the sash for ten minutes with someone inside watching. If dry, move to one side flashing, then the other, then the head flashing and the tiles above. Allow ten minutes per zone, because water takes time to track. Testing the head first soaks everything and tells you nothing. Record which zone produced water inside; that is the repair.

Condensation and the cold-bridged reveal

A roof window in a bathroom or bedroom is the coldest surface in the room. On a 2°C morning with the room at 60 % relative humidity, the inner pane of an old double-glazed unit falls below the dew point and runs. The fix is ventilation and heat, not roofing: an extract fan to Approved Document F Volume 1 running on a humidistat or overrun, trickle ventilation, and a constant low background heat rather than short blasts. See condensation on windows.

The more damaging variant is the uninsulated reveal. Many windows fitted in the 1990s and 2000s went in without an insulation collar or a vapour barrier. The timber frame and the gap between it and the rafters run cold, warm moist air gets into the roof void around the frame, and condensation forms on the plasterboard at the bottom corners of the reveal and inside the lining. It stains, blisters paint and grows mould, and it looks exactly like a leak. Opening the reveal shows dry roofing and a cold, often damp, gap around the frame. The repair is to pack the gap with insulation (mineral wool or the manufacturer's collar), fit a vapour-control membrane lapped onto the frame and the ceiling membrane, and re-line. BS 5250:2021 covers the principle of keeping the warm, moist side sealed.

Head flashings and the underlay detail

Water running down the roof underlay above the window has to be diverted around it. The flashing kit's drainage gutter sits on the battens above the window and does this; the underlay collar seals the frame to the underlay so water cannot run behind the frame. Both are routinely left out by installers in a hurry, and the window works for years until the underlay ages or a tile slips above and more water starts running on the underlay. The symptom is water appearing at the top corners inside, or dripping in the loft above the window, while the visible flashings are bone dry. Lifting three or four tiles above the window shows whether the gutter and collar are present. Fitting them retrospectively is a half-day job with the tiles above removed.

The head apron must also be tucked under the tiles by the kit's stated overlap and the tiles must not be cut so short that they sit on the apron and lift it. Mortar fillets or mastic along the head apron are a sign someone has already guessed.

Side flashings, gutters and the wrong kit

The side pieces of a flashing kit form a gutter between the frame and the cut tiles. Moss, leaves and grit collect here, water backs up above the lip and finds the frame. Clearing the gutters is the cheapest repair there is and should be an annual item for a window under trees. Tiles cut too tight lift the apron lip and let wind-driven rain over it; cut too wide they expose the flashing to splash and look wrong. The kit instructions give the gap for each range.

A kit for the wrong covering is a replacement, not a repair. Profiled-tile kits have a deep foam or lead-replacement sill apron and wide side pieces to dress into the tile profile; slate kits are flat and rely on soakers. Each leaks on the other covering. On slate roofs check also that the side flashings or soakers have not been nailed through by a well-meaning repair.

Sash, gasket and ventilation flap

Water at the bottom rail inside, worse when the wind is on that elevation, is the sash. Close the sash on a strip of paper at several points around the perimeter: it should grip everywhere. A point where it slips means the sash is not pulling home, usually because the keepers have moved, the hinges are worn, or the gasket has hardened. Adjust keepers first, then replace the gasket. Check the external glazing gasket for cracks; on older windows it is a separate rubber that can be replaced, on newer ones it is part of the glazing cassette.

The ventilation flap is designed to pass air through a filter with the sash locked. At low pitches and in horizontal rain it can pass water. If the customer's leak happens only in storms with the flap open, the cure is a closed flap and a conversation, not a roofer.

Repair or replace?

Frequently Asked Questions

Is the water on my roof window a leak or condensation?

If it happens on cold mornings regardless of rain and the glass itself is wet inside, it is condensation. If it appears during or just after rain and the glass is dry inside but water is running down the frame or the reveal, it is a leak. Misting between the panes is a failed sealed unit, which is neither.

Can I just seal around the flashing with mastic or lead sealant?

No. Flashing kits are designed to shed water by overlap, not by adhesion, and sealant across a lap traps water behind it. Mastic on a head apron almost always marks a leak that was never diagnosed. Find the entry point with a hose test and correct the detail.

Does a leaking roof window mean the whole thing has to come out?

Rarely. Most leaks are a blocked side gutter, a tile cut wrongly, a missing drainage gutter or collar, a worn gasket or a latch that needs adjusting. The window itself comes out when the frame is rotten, the pitch is below the kit's minimum, or it is old enough that glazing and flashings are failing together.

Why does it only leak when it snows?

Snow sits in the side gutters and against the aprons, then melts from below as the house warms the roof. Meltwater backs up above the lip of the side gutter or the head apron and finds the frame. A deeper gutter profile, correct tile gaps and an insulated reveal (so the roof around the window stays cold and snow melts evenly) reduce it.

Do I need Building Control to replace a roof window?

Yes in England and Wales, because a replacement roof window is a controlled fitting under Approved Document L Volume 1 and must achieve 1.4 W/m²K or better. A competent person scheme member can self-certify; otherwise a building notice is needed. In a loft conversion the window may also be the escape route and must keep its minimum opening size under Approved Document B Volume 1.

Regulations & Standards