Summary

"The heating's not coming on" lands on the programmer more often than it deserves. The programmer is only a time switch: it connects a live to the heating circuit (terminal 4) and the hot water circuit (terminal 3) at the times it has been told to. Whether the boiler then fires depends on the room thermostat, the cylinder thermostat, the zone valves and the boiler itself, each of which can stop the heating with the programmer working perfectly. The engineer's job on this call is to find out, in five minutes with a meter, which side of the programmer the fault is on.

The commonest "fault" is not a fault at all. A power cut, a tripped lighting circuit the spur is wired from, or a flat backup battery resets the clock; the customer's 6 am programme now runs at 2 pm; the programmer is on "holiday" because a grandchild pressed it; the clock did not change in March or October; the heating is set to "timed" when the customer thinks "once" means once a day and it means one block. A third of programmer call-outs end with the clock reset and a two-minute lesson. This guide gives the order of tests, the wiring at the standard backplate, the failure modes of the common types, the rules on replacement — Part P, Boiler Plus, and when a combi's integral clock is a Gas Safe job — and what to charge.

For the controls these programmers drive, see heating controls, zone valves and wiring and smart thermostats; for the companion fault, see thermostat not working.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Symptom Most likely cause Test Fix
Blank display No supply at backplate, spur fuse blown, dead unit 230 V L–N at backplate? Replace 3 A fuse, remake terminal, or replace programmer
Display OK, heating comes on at wrong times Clock reset after power cut, DST not changed, wrong day Check clock, day and programme Reset; set auto-DST if available
Display shows ON, boiler does not fire Relay failed; L link missing; downstream fault 230 V on terminal 4 with ON? No volts: replace programmer. Volts: go downstream
HW works, CH does not CH relay failed, or room stat / CH valve fault 230 V on terminal 4? Replace programmer or trace CH circuit
CH works, HW does not HW relay failed, or cylinder stat / HW valve fault 230 V on terminal 3? Replace programmer or trace HW circuit
Heating never switches off Relay contacts welded; boost latched; stat bypassed Programme OFF, still 230 V on 4? Replace programmer
Programme lost after every power cut Backup cell flat or model has none Check battery type Replace cell or unit
Buttons do nothing / display frozen Firmware lock-up, failed keypad Power cycle at spur Replace if it recurs
New programmer fitted, nothing works Backplate wiring differs (old unit was volt-free or gravity-wired) Compare terminal functions Rewire to the new unit's diagram
Combi integral clock blank Clock module or PCB supply Gas Safe engineer checks PCB fuse and clock Replace clock module

Detailed Guidance

Safety first — isolation

The programmer, the wiring centre, the zone valves and the boiler are all live at 230 V and usually fed from one fused spur. Before pulling the programmer off its backplate:

  1. Find the fused connection unit (often next to the boiler or the airing cupboard) and switch it off; remove the fuse and keep it.
  2. Verify dead at the backplate with an approved voltage indicator, proving the indicator before and after.
  3. Lock off or keep the fuse in your pocket. Other people in the house will switch things back on.

For an integral clock inside a combi, the casing comes off: that is the appliance, and the engineer doing it should be Gas Safe registered for domestic boilers.

Decision tree

Programmer "not working" — start here
│
├── Is the display blank?
│   ├── Yes
│   │     ├── 230 V L–N at the backplate?
│   │     │     ├── No  → spur fuse blown? loose L or N? → fix supply, re-test
│   │     │     │         (a blown 3 A fuse that blows again = fault elsewhere
│   │     │     │          on the circuit: pump, valve motor, boiler)
│   │     │     └── Yes → programmer dead → replace
│   │     └── Battery-only type (rare) → replace batteries
│   └── No → continue
│
├── Is the clock, day and programme correct?
│   ├── No  → reset; ask about recent power cuts; set DST auto; show the
│   │         customer ONCE / TIMED / ALL DAY / OFF and the boost button
│   └── Yes → continue
│
├── Set the channel to ON (constant). Does the boiler fire within a minute?
│   ├── Yes → the programmer is fine; the programme was the problem, or
│   │         the thermostat was satisfied → explain, reset, done
│   └── No → continue
│
├── With the channel ON, is there 230 V between terminal 4 (CH) or 3 (HW)
│   and N at the backplate?
│   ├── No  → programmer output relay failed (or L link missing on a
│   │         volt-free unit) → check link; replace programmer
│   └── Yes → programmer is proving its output; fault is downstream
│         ├── Room thermostat: turn up to maximum; 230 V out of the stat?
│         │     ├── No  → thermostat fault (see thermostat article)
│         │     └── Yes → continue
│         ├── Zone valve / mid-position valve: does it drive open? end
│         │   switch making (230 V on the orange/grey)?
│         │     ├── No  → valve motor or microswitch → replace head
│         │     └── Yes → continue
│         └── Switch-live reaching the boiler terminals?
│               ├── No  → wiring centre fault, broken link, loose terminal
│               └── Yes → boiler fault (fan, pressure, PCB, lockout)
│
└── Heating will NOT go off with the programme OFF?
      ├── 230 V still on terminal 4 with OFF → relay welded → replace
      ├── Boost/advance latched → cancel, explain
      └── Volts gone from 4 but boiler still runs → valve stuck open, or
            a bypass/link in the wiring centre → trace

