Which screed should I use for underfloor heating?

Quick Answer: Anhydrite (calcium sulphate) liquid screed is the preferred screed for UK underfloor heating, typically laid at 35-50mm cover over the pipes per BS EN 13813 classification CA-C25-F5. Sand/cement screed to BS 8204-1 can also be used but requires 65-75mm cover and conducts heat less efficiently. Both must be commissioned per BS EN 1264-4 with a controlled heat-up cycle before any floor finish is laid.

Summary

Underfloor heating (UFH) screed is a specialised application: the screed encapsulates the heating pipes and acts as a thermal mass that distributes heat evenly to the floor surface. The screed type, thickness over pipes, and commissioning routine determine whether the system delivers its rated output and avoids cracking or pipe damage in service.

Two screed families dominate UK UFH installations. Calcium sulphate (anhydrite) liquid screed is the default for new build and renovation projects, offering thin sections, fast pour rates, and good thermal conductivity. Traditional sand/cement screeds remain valid where waterproofing, point loading, or chemical exposure rules out anhydrite. Self-levelling cementitious flowing screeds (CT-C30-F5 and similar) offer a middle path for retrofits where load and exposure are factors.

This guide focuses on screed selection for UFH specifically, covering thickness, additives, drying time, commissioning, and the impact of screed choice on subsequent floor finishes. For general screed types and tolerances, refer to the screed-types article in Related Articles below.

Key Facts

Quick Reference Table

Spending too long on quotes? squote turns a 2-minute voice recording into a professional quote.

Try squote free →
Property Anhydrite Liquid Screed Sand/Cement Screed Cementitious Flowing
Binder Calcium sulphate (CaSO₄) Portland cement Modified cement
BS EN 13813 class CA-C25-F5 typical CT-C25-F4 typical CT-C30-F6 typical
Min cover over UFH pipe 35mm 65mm bonded / 75mm unbonded 25mm
Typical thickness over UFH 40-50mm 75mm 40mm
Thermal conductivity (W/mK) 2.0-2.5 1.2-1.6 1.6-2.0
Drying rate (mm/day to 40mm) 1mm/day 1mm/day 1.5mm/day
Days to flooring (40mm) 40-60 days 60-90 days 30-45 days
Max pour without joints 1000m² 40-50m² 200-300m²
Surface regularity (as laid) SR1 SR2 SR1
Suitable for wet areas No (without surface DPM) Yes Yes
Compatible with ceramic tile Yes (after laitance removal) Yes Yes
Compatible with timber/LVT Yes (after sanding) Yes Yes
Reinforcement needed No Often (mesh or fibres) No

Detailed Guidance

Anhydrite (calcium sulphate) liquid screed

Anhydrite is the dominant UFH screed in the UK for residential and small-to-medium commercial work. Delivered by tanker and pumped through hose to the laying point, it self-levels with minimal trowelling, encapsulates pipes completely without voids, and reaches walking traffic in 24-48 hours.

Practical advantages for UFH:

Practical constraints:

Sand/cement (CT) screed

Traditional sand/cement screed is still specified where anhydrite's limitations matter. The typical mix is 1:3 to 1:4 cement to sharp sand with a polypropylene fibre dosing or A142 mesh reinforcement on a slip layer.

Practical advantages:

Practical constraints:

Cementitious flowing screeds

A growing category of modified cementitious flowing screeds (e.g. CT-C30-F6 to CT-C40-F7) offers the laying speed of anhydrite with the water tolerance of sand/cement. These products use Portland cement with shrinkage-compensating admixtures and pump-grade fluidifiers.

Practical positioning:

Commissioning the UFH before flooring

BS EN 1264-4 sets the commissioning protocol that must be followed regardless of screed type. The purpose is to ensure the screed is fully cured, dried, and stress-relieved before a sensitive floor finish is bonded.

The standard cycle:

  1. Initial cure period — anhydrite minimum 7 days; sand/cement minimum 28 days from pour
  2. Start-up — flow temperature at 25°C, hold for 3 days
  3. Daily increase — raise by 5°C per day to maximum design flow temperature (typically 35-45°C)
  4. Hold at maximum — minimum 3 days, ideally 7 days for residential
  5. Cool-down — drop by 5°C per day back to ambient
  6. Moisture verification — test at multiple locations after cool-down; must be ≤75% RH before flooring

The commissioning record must be kept and signed by the heating contractor. Most floor finish manufacturers require a copy as a warranty condition.

Laitance removal (anhydrite specific)

The single most common cause of flooring failure over anhydrite screed is failure to remove the surface laitance. The laitance is a layer of fine particles brought to the surface during pouring. It is weak, friable, and will not bond to adhesives or smoothing compounds.

Process:

  1. Verify screed is below 75% RH and fully cured
  2. Vacuum thoroughly to remove dust
  3. Sand with a 60-80 grit floor sander (or planetary diamond grinder for larger areas)
  4. Vacuum again
  5. Test bond: tape a piece of LVT down with masking tape, leave 24 hours, lift — if dust comes up, sand again
  6. Prime with the smoothing compound manufacturer's recommended anhydrite primer
  7. Apply smoothing compound to required depth

Skipping any step risks the final floor lifting in patches within weeks.

Pipe layout, fixings and screed depth

Pipe layout affects screed performance. Common patterns:

Fix pipes to the insulation (PIR or EPS) with staples, clips, or rails at 300-500mm intervals. Pipes must not lift during the screed pour. Use pressure-test the system to 6 bar minimum and leave under pressure during the pour to immediately identify any pipe damage.

Edge insulation (typically 10mm closed-cell foam) is fitted vertically against all walls and columns to create the perimeter expansion joint and prevent heat loss to the walls.

Frequently Asked Questions

Can I lay UFH pipes directly on a sand blinding without insulation?

No. UK Building Regulations Approved Document L requires minimum insulation under heated floors to prevent downward heat loss. Typical specification is 100-150mm PIR for ground floors, 25-50mm for intermediate floors over a heated space.

How long before I can walk on liquid screed?

Anhydrite: 24-48 hours for foot traffic, 7 days for light tools and equipment. Loading the screed before 7 days risks cracking. Heavy loads should wait until 28 days.

Why can't I force-dry sand/cement screed for the first 28 days?

Portland cement requires water for hydration. Force-drying before primary cure removes the water needed for the cement to develop full strength. Force-drying too early gives a weak, dusty screed that will fail in service.

Can I use UFH with a timber floor over screed?

Yes, but with constraints. Solid timber is rarely recommended above UFH due to shrinkage; engineered wood with a multi-ply backing is the safer choice. Maximum surface temperature at the timber/screed interface is typically 27°C — confirm with the timber manufacturer.

What happens if I flood test before commissioning?

Anhydrite screed will degrade immediately on contact with water. Sand/cement is tolerant. Run UFH pressure tests in air or with the system filled and pressurised before screeding, not water-flood tested after.

Regulations & Standards