No Power to a Circuit: MCB Tripped, RCBO Fault or Broken Ring - Step-by-Step Diagnosis
Quick Answer: When a single circuit loses power, check first whether an MCB or RCBO has tripped at the consumer unit (90% of cases). A tripped MCB typically indicates an overload (too many appliances) or short circuit; a tripped RCBO indicates an earth leakage fault. Reset and observe — if it trips again immediately, there's a fault on the circuit. A broken ring final circuit (one leg of the ring open) leaves outlets working but with overloaded conductors and overheating risk — diagnosed by an inspection and testing visit using insulation resistance and continuity tests under BS 7671:2018+A2:2022. All circuit-side investigation must be by a competent person under Part P; resetting tripped switches at the consumer unit is the only homeowner-safe diagnostic.
Summary
Single-circuit power loss is one of the most-called electrical faults in UK domestic property because it's specific (one room or set of outlets stops working) but not usually an emergency (the rest of the house is fine). The diagnostic pattern is consistent: check the consumer unit first, identify which MCB or RCBO has tripped, attempt reset, observe whether it trips again, then trace the fault.
The trade pricing pattern: most circuit-loss calls are £80–£180 for diagnosis and reset where the cause is a faulty appliance, plus the cost of any specific repair. £180–£400 for a broken ring or loose terminal that needs trace-and-repair work. £400–£900 if multiple components need replacing or rewiring is involved.
The safety-critical case is the broken ring final circuit — a ring circuit where one leg has been broken (often by a DIY drilling into wall, or rodent damage) but the other leg still carries current. The outlets still work but the cable is now operating at twice its design current, and the conductors heat up under load. This is invisible without testing and is a fire hazard. EICR inspection picks it up; routine reset doesn't.
Key Facts
- MCB (Miniature Circuit Breaker) — over-current protection, trips on overload or short circuit
- RCBO (Residual Current Breaker with Overcurrent) — combines MCB plus RCD function in one device
- RCD (Residual Current Device) — earth leakage protection, trips on imbalance between live and neutral currents
- Standard ratings — domestic — 6A (lighting), 16A or 20A (small power), 32A (ring final or radial), 40A or 50A (cooker, shower)
- Domestic ring final circuit — 32A MCB protecting 2.5mm² T+E cable in ring
- Radial circuit — 16A or 20A MCB protecting 2.5mm² (16A) or 4mm² (20A) T+E cable
- Maximum continuous current — 2.5mm² T+E — about 27A in cavity wall (rating depends on installation method)
- Trip curve types — Type B (3–5× rated current), Type C (5–10×), Type D (10–20×); domestic typically Type B
- Test functions on consumer unit — RCD test button (intentional trip); typical 6-monthly press-test
- Insulation resistance test (Megger) result — 1MΩ minimum at 500V DC for installation conductors (BS 7671)
- Ring circuit continuity test — measure conductor end-to-end; both legs should give similar readings
- EICR (Electrical Installation Condition Report) — inspection report grading installation per BS 7671
- Part P notification — notifiable work (new circuit, consumer unit replacement, kitchen/bathroom rewires); self-cert by competent person scheme member, or LABC sign-off
- Common fault appliances — kettles, toasters, hairdryers (heating elements failing), washing machines (motor or heater fault), faulty extension leads
Quick Reference Table — Circuit Loss Diagnosis
Diagnosed the problem? Create a repair quote in minutes with squote.
Try squote free →| Symptom | Most likely cause |
|---|---|
| MCB trips immediately on reset | Short circuit on circuit |
| MCB trips after a few seconds | Overload (too many appliances) |
| MCB trips intermittently | Loose terminal, intermittent short, sparing fault |
| RCBO trips immediately on reset | Earth fault on appliance or circuit |
| RCBO trips intermittently | Damp accumulation, deteriorating insulation |
| MCB resets and stays on | Reset successful — observe pattern |
| Outlets work but overheating | Broken ring — testing required |
| One outlet dead, others on circuit work | Local outlet fault (loose terminal, failed back box) |
Detailed Guidance
Systematic Diagnosis Flow
NO POWER TO CIRCUIT
Step 1: Identify which circuit
├── List affected outlets/lights
├── Match to circuit chart on consumer unit door
└── Identify the MCB or RCBO protecting that circuit
Step 2: At the consumer unit
├── Is the relevant MCB/RCBO tripped (down/off)?