The standard backplate and what each terminal does

Terminal Function Where it goes
L Permanent live in From the 3 A fused spur, via the wiring centre
N Neutral Wiring centre neutral block
E Earth Wiring centre earth block
1 HW off (switched live when HW is OFF) Used on Y-plan and gravity systems; often unused on S-plan
3 HW on To the cylinder thermostat
4 CH on To the room thermostat

Most twin-channel programmers from the main UK manufacturers use these six positions, which is why a swap is usually a matter of pulling one off and pushing the other on. The traps:

Why the clock keeps losing time

A programmer that loses its programme every time the power blips has a flat backup. On older units it is a rechargeable cell or a supercapacitor that only holds for hours once it has aged; some budget units have no backup at all. If the customer has frequent short outages — rural overhead supply, a sticky RCD — a programmer with a lithium coin-cell backup (typically several years) or a smart control that stores the programme in the cloud ends the call-backs. Daylight-saving errors come from units with no automatic DST; newer ones adjust themselves, older ones need the customer told in March and October.

Relay failure — the genuine programmer fault

Inside the programmer, each channel is a small relay carrying the heating demand current — a zone-valve motor, a thermostat, sometimes a pump. After ten to twenty years the contacts pit or weld. Pitted contacts give an intermittent output: the display says ON, the heating works some days. Welded contacts give a channel that never turns off: the programme says OFF and terminal 4 still reads 230 V. Either way the unit is replaced; the relay is not a serviceable part. A relay that has welded because it was switching a load it should not — a circulating pump directly, or a motorised valve with a jammed motor drawing stall current — will weld the replacement too, so check what the output is feeding.

Replacement: Part P, Boiler Plus and Part L

Replacing a programmer with another on the same backplate and the same circuit is replacement of an accessory — not notifiable under Part P, no certificate required beyond a minor works certificate if you choose to issue one. A new fused spur from the consumer unit, or a new circuit for a relocated programmer, is notifiable (self-certify through a competent person scheme or notify Building Control).

Boiler Plus applies in England when a combi boiler is replaced: time and temperature control plus one of weather compensation, load compensation, flue gas heat recovery or smart control with automation and optimisation. Swapping a failed programmer on its own does not trigger it, but if the existing control was a smart thermostat providing load compensation under Boiler Plus, replacing it with a mechanical time switch takes the installation backwards; put back something at least as good. Under Approved Document L (2021 edition, England) every boiler installation must have a time control and a room thermostat with interlock, and stored hot water must have a cylinder thermostat and time control — the minimum any replacement programmer must still achieve. Scotland and Wales have their own building standards with similar control requirements.

Upgrading rather than replacing

If the programmer has failed and the customer has a 15-year-old mechanical room stat as well, the better job is one combined smart programmable thermostat: time and temperature in one unit, often wireless to a receiver on the old backplate, with load compensation that a modern boiler can use. Parts £130–£250, 1–2 hours including the app, versus £40–£120 and 45 minutes for a straight swap. On an S-plan with stored hot water, a smart control that handles both channels is needed, or a twin-channel programmer stays and only the room stat is replaced. See heating controls upgrade and smart thermostat installation pricing guide.

Charging the job

Job Time Parts Typical charge
Diagnose, reset clock and programme, show the customer 20–30 min — Call-out or minimum charge £60–£110
Replace programmer, same backplate 30–60 min £40–£120 £120–£220
Replace programmer, re-terminate backplate 1–2 h £40–£120 £160–£300
Replace with smart programmable thermostat (combi) 1–2 h £130–£250 £250–£450
Integral combi clock (Gas Safe engineer) 45–90 min £40–£150 £150–£300

Make the diagnostic charge clear before you start, because a third of these calls end with nothing replaced; a customer told "£75 to look at it, deducted from any repair" does not argue when the fault was the clock. See plumber hourly rate guide and electrician hourly rate guide for the rates behind the table.

Frequently Asked Questions

The programmer display is on but the heating won't come on — is the programmer broken?

Not necessarily. Set the heating channel to constant ON and measure between terminal 4 and neutral at the backplate: 230 V means the programmer is doing its job and the fault is in the room thermostat, the zone valve, the wiring centre or the boiler. No voltage with ON showing means the output relay has failed and the unit needs replacing.

Can I replace a boiler programmer myself?

Like-for-like replacement on the existing backplate is not notifiable under Part P, but it is live 230 V work in a circuit shared with the boiler and valves, and most programmers are fitted by heating engineers or electricians for that reason. A clock inside a combi boiler's casing should be left to a Gas Safe registered engineer.

Why does the heating come on at the wrong time after a power cut?

The programmer lost the clock during the outage and restarted from a default time and day; the programme may be intact but is running on the wrong clock. Reset the time and day. If it happens on every short outage the backup cell is flat — replace it, or fit a unit with a longer backup.

Do I need a Boiler Plus compliant control when I replace a programmer?

Boiler Plus applies to combi boiler replacements in England, not to a programmer replaced on its own. But the system must still meet the Part L minimum of a time control plus a room thermostat with interlock, and you should not replace a smart control that was providing Boiler Plus compliance with something less capable.

Does a programmer need its own fused spur?

No — it is normally fed from the same 3 A fused connection unit as the boiler and wiring centre, so one isolation point kills the whole control circuit. If a programmer is on a separate supply, label both isolators; two live feeds into one wiring centre is a shock risk for the next engineer.

Regulations & Standards