Summary
"The hot tap just gurgles" is one of the oldest plumbing calls there is, and the honest answer is that most of them are not airlocks at all. On a gravity hot water system the water in the hot pipes is pushed only by the head of water in the cold-water storage cistern in the loft — about 0.1 bar for every metre of height between the cistern water level and the tap. That is not much. A pocket of air at a high point in a 22 mm or 15 mm hot draw-off can be enough to stop it, because the head cannot compress the air pocket out of the way. The same system is fed from a cistern that can run dry when the float valve sticks, and a dry cistern produces exactly the same symptom; the difference is that one is cured in five minutes with a hose and the other comes back the moment the cistern fills and empties again.
This guide gives the tests that separate a genuine airlock from the three mimics, the four ways to purge an airlock in order of preference (and why the old hose-between-the-taps trick is a Water Regulations problem if it is left connected), the places air gets in, and the permanent fixes that stop the call-back. It also covers the cases that are not airlocks but get the name anyway: air in the primary circuit (the boiler side) that stops the cylinder heating, and the spluttering combi that has a different cause entirely.
For how gravity, system and combi hot water differ, see combi vs system vs conventional; for cylinder types and the open-vented arrangement, see hot water cylinder types guide.
Key Facts
- Where airlocks happen — only on open-vented (gravity) hot water: cold-water storage cistern in the loft, 22 mm cold feed to the base of the cylinder, 22 mm open vent from the top of the cylinder rising over the cistern, hot draw-off teed from the vent to the taps. Head pressure: roughly 0.1 bar per metre from cistern water level to the outlet
- Not where airlocks happen — combi boilers and unvented cylinders run at mains pressure (typically 1–3 bar after the pressure-reducing valve); air is pushed through to the tap. A spluttering combi tap is usually a scaled plate heat exchanger, a failed flow sensor or mains supply trouble, not an airlock
- Symptom pattern — hot tap gurgles, spits, runs then stops, or gives nothing; cold tap at the same basin runs normally; cylinder is hot to the touch at the top. If the cylinder is cold, the fault is heating, not air
- The three mimics — (1) cistern empty or nearly empty (float valve jammed, cistern drained for other work, supply isolated); (2) cold feed from cistern to cylinder blocked by scale, debris or a collapsed flexible; (3) hot draw-off restricted by a part-closed gate valve or a failed tap cartridge
- Cistern check — lift the lid: water should be 25 mm or so below the overflow level, with the float valve shutting cleanly. Air gets in when the level drops below the cold feed outlet at the cistern base; the feed then draws air into the cylinder and the hot pipes
- How air gets in — cistern runs dry (stuck float valve, supply off, heavy draw-off faster than the float valve can refill), system drained and refilled (cylinder change, immersion change, tap change), negative pressure at the vent when a bath is drawn on a low-head system, a draw-off pipe that rises then falls (a loop over a doorway, a pipe run up into the loft and back down)
- Purge method 1 (preferred): refill from the cistern with the taps closed — isolate the hot draw-off nearest the cylinder if there is a gate valve, open the highest hot tap, then open the valve slowly: the head pushes the pocket to the open tap. Works for small pockets near the top of the run
- Purge method 2: back-feed from a mains tap — connect a hose from the kitchen cold tap (mains) to the airlocked hot tap, open the hot then the cold: mains pressure drives the air back down into the cylinder and out of the open vent. Disconnect the hose as soon as flow is restored. This is the standard trade method, but a permanent or forgotten connection is a backflow contravention under the Water Supply (Water Fittings) Regulations 1999 (fluid category 2 or 3 cross-connection between mains and stored water)
- Purge method 3: monobloc mixer trick — on a basin or kitchen mixer with a single spout, block the spout with the palm and open hot and cold together: the cold (mains) side back-feeds the hot. Only works on mixers where the hot and cold mix in the body, not on separate-channel "dual-flow" mixers
