Boiler Ignition Parts Fault Finding: Spark Electrode, Gas Valve, PCB, Flame Sensor and Ignition Lead Diagnosis

Quick Answer: Boiler ignition failures account for the majority of "no heating, no hot water" call-outs. The ignition sequence involves: PCB fires the spark electrode → gas valve opens → burner lights → flame sensor (ionisation probe) confirms flame → PCB holds gas valve open. Failure at any stage produces a lockout. All gas work, including diagnosis and parts replacement on gas boilers, is notifiable under the Gas Safety (Installation and Use) Regulations 1998 and must be carried out by a Gas Safe registered engineer.


SAFETY WARNING: Gas work is notifiable. Only Gas Safe registered engineers may work on gas appliances. If you smell gas, leave the property immediately, do not operate any switches, and call the National Gas Emergency Service on 0800 111 999. Never attempt to diagnose or repair a gas boiler unless you hold a valid Gas Safe registration and the relevant ACS competencies (e.g. CCN1, CPA1, CKR1).


Summary

A boiler that locks out on ignition but has a working gas supply, correct pressure, and no visible fault can be maddening to diagnose. The components in the ignition chain — spark electrode, ignition lead, gas valve, ionisation probe (flame sensor), and PCB — are all interdependent, and a fault in one can look exactly like a fault in another.

The approach used by experienced Gas Safe engineers is systematic: confirm gas supply and pressure first, then work through the ignition chain from PCB output to burner, testing each component in sequence. Replacing parts without this sequence wastes the client's money and delays resolution.

This article provides a structured fault-finding framework for Gas Safe registered engineers. It covers the most common failure modes, testing procedures, and a decision-tree diagnostic for the most frequently seen ignition faults on combi boilers.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Component Symptom of failure Test method Pass criteria
Spark electrode No spark, intermittent spark, lockout Visual check gap (3–4mm), crack. Multimeter ground test. No carbon bridge, gap correct, insulation intact
Ignition lead Spark at electrode weak/absent Multimeter, high-Ω range. Visual for insulation damage. 5–20 kΩ (check manufacturer spec)
Gas valve (solenoid) Spark present, no gas, lockout Multimeter across valve terminals (with power). Coil resistance. 230V AC applied in ignition sequence; coil resistance per spec
Ionisation probe Burner lights then lockout (usually within 5 sec) DC microammeter in series with probe lead 1.5–8 μA DC in stable flame
PCB No spark output, no valve signal, random lockouts Process of elimination after ruling out all above Correct voltages at all output terminals per wiring diagram
Air pressure switch (APS) Fan runs, no ignition, no spark Multimeter across switch contacts. Tube block test. Closed in run, open at rest; silicone tube unblocked, condensate free
Gas pressure Ignition fails at peak demand or in cold weather Calibrated manometer at gas valve inlet test point ≥17 mbar working pressure at max rate

Detailed Guidance

ASCII Decision Tree — Boiler Ignition Fault Diagnosis

BOILER LOCKOUT / WILL NOT IGNITE
          |
          v
Is there a gas supply to the property?
(Check gas hob if present, or meter supply)
          |
    NO ---+---> Call National Gas Emergency: 0800 111 999
          |
         YES
          |
          v
Check boiler fault code (manufacturer guide).
Is code an ignition fault?
(E.g. EA / E01 / F01 / 3H / E1 / 110)
          |
    NO ---+---> Follow fault-code specific guide (overheat, APS, pump, etc.)
          |
         YES
          |
          v
Check gas inlet pressure at valve test point.
Is working pressure ≥17 mbar?
          |
    NO ---+---> Low pressure fault — check meter regulator, pipework.
          |     Notify gas transporter (Cadent, Wales & West, SGN) if meter issue.
          |
         YES
          |
          v
Power boiler OFF. Remove burner cover.
Inspect spark electrode visually.
Is electrode cracked, carboned up, or gap outside 3–4mm?
          |
   YES ---+---> Clean/adjust/replace electrode.
          |     Reset and test. Does it ignite?
          |        YES → resolved.
          |        NO  → continue below.
          |
    NO (electrode looks OK)
          |
          v
Test ignition lead with multimeter (high-Ω range, 20MΩ).
Is resistance within spec (typically 5–20 kΩ)?
          |
    NO ---+---> Replace ignition lead. Test. Ignites? YES → resolved.
          |
         YES
          |
          v
Power boiler ON. Observe ignition attempt.
Is there a visible spark at electrode?
          |
    NO ---+---> Check PCB ignition output terminals.
          |     Is 230V AC present at ignition terminal during attempt?
          |        NO  → PCB not firing. Check APS first (see below).
          |        YES → Spark transformer failed (if separate) or
          |              electrode/lead fault not caught above.
          |
         YES (spark present)
          |
          v
Does gas flame appear at burner?
          |
    NO ---+---> Gas valve not opening.
          |     Check 230V AC at valve coil terminals during attempt.
          |        NO  → PCB not sending valve signal. Check APS, fan signal.
          |        YES → Check valve coil resistance. Within spec?
          |              NO  → Replace gas valve.
          |              YES → Valve mechanically stuck (rare). Replace.
          |
         YES (flame appears)
          |
          v
Does boiler run for >5 seconds then lock out?
          |
    NO ---+---> Ignition succeeds. Look for other fault (overheat, etc.)
          |
         YES
          |
          v
Ionisation/flame sense fault.
Test probe current with DC microammeter in series.
Is current ≥1.5 μA DC during stable flame?
          |
    NO ---+---> Probe dirty, cracked, or grounded. Clean/replace probe.
          |     Check earth reference for probe circuit.
          |     Still fails? Check PCB flame sense circuit.
          |
         YES
          |
          v
PCB failing to hold on adequate flame signal.
Consider PCB replacement (after checking all wiring, connectors,
and earthing — loose earths cause spurious ionisation readings).