│ ├── YES → Continue to Step 3
│ └── NO → Check connections inside CU (ELECTRICIAN ONLY)
│
Step 3: Reset attempt
├── Unplug all appliances on the circuit
├── Switch the MCB/RCBO back ON
│ ├── Stays ON → Plug appliances in one at a time to find faulty one
│ ├── Trips immediately → Short or earth fault on circuit
│ └── Trips after seconds → Overload or developing short
│
Step 4: If MCB trips immediately
├── Likely a short circuit
├── Disconnect circuit from CU at this point — DO NOT reset further
└── Electrician needed for testing
│
Step 5: If RCBO trips immediately
├── Likely an earth fault
├── Unplug everything and reset
│ ├── Holds with nothing plugged in → Fault is in an appliance
│ │ └── Plug back in one at a time to identify
│ └── Still trips with nothing plugged in → Fault on fixed wiring
│ └── Electrician needed for insulation resistance test
│
Step 6: If MCB stays on after reset
├── Identify which appliance caused trip
├── Inspect appliance flex and plug
├── Replace appliance, fuse in plug, or have appliance repaired
└── Monitor for re-trip
Common scenario — overload trip
Most-common cause: customer plugs an extra heater or appliance into a circuit already running near capacity. MCB trips after a few seconds.
Reset procedure:
- Identify and unplug the high-current appliance
- Reset MCB
- Run on lighter load
- Long-term: dedicated circuit for the high-current appliance, or accept the load profile
A 32A ring circuit (typical UK socket circuit) handles about 7,360W continuous (32A × 230V). A kettle at 3,000W + microwave at 1,200W + toaster at 1,000W = 5,200W = OK, but adding a 2,500W heater pushes it over. Trip is the safety system working correctly.
Common scenario — short circuit (MCB instant trip)
Live and neutral conductors making direct contact, or a faulty appliance with internal short. Symptoms: MCB trips the moment it's switched on.
Diagnostic:
- Unplug all appliances
- Try MCB reset
- Stays on → fault in unplugged appliance; reintroduce one by one
- Trips even with nothing plugged in → fault in fixed wiring (cable damage, faulty back box, water ingress)
If the fault is in fixed wiring, an electrician investigates by disconnection at the CU and live-side testing. Common fixed-wiring causes:
- Nail or screw through cable (DIY)
- Rodent damage to cable in loft or void
- Damaged cable at flexible connection (e.g. cooker outlet plate)
- Failed accessory (smashed socket, water-damaged outdoor outlet)
Repair cost: £140–£500 depending on access and extent.
Common scenario — earth fault (RCBO trip)
Earth leakage exceeds 30mA (RCD trip threshold). Causes:
- Faulty appliance — internal short to earth in motor, heating element, transformer
- Damaged cable — earth conductor short to live or neutral
- Damp or water ingress — outdoor outlet flooded, kitchen circuit with water damage
- Cumulative leakage — many small leakages summing to over 30mA (fridge, freezer, computer, washing machine all on one RCD)
Diagnostic:
- Unplug everything on the circuit
- Reset RCBO
- Holds → fault is in an appliance (plug back in one at a time)
- Doesn't hold → fault in fixed wiring
- For fixed wiring: insulation resistance test (Megger) at 500V — should read >1MΩ; failure indicates earth leakage point
Specialist scenario — broken ring final circuit
A ring final circuit has two legs running from the consumer unit, around the property, and back. If one leg is broken (cable cut, terminal disconnected, rodent damage), outlets still work because the remaining leg supplies them — but at twice the design current.