- Purge method 4: drain and refill — close the cistern supply, drain the hot draw-off from the lowest hot tap or a drain-off, then refill with all hot taps open starting from the highest: air leaves as the water rises. Used when the airlock keeps reforming because the pipe geometry holds air
- Air in the primary (boiler) circuit — a different fault with a different symptom: the cylinder does not heat (coil airlocked, pump airlocked, or the feed-and-expansion cistern in the loft has run dry). Bleed the pump and any air vent on the primary flow; check the F&E cistern level. See no hot water but heating works
- Permanent fixes — replace the float valve (BS 1212 Part 2 or 3 diaphragm type, not a worn Part 1 Portsmouth), remove the rising loop in the draw-off or fit an automatic air vent at its high point, increase cistern capacity or raise it, replace a scaled 22 mm cold feed, fit a 22 mm not 15 mm cold feed, or convert to an unvented cylinder (G3-registered installer) or a combi
- Cistern standards — cold-water storage cistern to BS 7181 or BS 4213 with a close-fitting lid, insect screen on the overflow and warning pipe, insulation; the Water Regulations require the stored water to be protected from contamination (Schedule 2, paragraph 16). Many "airlock" houses have an open, uninsulated cistern with a dead pigeon in it
- Legionella — stagnant stored water between 20 °C and 45 °C is a growth risk; a cistern that keeps emptying and refilling is not the problem, but a cistern with excess capacity that turns over slowly is. HSE HSG274 Part 2 guidance applies to landlords and to any premises where there is a duty under the Health and Safety at Work etc. Act 1974
- Charging — diagnosis and purge: 30–60 minutes, £60–£120; float valve replacement adds £15–£40 in parts and 30 minutes; re-piping a looped draw-off £150–£350; new cistern £250–£500 fitted. See plumber hourly rate guide
Quick Reference Table
Diagnosed the problem? Create a repair quote in minutes with squote.
Try squote free →| Symptom | Cylinder hot? | Cistern level | Most likely cause | Fix |
|---|---|---|---|---|
| Hot tap gurgles, spits, then stops | Yes | Normal | Airlock in hot draw-off | Purge (methods 1–3) |
| Hot tap gives nothing, cold fine | Yes | Empty or low | Float valve stuck; supply isolated | Free or replace float valve, refill, then purge if still airlocked |
| Hot tap dribbles at all outlets | Yes | Normal | Blocked or scaled cold feed to cylinder; part-closed gate valve | Check gate valve; replace cold feed |
| Hot tap dribbles at one outlet only | Yes | Normal | Tap cartridge, flexible tail kinked, isolation valve part closed | Local fix at the tap |
| Hot tap runs cold | No | Normal | Cylinder not heating: boiler, zone valve, cylinder stat, immersion, primary airlock | Heating fault, not a draw-off airlock |
| Hot water fine upstairs, poor downstairs after a bath | Yes | Drops then recovers | Cistern too small or float valve too slow; air drawn at vent | Larger cistern or faster float valve; check vent |
| Airlock returns every few weeks | Yes | Normal | Rising loop in draw-off; cistern running low under heavy draw-off | Re-route pipe or fit automatic air vent at the high point |
| Airlock after any plumbing work | Yes | Normal | System refilled with taps closed | Refill with highest hot tap open |
| Spluttering at a combi or unvented system | n/a | n/a | Not an airlock: mains supply, scaled heat exchanger, flow sensor, PRV | Mains-pressure diagnosis |
Detailed Guidance
First five minutes: is it actually an airlock?
Before touching a hose, settle three questions.
- Is the cylinder hot? Hand on the top third of the cylinder. Cold cylinder means the fault is heating — boiler, motorised valve, cylinder thermostat, immersion, or air in the primary circuit — and no amount of purging the draw-off will help.
- Is there water in the cistern? Up the loft ladder. The level should be within 25 mm of the float valve's shut-off point and the valve should be closed and silent. Low or empty means a float valve fault or an isolated supply; an airlock is then a symptom, and the valve is the job.
- Does cold water run normally at the same outlet? If both hot and cold are poor at a basin, the fault is the tap, the flexible tails or a local isolation valve, not the hot system.
