Summary

The call comes at 7am or 11pm: "the alarm is beeping and we can't make it stop". The customer has usually tried entering their code, which silences the beep for a few minutes, after which it starts again. What they are hearing is the panel's internal sounder or the keypad buzzer announcing a fault condition that it is required to report. Intruder alarm panels built to the European standards used in the UK since 2005 are designed not to fail silently: a lost mains supply, a battery that cannot hold the system up, a detector that has gone quiet or been opened, or a monitoring path that has dropped all generate a fault indication, and on most panels an audible one at least until acknowledged.

For the engineer, the diagnostic is mostly about reading the panel. Every modern panel will show the fault on the keypad (text on an LCD, a code or a flashing LED pattern on an LED keypad); the manufacturer's user guide lists the codes, and most are self-explanatory: "AC fail", "Battery low", "Tamper zone 4", "Comms fail", "RF low battery zone 7", "Bell tamper". Older panels and the budget end of the market are cruder, but the same five causes account for nearly all of the beeping. The fix ranges from pressing the right button to a new panel, and the skill is in knowing which before you turn up with the wrong parts.

This guide gives the diagnostic order, the standards behind the behaviour (why the panel beeps, how long it must run on battery, what a tamper is), the common causes and fixes on wired and wireless domestic systems, the PSTN switch-off issue that is now generating comms faults on monitored systems across the country, and what to charge. For false alarms (the external sounder going off) rather than panel beeping, see alarm system false alarms; for system grades and what they mean see intruder alarm grades.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Keypad / panel indication Most likely cause Check Fix
"AC fail", "Mains fail", mains LED off Spur switched off, fuse blown, circuit tripped, power cut Spur switch and fuse; consumer unit; neighbours Restore supply; replace 3 A fuse; find what trips the circuit
"Battery low", "Battery fault", beeps every minute Standby battery exhausted or failed; charger fault Battery date and voltage; charging voltage at terminals Replace SLA battery; if no charge voltage, PSU or panel fault
"Battery missing" after a power cut Battery too flat to be recognised; disconnected lead Battery terminals and voltage Charge or replace; reconnect
"Tamper zone N" or "Tamper" Detector lid open, loose on bracket, cable damaged, decorating The named zone's device and its lid screw Refit lid; re-terminate; replace tamper switch
"Bell tamper", "Bell fault", "SAB fault" Bell box lid, water ingress, flat bell battery, cable fault Bell box externally (ladder); battery and board for water Dry and reseal or replace bell box; replace battery
"RF low battery zone N", "Low batt" Wireless detector, contact, keypad or sounder cell low Device battery Replace lithium cell; re-learn or poll device
"RF fault", "Supervision fail", "Device missing" Wireless device not reporting: dead battery, moved, out of range, interference Device, signal strength on panel Replace battery or device; re-site; add repeater
"Comms fail", "Line fault", "Path fault", "Dialler fault" Phone line migrated to digital or disconnected; broadband off; SIM lapsed; ARC down Line/broadband status; communicator LEDs Fit IP/GSM communicator; restore line; renew SIM
"Fuse fault" or auxiliary 12 V missing Blown panel fuse or auxiliary short (detector cable damaged) Panel fuses; aux current Replace fuse; find the shorted device
"Engineer reset required" after any of the above System configured for engineer reset — Clear fault, enter engineer code or remote reset
Keypad beeps on entry/exit only Normal: entry/exit tone; or chime enabled on a zone Chime setting Explain or disable chime
Beeping with no display and no mains LED Mains failed and battery now flat; panel on its last reserve Spur, fuse, battery Restore mains, then replace battery (it will not recover)

Detailed Guidance

Step 1 — read the panel before you touch it

Ask the customer what the keypad says, or get them to send a photograph of the display. On an LCD keypad the fault is written in words. On an LED keypad there is a fault LED and a sequence (often the zone LEDs flash to indicate which zone or which fault type: the user manual lists them). Then open the event log (engineer or user menu) and read the last twenty events. The log turns a vague "it started beeping yesterday" into "mains fail 18:42, mains restore 18:44, battery low 06:10", which tells you the supply dropped briefly, the battery could not take even a two-hour hold, and the battery is the job.