If all components test correctly and fault persists:
→ Flue gas CO₂ reading — is combustion in spec?
→ Gas rate at meter (ft³/hr or m³/hr) — within boiler spec?
→ Check for intermittent gas supply (pressure surge/dip).
→ Consult manufacturer technical support.

Spark Electrode Diagnosis

The spark electrode is the most commonly replaced ignition part, and also the most commonly misdiagnosed. Before replacing:

Visual inspection:

Electrical test: Using a multimeter in resistance mode (highest range), measure between the electrode tip and earth. In air (electrode removed from boiler), resistance should be >1 MΩ. If it is significantly lower, the insulator is tracking. Replace the electrode.

Ignition Lead Diagnosis

The ignition lead carries the high-voltage pulse from the ignition transformer to the electrode. Leads fail due to insulation breakdown, especially near the boiler casing where they are subject to heat cycling.

Test:

Visual: Check for insulation damage, kinks, burns, or a poorly seated push-fit connector at the electrode end. Corrosion at the connector can cause intermittent spark even when the lead itself is intact.

Gas Valve Diagnosis

Safety: Gas valve diagnosis involves working on the gas-carrying components of the appliance. Confirm the gas is isolated at the boiler service valve before testing coil resistance. Never bypass or manually force a gas valve open.

Solenoid coil test:

Live voltage test (Gas Safe engineer only):

Ionisation Probe (Flame Sensor) Diagnosis

The ionisation probe works by passing a small DC current through the flame. The flame conducts electricity (due to ionised gas ions), completing the circuit back to the PCB. A PCB typically looks for 1.5–8 μA DC.

Common failure modes:

Test: A DC microammeter connected in series with the probe lead (break the circuit, insert the ammeter) will show the actual probe current during a flame attempt. This is the definitive test. Most modern diagnostic tools (e.g. Fluke 87V with μA mode, or dedicated boiler diagnostic meters) can measure this directly.

PCB Diagnosis

The PCB is the last component to replace — it is the most expensive and most often incorrectly blamed. Before replacing a PCB:

  1. Check all wiring connectors are fully seated — vibration from the fan loosens connectors over time.
  2. Check the PCB for visible burn marks, swollen capacitors, or corrosion.
  3. Verify all input signals are correct (fan speed signal, APS switch, NTC thermistor readings, pressure sensor).
  4. Consult the manufacturer's wiring diagram and service manual — PCB outputs can be tested with a multimeter at the terminal block.

If a PCB is replaced and the fault persists, the original component was not the cause. A systematic approach at the start saves this outcome.

Frequently Asked Questions

The boiler sparks but the gas never lights — where do I start?

Confirm spark is present at the electrode (not just that the PCB is sending a signal). If spark is confirmed, the issue is with gas delivery to the burner — check gas pressure at the valve inlet test point, then check the valve solenoid coil resistance and whether the PCB is energising the valve during the ignition attempt. A gas valve that opens but does not allow adequate flow may have a blocked filter (replaceable on some valves) or a faulty actuator.

The boiler lights, runs for 3–5 seconds, then locks out — what is this?

This is almost always an ionisation probe (flame sensor) issue. The boiler lights successfully, but the PCB does not receive a strong enough flame-sense signal to hold the gas valve open. Clean the probe first. If that fails, test probe current with a DC microammeter. If current is adequate, the PCB flame-sense circuit may be at fault.

The boiler ignites fine on first call of the day but then locks out on subsequent calls — what causes this?

Intermittent ignition faults that worsen when the boiler is hot are often caused by a cracked electrode insulator (tracking worsens when hot), a heat-degraded ignition lead, or a PCB component that fails when warm. A gas valve that sticks when hot (thermal expansion of valve body) is less common but possible. Diagnose in the hot condition, not after allowing the boiler to cool.

Can I replace a gas valve myself if I am Gas Safe registered?

Yes, if you hold the relevant ACS competencies. Gas valve replacement is gas work within the scope of a Gas Safe registered engineer with CCN1/CPA1. The replacement valve must be the correct OEM part or an approved equivalent for that boiler. After replacement, a full tightness test, combustion analysis, and Benchmark record are required.

My client has a boiler under a service contract — should I still carry out the repair?

Check the terms of the service contract. Many contracts (British Gas HomeCare, etc.) require the client to use the contract provider for repairs. If you carry out repair on a boiler under a live third-party contract, the client may face issues with their contract warranty. Advise the client to check first.

Regulations & Standards