Only when the cylinder is hot, the cistern is full and the cold runs is it a draw-off airlock or a restricted cold feed. The two are told apart by where the symptom appears: an airlock gives spitting and gurgling and often clears at one tap and not another; a blocked cold feed gives a steady weak dribble at every hot tap, getting worse as the cylinder is drawn down, with no air noise.
Decision tree
"No hot water at the tap" on a cistern-fed system
│
├── Is the cylinder hot at the top?
│ ├── No → heating fault (boiler / valve / stat / immersion / primary air)
│ │ → see no-hot-water-but-heating-works; check F&E cistern level
│ └── Yes → continue
│
├── Is the cold-water storage cistern full, float valve shut?
│ ├── No → float valve stuck / supply off / valve too slow
│ │ → free or replace float valve; refill; THEN test taps again
│ │ (the airlock may have cleared itself as the cistern filled)
│ └── Yes → continue
│
├── Does the cold run normally at the same outlet?
│ ├── No → tap, tails, local isolation valve → local repair
│ └── Yes → continue
│
├── Hot gurgles / spits / runs then stops?
│ ├── Yes → AIRLOCK in hot draw-off
│ │ → purge: method 1 (highest tap open, let head push)
│ │ → method 2 (mains back-feed via hose, then DISCONNECT)
│ │ → method 3 (mixer palm trick)
│ │ → method 4 (drain and refill, highest tap open)
│ │ → then find the cause (below)
│ └── No, steady weak dribble, no air → RESTRICTED COLD FEED
│ → gate valve on cold feed fully open?
│ → cold feed scaled / debris / collapsed flexible → replace
│
└── Airlock clears but returns?
├── Rising loop in draw-off → re-route or AAV at the high point
├── Cistern empties under heavy draw → larger cistern / faster valve
├── Vent pipe too short or draw-off teed above the vent → correct
└── Cold feed too small (15 mm) → upgrade to 22 mm
Purging the air
Method 1 — let the head do it. Open the highest hot tap in the house fully (usually a bathroom basin or bath). If there is a gate valve on the hot draw-off near the cylinder, close it, wait ten seconds, then open it slowly: the surge of head behind the pocket often shifts it. Leave the tap running until it runs clean. Then open every other hot tap in turn from top to bottom. This works for the common case — air drawn in while a bath was running — and costs nothing.
Method 2 — back-feed from the mains. The trade standby. Take a short hose with a tap connector at each end, connect the kitchen cold tap (mains fed) to the airlocked hot tap, open the hot tap first, then the cold. Mains pressure pushes water backwards up the hot draw-off, through the cylinder and out of the open vent into the cistern, carrying the air with it. Thirty seconds is usually enough; you will hear the vent discharge in the loft if you listen. Close the cold, then the hot, then remove the hose and run the hot tap normally. Two warnings. Never leave the hose connected: a mains-to-stored-water connection is a backflow risk the Water Supply (Water Fittings) Regulations 1999 prohibit without a suitable backflow device, and a permanently connected hose is exactly what a Water Regulations inspector writes up. And on a cylinder that is scaled or old, check the vent is not blocked before you pressurise — a blocked vent and a closed cistern lid turn method 2 into a pressure test of a cylinder designed for 0.3 bar.
Method 3 — the mixer tap. On a kitchen or basin monobloc mixer where hot and cold mix in the body (most budget and mid-range mixers do; high-end "dual-flow" mixers with separate waterways do not), block the spout firmly with your palm or a rag and open both hot and cold. The mains cold back-feeds the hot. Release after twenty seconds and let the hot run. It is method 2 without the hose and works often enough to try first.
Method 4 — drain and refill. For the airlock that reforms every time, or where the pipe run holds air that the head cannot clear. Close the cistern supply (or tie the float valve up), open every hot tap, drain the draw-off from the lowest point — a drain-off cock if there is one, otherwise the lowest hot tap — and when it stops, close the drain and refill with the highest tap open. Air leaves ahead of the rising water. If the airlock returns after a correct refill, the pipework has a trap: find it.