Panel/keypad beeping
├─ Display says MAINS / AC FAIL ────────► Spur switch, fuse, circuit, power cut
├─ Display says BATTERY ───────────────► Replace SLA battery; check charging voltage
├─ Display says TAMPER + zone ─────────► That device's lid/bracket/cable
├─ Display says BELL / SAB ────────────► Bell box battery, lid, water, cable
├─ Display says RF / LOW BATT + zone ──► Wireless device cell; re-poll
├─ Display says COMMS / LINE / PATH ───► Phone line digital migration, broadband, SIM
├─ Display blank, no mains LED ────────► Mains lost AND battery flat: restore, then new battery
└─ No fault shown, beeps on arming ────► Chime / exit tone: user setting, not a fault

Step 2 — mains

Find the panel's fused spur. It is routinely in an under-stairs cupboard, airing cupboard or loft, and routinely switched off by a decorator, a plumber or a curious child. Check the switch, then pull the fuse carrier and check the fuse (3 A, BS 1362). If the spur is live and the panel still shows mains fail, measure at the panel's transformer input and output; a dead transformer or a failed switched-mode PSU with mains present is a panel repair or replacement. If the spur is on a circuit that keeps tripping, the fault is in that circuit, not the alarm, and an electrician needs to find it. Note: a panel showing mains fail after a power cut that has since been restored usually just needs the fault acknowledged; the battery, however, has now been discharged and should be tested.

Step 3 — the standby battery

The battery is the most common cause and the most common lazy fix, so do it properly. With mains on, measure across the battery terminals: 13.5–13.8 V means the charger is working. Disconnect the battery and measure again after a minute: a healthy charged SLA sits at 12.8–13.0 V; one that falls to 12.0 V or below on open circuit, or that collapses under the bell test load, is finished. Look at the date code on the battery; anything over five years old is replaced on sight. Fit the correct capacity for the panel and the standby time the grade requires (the installer should have done a standby calculation: panel quiescent current plus every detector and keypad, times 12 hours, divided by 0.8 for battery ageing, with the bell load added for the alarm period). On a 7 Ah system the maths usually works for a Grade 2 domestic install with up to 8–10 detectors; a system with more devices, or sounders drawing from the aux, may need 17 Ah.

If the new battery shows no charge voltage, or the fault returns within weeks, the PSU's charging circuit is the fault. Some panels have a replaceable PSU board; most of the domestic ones are replaced whole.

Step 4 — tampers

A tamper fault names the device, and the fix is at the device. Check its lid is on, the lid screw is present and tight (tamper switches are microswitches with little travel: a lid a millimetre proud is open), the device is fully on its bracket, and the cable to it is not damaged or disturbed (a picture hook into a cable in a safe zone will do it). On wireless devices a back-tamper reports if the device is lifted off the wall. Decorating is the usual trigger: PIRs taken down to paint and not clicked home. Clear the fault and reset; on systems configured for engineer reset, the engineer code or remote reset is needed even after the lid is refitted. If the system has a lot of tampers over the log, look for a loose panel lid, a junction box behind a wardrobe, or a cable chewed by a rodent in the loft.

Step 5 — bell box

Bell box faults need a ladder and are the one domestic alarm job with a real height risk (Work at Height Regulations 2005: a stable ladder, three points of contact, or a tower for anything above first-floor eaves). Open the box: a flat or swollen standby battery, water tracking down the cable into the board, corroded terminals, a lid tamper spring that has fatigued, or a cable with a nail through it from a fascia replacement. Dry, repair or replace; if the box is over ten years old and the board is corroded, replace the box rather than its battery.

Step 6 — wireless devices

A wireless detector, door contact, keypad or siren with a low cell reports it in advance of failing; a device that has not reported at all for the supervision period (typically 2–24 hours depending on grade and settings) generates a supervision or missing-device fault. Replace the cell with the specified lithium type (CR123A, CR2, AA or ½AA lithium: never alkaline where lithium is specified, the voltage curve is wrong and the panel will report low battery within weeks), then trigger the device so the panel sees it and re-polls. If a device keeps dropping off, check range and interference: a new metal-faced door, a mirror, a wifi mesh node or a smart meter installed nearby can be enough; re-site the device or add a repeater. Grade 2 wireless systems should also be checked against their supervision and jamming settings; see wireless alarm systems.