Symptoms:
- Outlets working normally
- Sometimes warm sockets or covers
- Burning smell when high load run
- No tripped MCB
Detection: continuity test of conductors at both ends of ring. Both legs should give similar readings. A broken leg shows infinite resistance on one side.
Repair: identify break point, restore connection. Cost £180–£500 depending on access (cable in floor void, behind plaster, etc.).
EICR inspection picks this up — homeowners with no symptoms but a broken ring won't know without periodic testing.
Specialist scenario — failed MCB or RCBO
Less common, but MCBs and RCBOs do fail:
- Internal mechanical failure — won't reset, or won't trip on fault
- Internal contact failure — high resistance, heats up under load
- Coil failure — RCBO doesn't trip on test button
Diagnosed by competent person; replace device (£15–£40 supply, £80–£180 fitted including isolation and testing).
A consumer unit older than ~25 years may have multiple devices nearing end of life — full unit replacement (£600–£1,200 typical) often more economic.
When to call out an electrician immediately
- Smell of burning from any outlet, switch or consumer unit
- Smoke from any outlet or fitting
- Cable visible damage (sheath compromised, conductor exposed)
- Water or damp ingress at consumer unit
- MCB/RCBO won't reset and stays in tripped position
- Lights flickering with whole-house pattern
- Voltage anomalies (lights very bright then very dim)
Resetting safely as a homeowner
The only homeowner-safe diagnostic is resetting an MCB or RCBO at the consumer unit:
- Identify the tripped device (lever in down/off position)
- Unplug all appliances on that circuit (if ring final)
- Push the lever firmly to ON
- Test by plugging appliances back in one at a time
If the device won't reset, or trips again immediately, stop and call an electrician. Repeated reset attempts on a fault circuit risk fire and personal injury.
Frequently Asked Questions
Why does my MCB keep tripping?
Three possible causes: overload (too many high-current appliances), short circuit (live touching neutral), or faulty MCB. Unplug everything, reset, then plug in one at a time to identify a faulty appliance. If it trips with nothing plugged in, you need an electrician.
What's the difference between an MCB and an RCBO?
MCB protects against over-current (overload, short circuit). RCBO does both that and earth leakage protection. RCBOs are now the standard in modern consumer units, replacing the older MCB+RCD split-load arrangement.
Can I replace a tripping MCB myself?
No. Work inside the consumer unit is notifiable under Part P (England and Wales) and must be done by a competent person who can self-certify. DIY replacement risks injury and invalidates insurance.
Why do RCBO trips happen at random times?
Often cumulative leakage from multiple appliances, or a marginal fault that develops under specific conditions (temperature, humidity). Pattern-tracking helps: note when trips occur (time, weather, what was running). Sometimes a single appliance is the cause but only at end of cycle.
How much does an electrician charge to diagnose a tripping circuit?
£80–£180 typical for a diagnostic visit. Repair cost extra: £40–£100 for accessory replacement, £180–£500 for fixed-wiring repair, £600–£1,200 for consumer unit replacement.
Regulations & Standards
BS 7671:2018+A2:2022 — IET Wiring Regulations (current edition for UK fixed installations)
Building Regulations Approved Document P — electrical safety in dwellings
The Electricity at Work Regulations 1989 — workplace electrical safety
The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 — landlord EICR every 5 years
BS EN 60898 series — circuit-breakers for over-current protection
BS EN 61009 series — residual current operated circuit-breakers with integral overcurrent protection (RCBOs)
BS EN 61008 series — residual current operated circuit-breakers without integral overcurrent (RCDs)
BS EN 60669 series — switches for household and similar fixed-electrical installations
BS EN 62606:2013+A1:2018 — arc fault detection devices (AFDDs)
The Electricity Safety, Quality and Continuity Regulations 2002 (ESQCR) — DNO supply standards
BS 7671 Wiring Regulations — IET / NICEIC publication
NICEIC — UK electrical competent person scheme
NAPIT — alternative competent person scheme
Electrical Safety First — UK consumer-facing safety body
HSE — Electricity at Work — workplace electrical safety