Where the air comes from — and the permanent fix
The cistern ran dry. The float valve stuck (a worn washer or a scaled piston on a Portsmouth valve), the supply was turned off, or a bath and a washing machine together emptied a small cistern faster than a 15 mm valve could refill it. As the level drops below the cold feed outlet at the cistern base, air is drawn into the feed and into the cylinder. Fix the valve — fit a diaphragm type to BS 1212-2 or BS 1212-3 with a decent float — and check the cistern size: 100–115 litres actual capacity is the usual minimum for a house with one bathroom, 230 litres where there are two. Make sure the warning (overflow) pipe is clear and visible.
The system was drained and refilled. After a cylinder swap, an immersion change or a tap replacement, refilling with the hot taps closed leaves air at every high point. Refill with the highest tap open, always.
The pipework has a trap. A hot draw-off that rises from the vent connection, runs across a ceiling, drops to a bathroom, then rises again to a loft shower, holds air at the second high point that no head will clear. The fix is to re-route so the pipe falls continuously from the vent connection to each outlet, or to fit an automatic air vent (with an isolation valve for service) at the high point. On a long run, a 22 mm main with 15 mm branches falling to each tap is the arrangement BS EN 806-2 and BS 8558 intend.
The draw-off is teed above the vent. The hot draw-off should come off the vent pipe no higher than 450 mm above the cylinder top (the manufacturer's connection point), so that the vent carries expansion and any air and the draw-off takes water. A draw-off teed higher up, near the loop over the cistern, pulls air every time a tap opens. Re-make the tee.
Low head and a shower. A gravity shower on a system with less than a metre of head between cistern base and shower head will draw air at the vent when the bath is run. A shower pump needs a dedicated cold feed from the cistern and a hot draw-off from a surrey or essex flange or a dedicated connection, so it never competes with the vent — see shower pump installation.
What this is not: air on the boiler side
The other "airlock" is in the primary circuit — the sealed or open-vented circuit from the boiler through the cylinder coil. Symptoms: cylinder cold or lukewarm, boiler cycling or kettling, pump running but noisy, heating may still work. On an open-vented primary, check the feed-and-expansion cistern in the loft has water in it and its float valve works; a dry F&E cistern is the commonest cause of a cold cylinder on an old system. Bleed the pump (bleed screw on the pump body), any air vent on the primary flow, and the top of the coil if there is a bleed point. On a sealed system, check the pressure gauge (1–1.5 bar cold) and top up before bleeding. See no hot water but heating works and boiler kettling.
The customer who wants it to stop happening
An airlock that keeps returning is a design fault, and the honest advice is one of three things: fix the cistern (valve, size, feed), fix the pipe geometry, or get rid of the cistern. An unvented cylinder (G3-registered installer, mains pressure, no loft cistern) or a combi removes the cause completely, and on a house with a decent mains supply it is often the better value over ten years than three more purge visits. The quote for that is a different article: cylinder replacement and unvented cylinders.
Charging the job
| Job | Time | Parts | Typical charge |
|---|---|---|---|
| Diagnose and purge airlock | 30–60 min | — | £60–£120 |
| Replace float valve, refill, purge | 45–75 min | £15–£40 | £90–£160 |
| Replace scaled 22 mm cold feed, cistern to cylinder | 2–3 h | £30–£80 | £180–£320 |
| Re-route looped draw-off or fit AAV at high point | 1.5–3 h | £20–£60 | £150–£350 |
| New cold-water storage cistern, 230 l, with valves and insulation | Half a day | £120–£250 | £350–£550 |
Agree the diagnostic charge first: a third of these calls end with a float valve and a lecture about the overflow pipe, and the customer who was told "£80 to find it, deducted from the repair" does not argue.
Frequently Asked Questions
How do I get an airlock out of a hot water system?
Open the highest hot tap and, if the system has a gate valve on the hot draw-off, close and reopen it to surge the pipe. If that fails, back-feed mains pressure into the hot tap with a hose from the mains cold tap (or by blocking the spout of a mixer tap with both sides open) for twenty to thirty seconds, then disconnect the hose. If the air returns, drain the hot draw-off and refill with the highest tap open, and look for a rising loop in the pipework.
