Summary

A pitched roof is a triangulated structure: the slope (pitch) lets water and snow run off, and the geometry turns the roof covering's weight and the external loads into forces the supporting walls can carry. Two broad forms exist. A cut roof is built on site from individual rafters, purlins, ridge boards, ceiling joists and struts — flexible for complex or traditional shapes and for loft conversions. A trussed roof uses factory-made, gang-nailed truss rafters at close centres, which is faster and cheaper but fills the roof space with webs and is not designed to be cut without an engineer's approval.

The covering dictates the minimum pitch. Plain clay or concrete tiles need a steep pitch (around 35–40 degrees) because each small unit overlaps the ones below; interlocking concrete tiles can go much lower (some down to 15 degrees), and natural slate sits in between depending on slate size and lap. Get the pitch wrong for the covering and the roof will leak by wind-driven rain tracking back under the units, regardless of workmanship.

Two things sink otherwise sound pitched roofs: inadequate fixing and inadequate ventilation. BS 5534 sets out how every tile and slate must be mechanically fixed to resist wind uplift — modern practice is to fix far more units than the old "every fifth course" rule, and to clip and nail perimeters and verges. BS 5250 deals with moisture: a traditional cold roof (insulation at ceiling level, cold void above) needs cross-ventilation so warm moist air from the house does not condense on the cold underside of the roof and rot the timbers.

Key Facts

Quick Reference Table

Spending too long on quotes? squote turns a 2-minute voice recording into a professional quote.

Try squote free →
Covering Typical minimum pitch Approx. dead load (kg/m²) Notes
Plain clay/concrete tile 35–40 degrees 65–80 Small units, double lap, heavy
Interlocking concrete tile 15–22.5 degrees 45–55 Low-pitch capable, single lap
Natural slate (large) 20–25 degrees 25–35 Depends on size and lap
Natural slate (small) 30–35 degrees 25–40 Smaller slates need steeper pitch
Fibre-cement slate 15–20 degrees 19–21 Light, check manufacturer min pitch
Clay pantile 30–35 degrees 45–55 Single lap, large format
Metal sheet/standing seam 5–15 degrees 5–15 Different fixing rules, not BS 5534

Pitches and loads are indicative — always use the manufacturer's data sheet for the specific product.

Detailed Guidance

Anatomy of a pitched roof

The principal members, working from the wall up:

            RIDGE
             /\
   purlin-> /  \ <-purlin
           /    \
  rafter->/      \<-rafter
         /        \
  ======/==========\======  <- wall plate (strapped down)
  |     ceiling joist/tie  |
  WALL                  WALL

Cut roof vs trussed roof

A cut roof is assembled from individual timbers on site. It suits complex geometries, hipped and valley roofs, vaulted ceilings, and loft conversions where you want a usable space. It needs more skilled labour and the members must be sized for the spans and loads. A trussed rafter roof is delivered as prefabricated triangulated frames at close centres, craned or lifted into place and braced — far quicker and well-suited to standard rectangular roofs. The trade-off: the truss webs occupy the loft, and a trussed roof is a complete engineered system. Cutting or removing any member to "make room" destroys the load path and can cause collapse — alterations need a structural engineer.

Pitch and the covering

Minimum pitch is set by the roof covering, not by taste. Small double-lapped units (plain tiles, small slates) need steep pitches so water sheds before it can be driven back under the lap. Large single-lap interlocking tiles can go much lower because the interlock and underlay handle wind-driven rain. Below a covering's stated minimum pitch the manufacturer's warranty is void and the roof will leak. Always confirm the minimum pitch from the specific product's data sheet — a "concrete tile" is not one number; it depends on profile and lap.

Loads: dead, imposed and wind

Roof design under BS EN 1991 (Eurocode 1) considers three load families:

A re-roof that changes the covering weight or pitch is a Part A structural matter — the rafters, wall plate fixings and restraint must still work for the new loads.

Ventilation and condensation (cold roof)

In a traditional cold roof the insulation sits at ceiling (joist) level and the loft void above is cold. Warm, moist air leaks up from the house; if the void is not ventilated, that moisture condenses on the cold underside of the roof and the timbers, leading to rot and mould. BS 5250 requires cross-ventilation:

A warm roof (insulation following the slope, at rafter level) changes the strategy — it may be unventilated if a vapour-control layer and the right membrane are used, or have a ventilated air gap above the insulation. The membrane choice (breathable vs non-breathable) interacts with the ventilation design, so the two must be specified together, not in isolation.

Fixing and weatherproofing details

BS 5534 governs how the covering is held down. Modern practice fixes far more tiles/slates than the old rule of thumb, with the fixing specification driven by a wind-uplift calculation for the building's location, height and exposure. Dry-fix systems (dry ridge, dry verge, dry valley) using mechanical clips and unions have largely replaced sand/cement mortar bedding for ridges and verges because mortar cracks and fails. Eaves, verges, ridges and abutments are the detail-critical zones — that is where wind gets under the covering and where most leaks start.

Frequently Asked Questions

Can I cut a trussed rafter to make loft space?

No — not without a structural engineer designing a replacement load path. Trussed rafters are an engineered system where every web carries load; cutting one transfers force to members never designed for it and can cause progressive failure. Loft conversions on a trussed roof usually need new structural steel or a rafter/floor redesign.

What's the minimum pitch I can lay tiles to?

It depends entirely on the tile. Plain tiles need around 35–40 degrees, large interlocking concrete tiles can go down to about 15 degrees, and slate sits in between depending on size and lap. Always use the manufacturer's data sheet for the exact product — laying below the stated minimum voids the warranty and the roof will leak.

Why does my cold loft need vents at both eaves and ridge?

Ventilation works by cross-flow: cool dry air enters low at the eaves and warm moist air leaves high at the ridge. With only one opening there is no through-path, so moisture stagnates and condenses on the cold roof timbers. BS 5250 sets the eaves (about 25mm) and high-level (about 5mm) provision for this reason.

Does re-roofing with heavier tiles need building control?

Often yes. Changing the covering weight or pitch is a structural alteration under Part A — heavier tiles increase dead load and may overload the existing rafters, wall plate and fixings. A significant re-roof (commonly more than 25% of the roof area) is notifiable to building control, who will want the structure and thermal/ventilation details checked.

What stops the roof pushing the walls outwards?

The ceiling joists or collar ties act as the bottom chord of the triangle, holding the feet of the rafters together so the roof's geometry doesn't spread and shove the walls out. Restraint straps tie the roof and gable walls together against wind racking. Remove or weaken those ties and the walls can bow.

Regulations & Standards