How Do I Calculate Staircase Rise, Going, Headroom & Number of Treads?

Quick Answer: Under Approved Document K (England and Wales), a private stair must have a maximum rise of 220mm, minimum going of 220mm, and 2000mm minimum headroom. The total floor-to-floor height divided by the riser height gives the number of risers; the number of treads is always one less than the number of risers. The "comfort formula" 2R + G = between 550mm and 700mm should be satisfied.

Summary

Staircase geometry is tightly regulated because poorly designed stairs are one of the most common causes of serious domestic accidents. Getting the rise, going, and headroom right is not just about Building Regulations compliance — it directly affects how comfortable and safe the stair feels to use. Stairs that are too steep or have inconsistent riser heights are dangerous, and Building Control will require correction before sign-off.

The fundamental design task is to divide the total floor-to-floor height into a whole number of equal risers. This sounds simple, but the challenge is fitting the stair into the available plan area within the rise/going constraints, while maintaining adequate headroom. Loft conversion stairs face the most difficulty because they must fit within a restricted space and headroom is often compromised by the roof slope.

Understanding the rules also helps tradespeople identify when an existing stair is non-compliant — important when renovating, replacing balustrades, or advising clients on proposed alterations.

Key Facts

Quick Reference Table

Got your quantities? squote builds the full quote with labour, materials and markup.

Try squote free →
Total Height (mm) Risers Riser Height (mm) Going (min, mm) Total Plan Length (no landing)
2500 12 208 220 11 × 220 = 2,420mm
2500 13 192 240 12 × 240 = 2,880mm
2600 12 217 220 11 × 220 = 2,420mm
2600 13 200 220 12 × 220 = 2,640mm
2700 13 208 220 12 × 220 = 2,640mm
2700 14 193 244 13 × 244 = 3,172mm
2800 13 215 221 12 × 221 = 2,652mm
2800 14 200 220 13 × 220 = 2,860mm
3000 14 214 222 13 × 222 = 2,886mm
3000 15 200 220 14 × 220 = 3,080mm

Going values shown are the Approved Document K minimum (220mm) where the comfort formula G = 650 − 2R gives a result below that minimum; otherwise the comfort formula result is used

Stair Type Maximum Rise Minimum Going Headroom
Private (domestic) 220mm 220mm 2000mm
Common (shared, e.g. flats) 190mm 240mm 2000mm
Institutional/public 180mm 280mm 2000mm
Utility/access (loft, cellar) 220mm 220mm 1800mm (reduced)
Alternating tread (loft) 220mm 220mm 1800mm

Detailed Guidance

Step 1: Measure Total Floor-to-Floor Height

Measure from finished floor level (FFL) of the lower storey to the FFL of the upper storey. This must be the finished floor level — not the structural floor. If the upper floor is timber with 22mm chipboard, add 22mm. If the lower floor is to receive a new tiled finish, add the tile depth. Even a 10mm error in this measurement will cause the last riser to be non-compliant.

Critical tip: Measure in at least two locations and take the larger figure if they differ. Floors are rarely perfectly level.

Step 2: Calculate Number of Risers

Divide total height by a trial riser height and round to the nearest whole number.

Example: Total height = 2,700mm

Check with comfort formula: G = 650 − 2 × 208 = 234mm — meets the 220mm minimum ✓

Step 3: Calculate Going and Total Plan Length

The going is the horizontal depth of each tread. Number of treads = number of risers − 1.

Example continued: 13 risers − 1 = 12 treads

Longer going is more comfortable but requires more plan space. The plan length must fit within the available floor area including any landing at top and bottom.

Landing allowance: Add one going width (220mm minimum) at both top and bottom of the stair for a landing area — Building Regulations require a clear landing at each end.

Step 4: Check Headroom

Headroom is measured vertically from the pitch line (an imaginary line connecting the nosings of all treads) to the nearest obstruction (ceiling, trimmer joist, floor structure above).

Minimum headroom: 2,000mm on the pitch line throughout the full width of the stair.

In loft conversions, the roof slope often cuts through this measurement zone. To check, draw the stair elevation to scale and overlay the roof pitch. The critical point is usually where the roof slope crosses the stair near the top.

If headroom is insufficient: Consider:

Step 5: Verify with the Comfort Formula

2R + G must fall between 550mm and 700mm.

Winders (Tapered Treads)

Winders are used where the stair turns a corner without a full landing. Approved Document K requires that the going, measured at 270mm from the narrow end of the winder, must meet the minimum going requirement of 220mm. The narrow end must have a minimum going of 50mm.

Winders are riskier than straight flights and are not preferred in Building Control submissions for new-build properties. They are acceptable in existing buildings where space is very limited.

Balustrade and Handrail Requirements

Frequently Asked Questions

My existing stair has a rise of 225mm — is it illegal?

An existing stair that predates current regulations is not automatically illegal. Building Regulations apply at the time of construction, and older stairs were built to older standards. You only need to comply with current Approved Document K if you are replacing the stair or carrying out work that triggers Building Control notification. However, it is good practice to inform clients of any safety deficiencies.

Can I have an open riser on a new stair?

Yes, Approved Document K permits open risers on private stairs, provided that a 100mm sphere cannot pass through the opening between treads. In practice, this means balusters or other infill must be installed between treads if the gap would otherwise exceed 100mm. Open risers are not permitted on stairs used by young children (e.g. access to an area specifically designed for children).

How many winders can I use in a quarter-landing?

There is no fixed maximum number of winders, but Approved Document K requires each to meet the going requirement at 270mm from the narrow end. In practice, three winders in a 90° turn is typical. Using more winders creates narrower individual treads and increases the risk of slipping. A full quarter-landing (full-width landing at the turn point) is always the safer design.

What's the minimum width for a domestic stair?

Approved Document K does not specify a minimum width for a private domestic stair (as of the current edition). However, NHBC standards require a minimum of 800mm clear width for new-build dwellings. Fire escape requirements (Part B) may require 750mm minimum clear width on escape stairs in purpose-built flats. Check with Building Control for the applicable requirement on your specific project.

What is an alternating tread stair?

An alternating tread device (sometimes called a space-saver or ship's stair) has steps that alternate left-right, allowing a steeper pitch in restricted headroom situations. They are only permitted where a conventional stair would be impractical, specifically for access to a single room in a loft conversion per Approved Document K. They cannot be used as a main stair in a dwelling. They still require a handrail each side and minimum headroom of 1,800mm.