Why do I keep getting an airlock in my hot water?
Because something keeps letting air in: a cold-water storage cistern that runs low when the bath is run (float valve slow or stuck, cistern too small), a hot draw-off that rises and falls so it holds air at a high point, or a draw-off teed too high on the vent pipe. Purging clears the symptom; the cause is in the loft or the pipe route.
Can a combi boiler get an airlock?
Not in the hot water draw-off: a combi delivers hot water at mains pressure, which pushes any air through to the tap. Spluttering from a combi tap usually means a problem with the incoming mains, a scaled plate heat exchanger or a flow-sensor fault. The combi's heating circuit can hold air, which is a different fault — radiators cold at the top, pump noise, pressure dropping.
Is connecting a hose between the hot and cold taps legal?
As a brief purge, with the hose removed afterwards, it is accepted practice. Leaving it connected is a cross-connection between the mains and stored water, which the Water Supply (Water Fittings) Regulations 1999 prohibit without an appropriate backflow prevention device; it also back-pressurises a vented cylinder that is not designed for mains pressure. Disconnect it as soon as the tap runs clean.
No hot water but the cistern is full and the cylinder is hot — what else is it?
A restricted cold feed between the cistern and the base of the cylinder: a gate valve left part closed, a scaled or sludged 22 mm pipe, or a flexible connector that has collapsed internally. The symptom is a weak, steady dribble at every hot tap rather than spitting and gurgling. Check the gate valve first; replace the feed if it is scaled.
Regulations & Standards
Water Supply (Water Fittings) Regulations 1999 (SI 1999/1148) — backflow prevention (Schedule 2, paragraph 15), protection of stored water from contamination (paragraph 16); applies to the mains-to-hot hose purge and to cistern condition
Building Regulations 2010, Approved Document G (2015 edition incorporating 2016 amendments) — G3 hot water supply and systems; unvented cylinder installation by a competent person; bath outlet temperature in new dwellings
BS EN 806-1 to 806-5 — specifications for installations inside buildings conveying water for human consumption; design, pipe sizing, installation, commissioning
BS 8558:2015 — guide to the design, installation, testing and maintenance of services supplying water for domestic use within buildings (UK complement to BS EN 806); cistern capacity and arrangement
BS 1212-2:1990 and BS 1212-3:1990 — diaphragm-type float-operated valves (brass and plastic bodies) for cisterns
BS 4213:2004 and BS 7181:1989 — cold-water storage cisterns (polyethylene and other materials); lids, overflows and screening
BS 1566-1:2002+A1:2011 — copper indirect cylinders for domestic purposes (open-vented); connection positions and working head
HSE HSG274 Part 2 (2014) — Legionnaires' disease: the control of legionella bacteria in hot and cold water systems; cistern turnover and temperature
HSE Approved Code of Practice L8 (2013) — legionella control duties under the Health and Safety at Work etc. Act 1974
Water Supply (Water Fittings) Regulations 1999 — legislation.gov.uk — backflow and stored water requirements
WRAS — Water Regulations guidance for installers — backflow prevention and fluid categories
Approved Document G: Sanitation, hot water safety and water efficiency — gov.uk
HSE HSG274 Part 2 — Legionella in hot and cold water systems — stored water guidance
BS 8558:2015 — BSI Knowledge — domestic water services design and installation
CIPHE — Chartered Institute of Plumbing and Heating Engineering — technical guidance for plumbers
no hot water but heating works — when the cylinder is cold, not the pipe
hot water cylinder types guide — open-vented versus unvented arrangements
combi vs system vs conventional — why only gravity systems airlock
water pressure flow rate — head, pressure and flow explained
shower pump installation — dedicated feeds that stop air being drawn at the vent
unvented cylinders — the permanent fix for a chronic airlock house
cylinder replacement — pricing the conversion
boiler kettling — air and scale on the primary side
plumber hourly rate guide — the rates behind the charges