Step 7 — communications and the PSTN switch-off

A monitored system reports to an alarm receiving centre over a path: traditionally a PSTN dialler on the house phone line, now increasingly IP over broadband, a GSM/4G SIM, or both. Openreach's analogue line switch-off is migrating phone lines to digital voice through a router, and a PSTN dialler plugged into a digital-voice adapter either fails outright or reports intermittently; the panel logs comms fail and beeps. The programme completes nationally in January 2027. The fix is a communicator upgrade: an IP module on the broadband router, a 4G module with a monitored SIM, or a dual-path unit for Grade 2 and 3 monitored systems (the ARC and the insurer usually require dual path for police response). Budget £180–£350 fitted plus the monitoring contract. Also check the simple things: broadband down, router replaced and the Ethernet lead not reconnected, SIM contract lapsed, ARC account suspended for non-payment. See alarm receiving centre arc.

Step 8 — when to replace the panel

Replace rather than repair when the panel is over 15 years old and shows PSU or charging faults; when the manufacturer no longer supplies spares, keypads or firmware; when it cannot accept a modern communicator; or when the customer wants app control that the old panel cannot offer. A Grade 2 hybrid panel (wired zones plus wireless expansion) with a new keypad, programmed and with existing wired detectors retained, is £350–£700 fitted. Document the zones before you power down the old one; the customer rarely knows which PIR is zone 5.

Pricing and the maintenance conversation

A fault-finding visit at £70–£130 that ends in a £25 battery is a fair job if you also test the whole system (walk test every detector, bell test, tamper check, battery and PSU voltages, log review) and leave the customer with a report. Most beeping call-outs are on systems that have had no service since installation. An annual service at £80–£150 (two visits a year for monitored Grade 2 and above, per PD 6662 and the ARC contract) finds the battery before it fails at 3am, and is the right thing to offer. See security system maintenance contracts.

Frequently Asked Questions

Can the customer just turn the alarm off to stop the beeping?

They can silence it with their code, but the fault remains and the panel will usually beep again at intervals until it is cleared. Disconnecting the mains and the battery stops it completely but leaves the house with no alarm, and on a monitored system generates a fault at the ARC. Better to read the fault off the keypad, fix the common ones (spur switched off, lid off a PIR) and book an engineer for the rest.

How long should a burglar alarm battery last, and how long will it run the system?

The sealed lead-acid standby battery in a domestic panel lasts three to five years in service, less in a hot loft or a cupboard next to a boiler. Once charged it must hold the system for 12 hours at Grade 2 under PD 6662:2017 (30 hours at Grade 3, 60 hours at Grade 4), and most 7 Ah batteries on a modest domestic system exceed that when new. A battery that cannot hold the panel through a two-hour power cut is at the end of its life.

Why does it beep every time there is a power cut, even though it comes back on?

Because mains failure is a reportable fault and the panel records it. Many panels require the user to acknowledge the fault even after the mains has returned; on some it clears automatically after restore. If the beeping continues after a power cut has ended and been acknowledged, the battery has been drawn down and cannot recover, which is the battery, not the power cut.

The alarm says "comms fail" and we have just gone to digital phone with our broadband provider. Is that connected?

Almost certainly. Analogue diallers do not work reliably through digital-voice adapters, and the PSTN switch-off completing in January 2027 means every PSTN-monitored alarm in the country needs an IP, GSM or dual-path communicator. Contact the alarm company that monitors the system (on the sticker on the bell box or panel) before the ARC suspends the account.

Do I have to be NSI or SSAIB approved to fix a beeping alarm?

Not for an unmonitored domestic system; any competent engineer can replace a battery or a PIR. For a monitored system, an insurance-specified system, or one with a police URN, the maintenance must be by an approved company to keep the certificate and the response, and the customer should be told that before a non-approved engineer touches it.

Regulations & Standards