Outdoor Electrical Installations: Armoured Cable, IP Ratings, RCD Protection and Part P

Quick Answer: Outdoor electrical work is notifiable under Approved Document P when it involves a new circuit, a consumer unit change, or any installation in a special location. Buried cables to garden buildings should be SWA (steel wire armoured) to BS 6724 at a depth of 600 mm minimum or sleeved in steel duct at lesser depths, with 30 mA RCD protection for any socket-outlet rated up to 32 A and an enclosure rating of IP44 minimum (IP65 for exposed positions). All work must be tested and certified to BS 7671:2018+A2:2022.

Summary

Outdoor circuits look superficially like indoor circuits with weatherproof boxes on the end, but they sit under a different set of pressure points: ingress, mechanical damage, earth-fault current paths over wet ground, and the prospect of an inexperienced user pushing a metal hedge trimmer through the supply cable. The Wiring Regulations treat outdoor installations as a hazard category because each of those failure modes individually has a poor history.

The dominant cable choice is SWA (steel wire armoured) — its armour gives both mechanical protection from spades and rodents and a metallic earth path that bonds the cable's earth conductor to a defined route. The choice of accessory enclosure depends on exposure: under cover, IP44 may suffice; in driving rain or pressure-washed environments, IP65 or better is required. RCD protection (30 mA for sockets, anywhere persons might come into contact with cables when working outdoors) is the final defence.

For homeowners, the question is normally either "can I run a power cable to the shed myself?" — and the legal answer is no, this is notifiable work under Part P — or "why does the garden socket trip every time it rains?" — almost always a sign that the IP rating of the accessory or the cable termination has been compromised.

Key Facts

Quick Reference Table

Quoting an electrical job? Describe the work and squote handles the pricing.

Try squote free →
Application Cable type Burial depth Accessory IP rating
Buried sub-main to detached outbuilding SWA 6 mm² – 16 mm² (sized to load + voltage drop) 600 mm IP65 enclosure at gland; CU inside outbuilding
Buried supply to garden lighting (mains) SWA 1.5 mm² or 2.5 mm² 600 mm IP65
Outdoor 13 A double socket on house wall T&E inside wall, IP rated FCU + socket n/a IP55 minimum, IP65 if exposed
Hot tub or swimming pool SWA + TT earthing typical 600 mm IP65; supplementary bonding mandatory
Garden lighting (12 V SELV) Cable rated for outdoor use, manufacturer-specified 75 mm typical IPX4 minimum on luminaire
EV charger T&E inside dwelling, dedicated circuit n/a IP54 minimum at charger
Pond pump Outdoor flex from RCD-protected outdoor socket n/a IP68 on pump body
Shed light + 2 sockets via existing house ring Spur not permitted; needs dedicated circuit n/a Inside shed: IP44 minimum

Detailed Guidance

Why SWA dominates outdoor work

Steel wire armoured cable does three jobs in one:

  1. The conductors carry current.
  2. The galvanised steel wires around the conductors provide mechanical protection — they will defeat a spade, a fork, and most rodent damage.
  3. The steel armour, when properly terminated with a CW-type gland and earth tag, forms a parallel earth path that extends the protective conductor to the cable's outer surface — hugely simplifying earth fault loop impedance compliance over long runs.

The alternative — multi-core flexible cable in conduit — is more vulnerable to damage, requires the conduit to be both sealed and earthed, and has a higher fitting time. SWA is universally specified for buried garden runs.

Sizing the cable

Two factors drive cable size for an outbuilding sub-main:

Common sizes:

Burial, sleeving and routing

Direct burial is straightforward: dig a trench, lay the cable on a 50 mm bed of sand or fine soil, cover with another 50 mm of fine material, then backfill with the excavated soil. Place yellow cable warning tape 150 mm above the cable. Mark the route on the as-built drawing — it saves the next person doing landscaping years later.

Where depth cannot be achieved (e.g. crossing under a paved patio you do not want to lift), use a steel duct (50 mm or 75 mm) bedded in concrete to provide mechanical protection. Keep duct bends gentle (radius ≥ 8× cable outer diameter).

For runs that pass into the building, bring the SWA up against the wall and into a junction box at the building entry; from there transfer to T&E or singles inside the building. The transition must keep the cable's earth continuity intact and the gland torqued correctly.

Accessories and enclosures

The IP rating you need depends on exposure:

Practical mistakes:

RCD protection — outdoor is more demanding than indoor

Two things drive the 30 mA RCD requirement outdoors:

For an outbuilding fed via a sub-main, design the protection as:

TT earthing for outbuildings

TN-C-S supplies (the typical PME urban supply) can extend their earth to outbuildings only where the safety case can be made. Where the earth would extend across a wet pool deck, a swimming pool zone, or where there is a risk of broken neutral on the supply, an alternative is to provide a local TT earth at the outbuilding via an earth electrode rod and serve the outbuilding as a TT system from an isolated sub-main.

Test the electrode resistance on commissioning — most domestic outbuilding TT systems target Ra ≤ 200 Ω, ideally below 100 Ω, with an MFT (multi-function tester) loop measurement.

Garden lighting — when 12 V is the better answer

Many garden lighting jobs are simpler and safer at 12 V SELV (Separated Extra-Low Voltage). A waterproof transformer fitted under the soffit feeds 12 V cable to LED spike lights, deck lights and pond lights. The incoming side is mains and notifiable; the 12 V side is SELV and not notifiable — provided the SELV is properly separated and the transformer is to BS EN 61558-2-6.

Practical advice:

Consumer-facing question — "can I install a garden socket myself?"

Single new outdoor socket addition (notifiable under Part P) — not legal DIY in England and Wales without LABC notification or a registered Competent Person Scheme electrician. In Scotland, Part P does not apply but the work is still required to be safe and tested. Replacing a like-for-like outdoor socket is permitted DIY but only where the installation is otherwise compliant.

Frequently Asked Questions

Can I run a 13 A flex through the wall to a garden socket?

No. A garden socket is a fixed installation requiring a dedicated circuit, RCD protection, and Part P notification. Running flex through a wall is non-compliant and a fire risk.

Does an outdoor socket need its own circuit?

Not necessarily — it can be a spur or extension of an existing ring or radial circuit, provided the upstream protection includes a 30 mA RCD and the cable type is suitable. In practice, a dedicated outdoor circuit is cleaner and avoids load problems.

What is the maximum length of SWA I can run from the consumer unit to the shed?

Limited by voltage drop, not by an absolute distance. With 4 mm² SWA at 16 A load, runs to 35 m are routine; 6 mm² extends that to 50 m+. For very long runs (60 m+), upgrade to 10 mm² or split the load.

Do I need a separate consumer unit in the outbuilding?

If there is more than one final circuit in the outbuilding (e.g. lighting and sockets), yes — fit a small CU. Single-circuit outbuildings can be served directly without a local CU.

What about a pond pump?

Pond pumps are normally fed from an outdoor RCD-protected socket in IP65 weatherproof housing. The pump itself must be IP68-rated and earthed via the supply cable. Avoid running the pump cable across a path; bury or duct.

Regulations & Standards