Summary

Domestic battery storage has grown rapidly alongside solar PV, driven by falling battery costs, time-of-use export/import tariffs, and backup-power demand. Lithium-ion chemistry (predominantly LiFePO4 — lithium iron phosphate — in current domestic products, valued for its comparatively lower thermal runaway risk versus other lithium chemistries) dominates the market, but any lithium battery carries a genuine fire risk if the cell is damaged, poorly manufactured, badly installed, or manages heat and charging incorrectly.

This risk profile prompted BSI to develop PAS 63100, published in 2024 (government-sponsored) specifically in response to growing installer numbers and a small but real number of domestic battery fire incidents, at a point where no dedicated UK installation fire-safety specification existed for this product category. PAS 63100 sits alongside — not instead of — the existing product-level safety standard BS EN 62619, which covers how the cells and battery packs themselves are designed, built and tested before they ever reach an installation site.

For an installer, the practical takeaway is: check the battery product itself is certified to BS EN 62619 (a manufacturer/product-level assurance), and follow PAS 63100 for how the system is sited, ventilated, protected and connected on site (an installer-level competency and practice standard) — treating either standard as sufficient on its own misses half the risk picture.

Key Facts

Quick Reference Table

Quoting an electrical job? Describe the work and squote handles the pricing.

Try squote free →
Standard Level Covers
BS EN 62619 Product/cell Design, construction, safety testing of lithium-ion cells and battery packs
PAS 63100 Installation/system Siting, fire risk mitigation, ventilation, installer competency for installed BESS
BS 7671 Electrical installation General wiring, isolation, protective device compliance for the connection
MCS (battery storage standard) Installer certification Installer competency scheme referencing PAS 63100 guidance

Detailed Guidance

Two different questions, two different standards

BATTERY STORAGE SAFETY — WHICH STANDARD ANSWERS WHICH QUESTION?
------------------------------------------------------------------
"Is this battery PRODUCT safe by design?"
   -> BS EN 62619 (cell/pack level testing and certification)

"Is this INSTALLATION sited and protected correctly?"
   -> PAS 63100 (siting, fire risk, ventilation, competency)

"Is the electrical CONNECTION compliant?"
   -> BS 7671 (Wiring Regulations)

A battery certified to BS EN 62619 installed badly (wrong location, poor ventilation, inadequate separation from escape routes) is not a safe installation overall — product certification and installation practice are separate, both necessary, assurances.

Siting decisions in practice

The core principle behind current siting guidance is limiting the consequences of a low-probability but high-severity event (thermal runaway), rather than assuming it can never happen. In practice this generally means:

Where this fits with wider solar/battery installation practice

Battery storage retrofits are frequently added to an existing solar PV installation, sometimes by a different installer to the original PV installer. PAS 63100 compliance and BS EN 62619 product certification should be checked independently at the point of the battery addition — an existing, compliant PV installation doesn't imply anything about the battery addition's compliance, since these are separate systems with separate standards.

Frequently Asked Questions

Is BS EN 62619 a UK-specific standard?

No — it's a European/international standard (EN-adopted) covering lithium-ion cell and battery safety more broadly, used across industrial and consumer battery applications, not written specifically for domestic UK solar-battery installations. PAS 63100, by contrast, is a UK-specific (BSI, government-sponsored) specification written specifically for fire protection in the installation of battery energy storage systems in UK dwellings.

Does PAS 63100 replace BS 7671 for the electrical connection?

No. PAS 63100 addresses siting, fire risk and installer competency specifically for the energy storage system; the general electrical installation (isolation, cabling, protective devices) still needs to comply with BS 7671 in the normal way. The two standards are complementary, not alternatives.

Why is siting given so much emphasis for battery storage compared with, say, a solar inverter?

Lithium-ion batteries carry a specific fire risk (thermal runaway) that most other domestic electrical equipment doesn't, including a small chance of a fire that's difficult to extinguish and can reignite. This is why siting guidance for batteries is more conservative than for equipment like inverters — the consequence profile of a rare failure is more severe, so the guidance prioritises keeping any such event away from escape routes and habitable spaces.

Do I need a specific certification to install battery storage systems?

There's no single mandatory licence in the way Gas Safe governs gas work, but MCS certification (for schemes requiring it, e.g. for certain grant eligibility) has its own installation standard for battery storage that references PAS 63100, and reputable manufacturers generally require installer training/accreditation before supplying products for warranty-backed installation. Always confirm the specific manufacturer's and any relevant scheme's installer requirements.

Regulations & Standards